I want to search for...

Permit #2021090139

Permit Details

Status: COED

Parcel Id: 07-11-31-7009-00180-0230
CONDITIONED SPACE: 1804 sqft
GARAGE: 490 sqft
OPENED PORCH (WITH ROOF) : 400 sqft
OPENED PORCH (WITH ROOF) : 28 sqft
Total Square Footage: 2722 sqft
Block: 00180
Subdivision: 2208 - SECTION 9-FLORIDA PARK
Job Phone: 321-610-3924
Location Address: 29 FAIRCHILD LN
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 10/27/2021
NOC: RECORDED
Applicant name: KENNETH WAYNE CAMBELL JR
Owner: LS-VEH 2 LLC

Address

4885 N WICKHAM ROAD

MELBOURNE, FL 32940

Lot: 0230
Contracted Stated Job Value: ¤250,000.00
Job Description: SINGLE FAMILY RESIDENCE
Type: CN

Contractor

MERCEDES PREMIER HOMES LLC
Status Location Address Mailing Address State License Number Phone
CANCEL

4885 N WICKHAM RD

MELBOURNE, FL 32940

SUITE 101

MELBOURNE, FL 32940

CBC058803 (Exp: 08/31/2022) 321-610-3924

Sub Contractors

SANTOS L HERNANDEZ
Status Location Address State License Number Phone Fax
ACTIVE

946 SHADDICK DRIVE

ORANGE CITY, FL 32763

CCC1328011 (Exp: 08/31/2026) 386-218-4942 386-218-4937
ZACHARY PETER BOERA
Status Location Address State License Number Phone
CANCEL

7225 SANDSCOVE COURT, SUITE 1

WINTER PARK, FL 32792

CAC1817652 (Exp: 08/31/2022) 407-629-6920
JEFFREY TROY SABAKA
Status Location Address State License Number Phone Fax
ACTIVE

2191 DEERWOOD ACRES DR

ST AUGUSTINE, FL 32084

CFC1427439 (Exp: 08/31/2026) 904-838-2218 904-819-0965
JOSEPH C WRIGHT
Status Location Address Mailing Address State License Number Phone Fax
ACTIVE

