I want to search for...
Permit #2021120468
Permit Details
Status: COED
| Parcel Id: 07-11-31-7023-00310-0110 |
| CONDITIONED SPACE: 1840 sqft |
| GARAGE: 674 sqft |
| OPENED PORCH (WITH ROOF) : 209 sqft |
| Total Square Footage: 2723 sqft |
| Block: 00310 |
| Subdivision: 2191 - SECTION 23-WYNNFIELD |
| Job Phone: 386-445-3405 |
| Location Address: 3 WHITE PL |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 01/20/2022 |
| NOC: RECORDED |
| Applicant name: JAY DARREN CURBOW |
| Owner: BLUE WATER HOMES INC |
|
Address UNIT 1 PALM COAST, FL 32137 |
|
Address 4881 PALM COAST PKWY PALM COAST, FL 32137 |
| Lot: 0110 |
| Contracted Stated Job Value: ¤215,364.00 |
| Job Description: Single Family Residence |
| Type: CN |
Contractor
BLUE WATER HOMES INC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
4881 PALM COAST PARKWAY NW UNIT 1 PALM COAST, FL 32137 |
CBC1258679 (Exp: 08/31/2026) | 386-445-3405 |
Sub Contractors
WILLIAM FRANK DUDLEY JR.
| Status | Location Address | State License Number | Phone |
| ACTIVE |
P.O. BOX 978 Bunnell, FL 32110 |
EC0003177 (Exp: 08/31/2026) | (386)437-3068 |
JACK DOUGLAS LANIER
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
485 COMMERCE WAY LONGWOOD , FL 32750 |
CCC058022 (Exp: 08/31/2026) | (321)441-2300 | (321)441-2313 |
JEFFREY TROY SABAKA
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
2191 DEERWOOD ACRES DR ST AUGUSTINE, FL 32084 |
CFC1427439 (Exp: 08/31/2026) | 904-838-2218 | 904-819-0965 |
BRETT CHRISTIAN GIBSON
| Status | Location Address | State License Number | Phone |
| ACTIVE |
250 SEGOVIA RD ST AUGUSTINE, FL 32086 |
CAC1818423 (Exp: 08/31/2026) | 904-229-8131 |
Inspection History
| Type | Request Date | Result | Inspector |
| BLD - BUILDING FINAL | 09/22/2022 | FINAL APPROVED | MKRASKI |
| Note: | |||
| BLD - BUILDING FINAL | 09/21/2022 | Disapproved - NO FEE | MKRASKI |
| Note: 1. Outside outlets not working 2. Outlet by ODU missing w/p cover 3. Hood vent for range missing trim 4. AHU has wrong size breaker installed Stopped inspection not ready | |||
| U-CROSS CONNECTION | 09/20/2022 | APPROVED - AS NOTED | LFITZGERALD |
| Note: no irrigation-no cross connection | |||
| U -UTILITY RESIDENTIAL FINAL | 09/20/2022 | FINAL APPROVED | LFITZGERALD |
| ROW - FINAL APRON (AFTER POUR) | 09/16/2022 | APPROVED | GBERTOLA |
| Note: AT THE TIME OF THE INSPECTION EVERYTHING LOOK GOOD | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 09/16/2022 | Disapproved - NO FEE | GBERTOLA |
| Note: The tolerance along side lot lines is no more than 20 feet flat, with positive fall on each side. Positive fall is considered to be 0.10 feet in 20 feet. The minimum fall from the rear property line to the front is 0.50 feet. CHECK FINAL SURVEY FOR REMARKS | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 09/16/2022 | APPROVED | GBERTOLA |
| Note: | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 09/16/2022 | APPROVED | GBERTOLA |
| ROW - STORMWATER FINAL | 09/16/2022 | APPROVED | GBERTOLA |
| Note: AT THE TIME OF THE INSPECTION EVERYTHING LOOK GOOD | |||
| ELECTRIC - EARLY POWER | 08/30/2022 | APPROVED - AS NOTED | MKRASKI |
| Note: Emailed FPL @ 1:50 PM 8/30/22 | |||
| ROW- PRE-APRON (PRE-POUR) | 08/22/2022 | APPROVED - AS NOTED | GBERTOLA |
| Note: 0822/22=correction were made AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS BEFORE POURING. MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL ............................................................................................................................................................................................................. 08/19/22=CULVERT PIPE IS OUT OF TOLERANCE BOTH END. PLEASE RESET THE PIPE ACCORDING SWALE PLAN – FOOTERS HAVE WASHED IN NEED TO BE DUG OUT REPAIR THE WASH OUT ON THE DRIVEWAY .................................................................................................................................................................................................................................. 08/18/22=I THINK THE SWALE PLAN IS WRONG I NEED TO ASK THE CITY TO REVISE THE SWALE PLAN DETAIL ................................................................................................................................................................................................................................... 08/09/22= ELBOW NEED AT THIS LOCATION ,22.5 degree elbow Culvert Adjustments entering a Cul de sac Sec 42-42 Sec 300.E | |||
| ROW- PRE-APRON (PRE-POUR) | 08/19/2022 | Disapproved - NO FEE | GBERTOLA |
| Note: 08/19/22=CULVERT PIPE IS OUT OF TOLERANCE BOTH END. PLEASE RESET THE PIPE ACCORDING SWALE PLAN – FOOTERS HAVE WASHED IN NEED TO BE DUG OUT REPAIR THE WASH OUT ON THE DRIVEWAY .................................................................................................................................................................................................................................. 08/18/22=I THINK THE SWALE PLAN IS WRONG I NEED TO ASK THE CITY TO REVISE THE SWALE PLAN DETAIL ................................................................................................................................................................................................................................... 08/09/22= ELBOW NEED AT THIS LOCATION ,22.5 degree elbow Culvert Adjustments entering a Cul de sac Sec 42-42 Sec 300.E | |||
