I want to search for...
Permit #2021080544
Permit Details
Status: EXPIRED
| Parcel Id: 16-11-31-1260-00000-0080 |
| Block: 00000 |
| Subdivision: 2081 - Creekside Village at Grand Haven |
| Job Phone: 386-698-1033 |
| Location Address: 1 CREEKSIDE CT |
| Type: GA - GAS |
| Issue Date: 08/11/2021 |
| NOC: Unknown |
| Applicant name: THELMA JOANNA SAMS |
| Owner: TEBBANO MICHAEL D & SHELIA K H&W |
|
Address 1 CREEKSIDE CT PALM COAST, FL 32137 |
| Lot: 0080 |
| Contracted Stated Job Value: ¤900.00 |
| Job Description: RUN ABOUT 70 FT OF LINE FROM EXISTING GENERATOR TO RANGE |
| Type: CN |
Contractor
SAMS III LLC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
8222 S. ORANGE AVE CRESCENT CITY, FL 32112 |
LQ24872 (Exp: 09/16/2027) | 407-855-1903 |
Inspection History
| Type | Request Date | Result | Inspector |
| GAS FINAL | 04/25/2022 | Disapproved -FEE REQUIRED | MGIBSON |
| Note: REGULATOR VENT NEEDS TO BE 5' AWAY FROM IGNITION SOURCE '' GENERATOR '' ALSO A BOND WIRE IS REQUIRED FOR MULTIPLE APPLIANCES WITH-IN 70' FROM GAS LINE | |||
| GAS ROUGH | 02/14/2022 | APPROVED - AS NOTED | MGIBSON |
| Note: WILL NEED ACCESS TO HOME FOR GAS FINAL | |||
| GAS FINAL | |||
| Note: THIS IS A REINSPECTION REGULATOR VENT NEEDS TO BE 5' AWAY FROM IGNITION SOURCE '' GENERATOR '' ALSO A BOND WIRE IS REQUIRED FOR MULTIPLE APPLIANCES WITH-IN 70' FROM GAS LINE |
Review History
| Department | Status | Date In | Date Out |
| PLUM | COMPLETE | 08/10/2021 | 08/11/2021 |
| Note: Released By: HAROLD ALLEN - - HALLEN@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 08/10/2021 | 08/10/2021 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM No zoning review required to run lines only to existing generator. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| EXTENSION | ¤40.00 | 03/10/2022 |
| CONTRACTOR CHANGE | ¤40.00 | 03/10/2022 |
| SURCHARGE FS 533.721 | ¤2.00 | 08/11/2021 |
| SURCHARGE - FS 468.631 | ¤2.00 | 08/11/2021 |
| SITE PLAN 15 | ¤15.00 | 08/11/2021 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 08/11/2021 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 08/11/2021 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 08/11/2021 |
| REINSPECTION RESIDENTIAL | ¤40.00 | |
| Fees | Total Due: ¤40.00 | Total Paid: ¤221.50 |