15 HARGROVE LANE

PALM COAST, FL 32137

UNIT 3 D

PALM COAST, FL 32137

EC13003278 (Exp: 08/31/2026) 386-447-9644 386-447-9633

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 07/13/2022 FINAL APPROVED AGAETANO
Note: THIS IS A REINSPECTION 1. Need dedicated circuits for Dishwasher (needs to be on outlet under the sink). Interlock device is not acceptable, outlet must be in the adjacent cabinet. NEC 210.52 (B) 1, 2, and 3. NEC 210.52 (B) 1, 2, and 3. 2. Interlock nuts are not installed on AC unit. 3. Range hood not installed.
BLD - BUILDING FINAL 07/12/2022 Disapproved - NO FEE AGAETANO
Note: 1. Need dedicated circuits for Dishwasher (needs to be on outlet under the sink). Interlock device is not acceptable, outlet must be in the adjacent cabinet. NEC 210.52 (B) 1, 2, and 3. NEC 210.52 (B) 1, 2, and 3. 2. Interlock nuts are not installed on AC unit. 3. Range hood not installed.
ROW - FINAL APRON (AFTER POUR) 07/12/2022 APPROVED - AS NOTED EMADISON
Note: THIS IS A REINSPECTION ** EVERYTHING LOOKS GOOD AT THE TIME OF THE INSPECTION ** NEED TO FILL CORE TEST HOLES IN DRFIVEWAY AND DRIVEWAY APRON Inspector Notes from Inspection 9270 ** SOD NEEDS TO BE PUT IN SWALE /ROW ON RIGHT AND BY POWER POLE ON THE LEFT SIDE BEFORE STORMWATER ROW FINAL ** NEED TO FILL HOLES IN DRIVEWAY WHERE CORE TEST WAS DONE PRIOR TO APRON FINAL THIS IS A REINSPECTION ** DRIVEWAY POURED WITHOUT A PRE-POUR INSPECTION DONE. EM New inspection due to canceled inspection THIS IS A REINSPECTION 6/16/22 - This Driveway Culvert Elevation just happened to be correct after the pour. To verify the depth, the builder was directed to have 3 'core' tests done both in the ROW and the upper part of the driveway. All showed the proper depth of concrete was poured. This was a first time offense and therefore being Approved As-noted. Next time the entire driveway to the ROW will have to be pulled and replaced.
U-CROSS CONNECTION 07/11/2022 APPROVED DHANEY
ROW - STORMWATER FINAL 07/11/2022 APPROVED - AS NOTED EMADISON
Note: THIS IS A REINSPECTION ** 07/11/22 CORRECTIONS MADE EVERYTHING LOOKS GOOD AT THE TIME OF THE INSPECTION ** SWALE ACROSS STREET WHERE JOB SITE DUMPSTER WAS LOCATED NEEDS TO BE REPAIRED TO MATCH EXISTING GRADE AND SODDED ** SOD NEEDS TO BE PUT DOWN ON RIGHT SIDE IN IN ROW AND LEFT SIDE BY POWER POLE ** NEED TO FILL CORE TEST HOLES IN DRIVEWAY AND DRIVEWAY APRON Inspector Notes from Inspection 9270 ** SOD NEEDS TO BE PUT IN SWALE /ROW ON RIGHT AND BY POWER POLE ON THE LEFT SIDE BEFORE STORMWATER ROW FINAL ** NEED TO FILL HOLES IN DRIVEWAY WHERE CORE TEST WAS DONE PRIOR TO APRON FINAL THIS IS A REINSPECTION ** DRIVEWAY POURED WITHOUT A PRE-POUR INSPECTION DONE. EM New inspection due to canceled inspection THIS IS A REINSPECTION 6/16/22 - This Driveway Culvert Elevation just happened to be correct after the pour. To verify the depth, the builder was directed to have 3 'core' tests done both in the ROW and the upper part of the driveway. All showed the proper depth of concrete was poured. This was a first time offense and therefore being Approved As-noted. Next time the entire driveway to the ROW will have to be pulled and replaced.
U -UTILITY RESIDENTIAL FINAL 06/28/2022 FINAL APPROVED JHARDING
ROW - STORMWATER FINAL 06/28/2022 Disapproved -FEE REQUIRED EMADISON
