I want to search for...

Permit #2021120011

Permit Details

Status: EXPIRED

Parcel Id: 07-11-31-7022-00040-0150
Block: 00040
Subdivision: 2217 - SECTION 22-WYNNFIELD
Job Phone: (386)437-2929
Location Address: 316 WESTHAMPTON DR
Type: ME - MECHANICAL
Issue Date: 12/02/2021
NOC: Unknown
Applicant name: JAMES KUYKENDALL
Owner: WHITE ELVIS R & ROSE C H&W

Address

316 WESTHAMPTON DRIVE

PALM COAST, FL 32164

Lot: 0150
Contracted Stated Job Value: ¤5,600.00
Job Description: REPLACE HVAC 4 TON 15 SEER
Type: CN

Contractor

AIR PROS OF CENTRAL FLORIDA LLC
Status Location Address State License Number Phone Fax
CANCEL

2550 US 1 NORTH SUITE 3

BUNNELL, FL 32110

CAC1815546 (Exp: 08/31/2022) (386)437-2929 (386)437-2942

Inspection History

Type Request Date Result Inspector
HVAC FINAL 04/14/2022 Disapproved -FEE REQUIRED CPISCITELLI
Note: NOT COMPLETED FROM PREVIOUS INSPECTION 2. Disconnect in closet does not open. The door has to open at 90 degrees. 3. AHRI paperwork does not match equipment installed. Provide correct paperwork
HVAC FINAL 12/02/2021 Disapproved -FEE REQUIRED CPISCITELLI
Note: 1. AHU calls for 45 AMP. There is a 50 AMP in panel. 2. Disconnect in closet open. The door has to open at 90 degrees. 3. AHRI paperwork does not match equipment installed. Provide correct paperwork
HVAC FINAL
Note: THIS IS A REINSPECTION NOT COMPLETED FROM PREVIOUS INSPECTION 2. Disconnect in closet does not open. The door has to open at 90 degrees. 3. AHRI paperwork does not match equipment installed. Provide correct paperwork

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 04/13/2022
ADMINISTRATIVE RESIDENTIAL ¤30.00 12/02/2021
INSPECTION - MECHANICAL ¤60.00 12/02/2021
SURCHARGE FS 533.721 ¤2.00 12/02/2021
SURCHARGE - FS 468.631 ¤2.00 12/02/2021
REINSPECTION RESIDENTIAL ¤40.00
Fees Total Due: ¤40.00 Total Paid: ¤134.00