I want to search for...
Permit #2021111182
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7006-00100-0130 |
| Total Square Footage: 1600 sqft |
| Block: 00100 |
| Subdivision: 2213 - SECTION 6-FLORIDA PARK |
| Job Phone: (386)446-1711 |
| Location Address: 25 FLAGLER PL |
| Type: ME - MECHANICAL |
| Issue Date: 11/29/2021 |
| NOC: Unknown |
| Applicant name: RICHARD THOMAS PINDELL JR |
| Owner: LEWIS DARLENE ANN |
|
Address 25 FLAGLER PLACE PALM COAST, FL 32137 |
| Lot: 0130 |
| Contracted Stated Job Value: ¤6,263.00 |
| Job Description: HVAC LIKE FOR LIKE TONNAGE |
| Type: CN |
Contractor
PINSKI MECHANICAL, LLC
| Status | Location Address | State License Number | Phone |
| INACTIVE |
1500 BEVILLE ROAD STE 606-236 DAYTONA BEACH, FL 32114 |
CAC1814876 (Exp: 08/31/2024) | (386)446-1711 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 12/10/2021 | FINAL APPROVED | CPISCITELLI |
| Note: THIS IS A REINSPECTION | |||
| HVAC FINAL | 12/02/2021 | Disapproved -FEE REQUIRED | CPISCITELLI |
| Note: 1. AHU (Downflow) unit is not serviceable. Unit needs to be turned for service and to change filter. 2. Flex duct on downflow unit needs to be sealed to plenum on top of unit and sealed at return plenum next to unit. 3. Both AHUs in closet call for 30 AMP breakers. There are 20 AMP in panel for both 4. ODUs for call for 20 AMP max. There are 30 AMP in panel. Both units 5. There is no permit for new 3.5 ton system installed. Seperate permit needs to be obtained. and called in for inspection. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 12/09/2021 |
| SURCHARGE FS 533.721 | ¤2.00 | 11/29/2021 |
| SURCHARGE - FS 468.631 | ¤2.00 | 11/29/2021 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 11/29/2021 |
| INSPECTION - MECHANICAL | ¤60.00 | 11/29/2021 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤134.00 |