Note: ** SWALE ACROSS STREET WHERE JOB SITE DUMPSTER WAS LOCATED NEEDS TO BE REPAIRED TO MATCH EXISTING GRADE AND SODDED ** SOD NEEDS TO BE PUT DOWN ON RIGHT SIDE IN IN ROW AND LEFT SIDE BY POWER POLE ** NEED TO FILL CORE TEST HOLES IN DRIVEWAY AND DRIVEWAY APRON Inspector Notes from Inspection 9270 ** SOD NEEDS TO BE PUT IN SWALE /ROW ON RIGHT AND BY POWER POLE ON THE LEFT SIDE BEFORE STORMWATER ROW FINAL ** NEED TO FILL HOLES IN DRIVEWAY WHERE CORE TEST WAS DONE PRIOR TO APRON FINAL THIS IS A REINSPECTION ** DRIVEWAY POURED WITHOUT A PRE-POUR INSPECTION DONE. EM New inspection due to canceled inspection THIS IS A REINSPECTION 6/16/22 - This Driveway Culvert Elevation just happened to be correct after the pour. To verify the depth, the builder was directed to have 3 'core' tests done both in the ROW and the upper part of the driveway. All showed the proper depth of concrete was poured. This was a first time offense and therefore being Approved As-noted. Next time the entire driveway to the ROW will have to be pulled and replaced.
ROW - FINAL APRON (AFTER POUR) 06/28/2022 Disapproved -FEE REQUIRED EMADISON
Note: ** NEED TO FILL CORE TEST HOLES IN DRFIVEWAY AND DRIVEWAY APRON Inspector Notes from Inspection 9270 ** SOD NEEDS TO BE PUT IN SWALE /ROW ON RIGHT AND BY POWER POLE ON THE LEFT SIDE BEFORE STORMWATER ROW FINAL ** NEED TO FILL HOLES IN DRIVEWAY WHERE CORE TEST WAS DONE PRIOR TO APRON FINAL THIS IS A REINSPECTION ** DRIVEWAY POURED WITHOUT A PRE-POUR INSPECTION DONE. EM New inspection due to canceled inspection THIS IS A REINSPECTION 6/16/22 - This Driveway Culvert Elevation just happened to be correct after the pour. To verify the depth, the builder was directed to have 3 'core' tests done both in the ROW and the upper part of the driveway. All showed the proper depth of concrete was poured. This was a first time offense and therefore being Approved As-noted. Next time the entire driveway to the ROW will have to be pulled and replaced.
ROW FIELD SURVEY /GRADING CERTIFICATION 06/27/2022 APPROVED - AS NOTED EMADISON
Note: Inspector Notes from Inspection 9270 ** SOD NEEDS TO BE PUT IN SWALE /ROW ON RIGHT AND BY POWER POLE ON THE LEFT SIDE BEFORE STORMWATER ROW FINAL ** NEED TO FILL HOLES IN DRIVEWAY WHERE CORE TEST WAS DONE PRIOR TO APRON FINAL THIS IS A REINSPECTION ** DRIVEWAY POURED WITHOUT A PRE-POUR INSPECTION DONE. EM New inspection due to canceled inspection THIS IS A REINSPECTION 6/16/22 - This Driveway Culvert Elevation just happened to be correct after the pour. To verify the depth, the builder was directed to have 3 'core' tests done both in the ROW and the upper part of the driveway. All showed the proper depth of concrete was poured. This was a first time offense and therefore being Approved As-noted. Next time the entire driveway to the ROW will have to be pulled and replaced.
FINAL SURVEY (OFFICE USE ONLY) 06/27/2022 APPROVED EMADISON
ROW- PRE-APRON (PRE-POUR) 06/16/2022 APPROVED - AS NOTED RGROSS
Note: THIS IS A REINSPECTION ** DRIVEWAY POURED WITHOUT A PRE-POUR INSPECTION DONE. EM New inspection due to canceled inspection THIS IS A REINSPECTION 6/16/22 - This Driveway Culvert Elevation just happened to be correct after the pour. To verify the depth, the builder was directed to have 3 'core' tests done both in the ROW and the upper part of the driveway. All showed the proper depth of concrete was poured. This was a first time offense and therefore being Approved As-noted. Next time the entire driveway to the ROW will have to be pulled and replaced.
ROW- PRE-APRON (PRE-POUR) 06/15/2022 Disapproved -FEE REQUIRED EMADISON
Note: ** DRIVEWAY POURED WITHOUT A PRE-POUR INSPECTION DONE. EM New inspection due to canceled inspection THIS IS A REINSPECTION
ROW- PRE-APRON (PRE-POUR) 06/09/2022 CANCELLED BY APPLICANT WEB
Note: THIS IS A REINSPECTION
ROW- PRE-APRON (PRE-POUR) 06/07/2022 CANCELLED BY APPLICANT EMADISON
ELECTRIC - EARLY POWER 05/27/2022 APPROVED AGAETANO
SECOND FLOOR SLAB 05/27/2022 APPROVED AGAETANO
ROW - DRAINAGE 05/05/2022 APPROVED RGROSS
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION ADDED ON 4/25/2022 10:51:14 AM Inspection results: CTroha 4/25/2022 Silt fence is down at the right rear corner stormwater is draining into the neighboring lots. Correction: 1) Re-install siltfencing 2) grade the property to drain to the front swale. 4/29/22 - Swale still blocking storm water flow. Next Inspection 5/5/22.
