I want to search for...
Permit #2021080045
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7030-00650-0060 |
| Block: 00650 |
| Subdivision: 2154 - SECTION 30-ROYAL PALMS |
| Job Phone: (386)437-2929 |
| Location Address: 1 RANBER PL |
| Type: ME - MECHANICAL |
| Issue Date: 08/03/2021 |
| NOC: Unknown |
| Applicant name: JAMES KUYKENDALL |
| Owner: JOHNSTON HARVEY J & ALICE M H&W |
|
Address 1 RANBER PLACE PALM COAST, FL 32164 |
| Lot: 0060 |
| Contracted Stated Job Value: ¤5,900.00 |
| Job Description: REPLACE 3.5 15 SEER HVAC |
| Type: CN |
Contractor
AIR PROS OF CENTRAL FLORIDA LLC
| Status | Location Address | State License Number | Phone | Fax |
| CANCEL |
2550 US 1 NORTH SUITE 3 BUNNELL, FL 32110 |
CAC1815546 (Exp: 08/31/2022) | (386)437-2929 | (386)437-2942 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 10/26/2021 | FINAL APPROVED | CPISCITELLI |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION | |||
| HVAC FINAL | 09/02/2021 | Disapproved -FEE REQUIRED | CPISCITELLI |
| Note: THIS IS A REINSPECTION AHU calls for 45 AMP max @ 240V, 43 AMP Min. There is a 40 AMP in panel. | |||
| HVAC ROUGH | 09/02/2021 | CANCELLED BY INSPECTOR | CPISCITELLI |
| HVAC FINAL | 08/19/2021 | Disapproved -FEE REQUIRED | CPISCITELLI |
| Note: 1. Hole in ceiling around lineset needs to be sealed. 2. Need disconnect by AHU. Panel not in line of sight. 3. Heatstrip not marked on AHU could not verify breaker in panel. 3. Need to use tapcons on hurricane straps on ODU to pad. One has a regular screw |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 08/02/2021 | 08/03/2021 |
| Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 10/25/2021 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 09/01/2021 |
| SURCHARGE FS 533.721 | ¤2.00 | 08/03/2021 |
| SURCHARGE - FS 468.631 | ¤2.00 | 08/03/2021 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 08/03/2021 |
| INSPECTION - MECHANICAL | ¤60.00 | 08/03/2021 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 08/03/2021 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤206.50 |