ROW - DRAINAGE 04/29/2022 Disapproved -FEE REQUIRED RGROSS
Note: THIS IS A REINSPECTION ADDED ON 4/25/2022 10:51:14 AM Inspection results: CTroha 4/25/2022 Silt fence is down at the right rear corner stormwater is draining into the neighboring lots. Correction: 1) Re-install siltfencing 2) grade the property to drain to the front swale. 4/29/22 - Swale still blocking storm water flow. Next Inspection 5/5/22.
ROW - DRAINAGE 04/25/2022 Disapproved -FEE REQUIRED CTROHA
Note: Inspection results: CTroha 4/25/2022 Silt fence is down at the right rear corner stormwater is draining into the neighboring lots. Correction: 1) Re-install siltfencing 2) grade the property to drain to the front swale.
ROW - DRAINAGE 04/22/2022 APPROVED RGROSS
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION the silt fence is falling down in a couple of places and draining onto adjacent lots that needs to be corrected asap next inspection 4/18/22 4/18/22 - Port-o-let in the swale. Silt fence not installed correctly in the ROW. Sediment Washout into the neighbor's lawn. Next inspection 4/22/22.
ROW - DRAINAGE 04/18/2022 Disapproved -FEE REQUIRED RGROSS
Note: THIS IS A REINSPECTION the silt fence is falling down in a couple of places and draining onto adjacent lots that needs to be corrected asap next inspection 4/18/22 4/18/22 - Port-o-let in the swale. Silt fence not installed correctly in the ROW. Sediment Washout into the neighbor's lawn. Next inspection 4/22/22.
ROW - DRAINAGE 04/12/2022 Disapproved -FEE REQUIRED KRUTH
Note: the silt fence is falling down in a couple of places and draining onto adjacent lots that needs to be corrected asap next inspection 4/18/22
INSULATION 03/18/2022 APPROVED AGAETANO
Note: THIS IS A REINSPECTION No insulation has been installed.
INSULATION 03/16/2022 Disapproved -FEE REQUIRED AGAETANO
Note: No insulation has been installed.
LATH/BRICK/ WATER BARRIER 03/15/2022 APPROVED AGAETANO
ALL ROUGH 03/07/2022 APPROVED AGAETANO
Note: THIS IS A REINSPECTION Head test not holding water.
ALL ROUGH 03/04/2022 Disapproved - NO FEE AGAETANO
Note: Head test not holding water.
ROOF VALLEY & METAL 02/17/2022 APPROVED AGAETANO
Note: THIS IS A REINSPECTION missing drip edge on left side of house
ROOF VALLEY & METAL 02/16/2022 Disapproved -FEE REQUIRED LMILLER
Note: missing drip edge on left side of house
ROOF SHEATHING / BRACES/TIES/DOWN CELL 02/07/2022 APPROVED AGAETANO
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION 1. Simpson 201 missing in multiple areas at entry. 2. A3A and A4A engineered members missing. 02-04-2022 1. Please install H2.5 at entry at indicated on drawings. 2. Remove nails at wall sheathing at left side of entry.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 02/04/2022 Disapproved -FEE REQUIRED AGAETANO
Note: THIS IS A REINSPECTION 1. Simpson 201 missing in multiple areas at entry. 2. A3A and A4A engineered members missing. 02-04-2022 1. Please install H2.5 at entry at indicated on drawings. 2. Remove nails at wall sheathing at left side of entry.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 02/02/2022 Disapproved - NO FEE AGAETANO
Note: 1. Simpson 201 missing in multiple areas at entry. 2. A3A and A4A engineered members missing.
WALL SHEATHING 02/01/2022 APPROVED AGAETANO
U - SEWER TIE IN 01/25/2022 APPROVED MGIBSON
FOUND SURVEY APPROVED (OFFICE) 12/15/2021 APPROVED TBAKER
TIE BEAM / LINTEL 12/10/2021 APPROVED KSANDOE
WATER METER INSTALLATION REQUEST 12/08/2021 APPROVED CSTONE
MONOLITHIC SLAB 11/24/2021 APPROVED DCUSHING
PLUMBING 1ST ROUGH UNDERGROUND 11/18/2021 APPROVED MGIBSON
GRAVITY SEWER TEST 11/18/2021 APPROVED MGIBSON

Review History

Department Status Date In Date Out
ENGIN1 COMPLETE 06/14/2022 06/14/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
SW1 COMPLETE 06/14/2022 06/21/2022
Note: Released By: PARREN FLANAGAN - (386)986-2392 - PFLANAGAN@PALMCOASTGOV.COM
ZON COMPLETE 06/14/2022 06/14/2022
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
MECH COMPLETE 03/04/2022 03/07/2022
Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM
ENGIN1 COMPLETE 12/14/2021 12/15/2021
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON COMPLETE 12/14/2021 12/14/2021
Note: Released By: CINDY CHIRI-GONCALVES - - CGONCALVES@PALMCOASTGOV.COM
BLD COMPLETE 09/20/2021 09/20/2021
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
BLD HOLD 09/03/2021 09/03/2021
Note: Held By: FRED REODICA - (386)986-4734 - FREODICA@PALMCOASTGOV.COM Product approval per F.S. 553.842: FL14170 - R14 for garage door - provide specific product approval number as there are several models, specifications and design pressures to meet the design requirements as indicated on Structural Sheet S001.
CUSVC COMPLETE 09/03/2021 09/08/2021
Note: Released By: HALEIGH HAND - -
ELEC COMPLETE 09/03/2021 09/03/2021
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ENGIN1 COMPLETE 09/03/2021 09/03/2021
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
LOCATE COMPLETE 09/03/2021 09/03/2021
Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM
MECH COMPLETE 09/03/2021 09/03/2021
Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM
SW1 COMPLETE 09/03/2021 09/14/2021
Note: Released By: KALEN RUTH - (386)566-1273 - KKRUTH@PALMCOASTGOV.COM
ZON COMPLETE 09/03/2021 09/08/2021
Note: Released By: CINDY CHIRI-GONCALVES - - CGONCALVES@PALMCOASTGOV.COM
SWALE COMPLETE 09/03/2021 11/17/2021
Note: Released By: JOHN HOWARD - - JHOWARD@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
PLAN REVIEW - REVISION ¤32.50 07/13/2022
REINSPECTION RESIDENTIAL ¤40.00 07/13/2022
REINSPECTION RESIDENTIAL ¤40.00 07/13/2022
REINSPECTION RESIDENTIAL ¤40.00 07/13/2022
SW ENG - INSPECTION 20 ¤20.00 07/13/2022
SW ENG - INSPECTION 20 ¤20.00 07/13/2022
SW ENG - INSPECTION 20 ¤20.00 07/13/2022
SW ENG - INSPECTION 20 ¤20.00 07/13/2022
SW ENG - INSPECTION 20 ¤20.00 07/13/2022
SW ENG - INSPECTION 20 ¤20.00 07/13/2022
SW ENG REINSPECTION 20 ¤20.00 07/13/2022
SW ENG REINSPECTION 20 ¤20.00 07/13/2022
SW ENG REINSPECTION 30 ¤30.00 07/13/2022
SW ENG - REVIEW 20 ¤20.00 10/27/2021
SW ENG RES REVIEW 200 ¤200.00 10/27/2021
3% TRANS IMPACT FEE CREDIT (¤51.54) 10/27/2021
SEWER INSPECTION ¤25.00 10/27/2021
SEWER CAPITAL FACILITY ¤4,664.55 10/27/2021
WATER CAPITAL FACILITY FEE ¤3,424.45 10/27/2021
SITE PLAN 30 ¤30.00 10/27/2021
METER - DEPOSIT ¤60.00 10/27/2021
WATER- TURN ON ¤25.00 10/27/2021
ADMINISTRATIVE RESIDENTIAL ¤30.00 10/27/2021
INSPECTION - RESIDENTIAL ¤687.50 10/27/2021
PLAN REVIEW - RESIDENTIAL ¤195.00 10/27/2021
SW ENG INSPECTION 60 ¤60.00 10/27/2021
SW ENG PRE APRON ¤30.00 10/27/2021
CONNECTION FEES ¤1,017.83 10/27/2021
3% FIRE IMPACT FEE CREDIT (¤11.01) 10/27/2021
IMPACT FEE FIRE ¤367.00 10/27/2021
IMPACT FEE PARKS ¤1,199.12 10/27/2021
IMPACT FEE SCHOOL ¤3,600.00 10/27/2021
IMPACT FEE TRANSPORTATION ¤1,718.00 10/27/2021
WATER -IRRIGATION INSPECTION ¤25.00 10/27/2021
3% PARKS IMPACT FEE CREDIT (¤35.97) 10/27/2021
SURCHARGE FS 533.721 ¤9.67 10/27/2021
SURCHARGE - FS 468.631 ¤14.50 10/27/2021
SW ENG - FOUNDATION SURVEY ¤20.00 10/27/2021
Fees Total Due: ¤0.00 Total Paid: ¤17,666.60