| ROW- PRE-APRON (PRE-POUR) | 08/18/2022 | Disapproved - NO FEE | GBERTOLA |
| Note: 08/18/22=I THINK THE SWALE PLAN IS WRONG I NEED TO ASK THE CITY TO REVISE THE SWALE PLAN DETAIL ................................................................................................................................................................................................................................... 08/09/22= ELBOW NEED AT THIS LOCATION ,22.5 degree elbow Culvert Adjustments entering a Cul de sac Sec 42-42 Sec 300.E | |||
| ROW- PRE-APRON (PRE-POUR) | 08/09/2022 | Disapproved -FEE REQUIRED | GBERTOLA |
| Note: 08/09/22= ELBOW NEED AT THIS LOCATION ,22.5 degree elbow Culvert Adjustments entering a Cul de sac Sec 42-42 Sec 300.E | |||
| U - SEWER TIE IN | 07/28/2022 | APPROVED | MGIBSON |
| PEP TANK INSTALLATION REQUEST | 07/06/2022 | APPROVED | CSTONE |
| INSULATION | 07/01/2022 | APPROVED | KSANDOE |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION 1. Garage wood stud wall needs to be sealed around edges and base plate 2. Nail plate missing for water line for master bathroom shower head 6/30/22 Incorrect protection for water heater lines from foundation. FBC P2603.2.1 Sealing of garage wood stud wall is insufficient. Needs to be completely sealed. | |||
| INSULATION | 06/30/2022 | Disapproved -FEE REQUIRED | KSANDOE |
| Note: THIS IS A REINSPECTION 1. Garage wood stud wall needs to be sealed around edges and base plate 2. Nail plate missing for water line for master bathroom shower head 6/30/22 Incorrect protection for water heater lines from foundation. FBC P2603.2.1 Sealing of garage wood stud wall is insufficient. Needs to be completely sealed. | |||
| INSULATION | 06/29/2022 | Disapproved - NO FEE | MKRASKI |
| Note: 1. Garage wood stud wall needs to be sealed around edges and base plate 2. Nail plate missing for water line for master bathroom shower head | |||
| ALL ROUGH | 06/27/2022 | Disapproved - NO FEE | MKRASKI |
| Note: THIS IS A REINSPECTION 1. Truss A20 tie down strap still not installed 2. Load bearing wood frame garage wall must be 100% on slab 3. Power for island coming into kitchen wall needs to be sealed | |||
| ALL ROUGH | 06/27/2022 | APPROVED | KSANDOE |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION 1. Truss A20 tie down strap still not installed 2. Load bearing wood frame garage wall must be 100% on slab 3. Power for island coming into kitchen wall needs to be sealed | |||
| LATH/BRICK/ WATER BARRIER | 06/24/2022 | APPROVED | MKRASKI |
| ALL ROUGH | 06/23/2022 | Disapproved - NO FEE | MKRASKI |
| Note: 1. Truss A20 tie down strap still not installed 2. Load bearing wood frame garage wall must be 100% on slab 3. Power for island coming into kitchen wall needs to be sealed 4. Main electrcial panel can not have ground screw bonding grounds and nuetrals. ground and neutrals are only tied together at first means of disconnect (meter main) | |||
| GRAVITY SEWER TEST | 06/21/2022 | APPROVED | MGIBSON |
| Note: Inspector Notes from Inspection 2060 FIRST ROUGH APPROVED ALSO GRAVITY SEWER C/M TO SCHEDULE IT FOR MONDAY, NOT INSPECTORS RESPONSABILITY TO SCHEDULE THEIR INSPECTIONS | |||
| WALL SHEATHING | 04/27/2022 | APPROVED | MKRASKI |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 04/27/2022 | APPROVED - AS NOTED | MKRASKI |
| Note: Missing tie down strap on truss A20 Check on all rough | |||
| ROOF VALLEY & METAL | 04/21/2022 | APPROVED | MKRASKI |
| TIE BEAM / LINTEL | 03/28/2022 | APPROVED | FWILLIS |
| FOUND SURVEY APPROVED (OFFICE) | 03/08/2022 | APPROVED | TBAKER |
| MONOLITHIC SLAB | 02/23/2022 | APPROVED | MKRASKI |
| PLUMBING 1ST ROUGH UNDERGROUND | 02/18/2022 | APPROVED - AS NOTED | MGIBSON |
| Note: FIRST ROUGH APPROVED ALSO GRAVITY SEWER C/M TO SCHEDULE IT FOR MONDAY, NOT INSPECTORS RESPONSABILITY TO SCHEDULE THEIR INSPECTIONS | |||
| WATER METER INSTALLATION REQUEST | 01/27/2022 | APPROVED | CSTONE |
Review History
| Department | Status | Date In | Date Out |
| ENGIN1 | COMPLETE | 03/04/2022 | 03/07/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 03/04/2022 | 03/04/2022 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| BADMIN | HOLD | 01/26/2022 | 01/26/2022 |
| Note: Held By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM For future NOC's, please enter the legal description in the description of property field. the Section block and lot, or the Subdivision, block and lot , etc. CONTRACTORS NEWSFLASH _____________________________________________________________________________________ Notice of Commencement Submittals October 7, 2021 We have seen an increase of incorrect Notice of Commencements submitted. It has typically been for the same issues and is causing frustrations for applicants. • DESCRIPTION OF PROPERTY - description sufficient for identification of the real property to be improved. The description should include the legal description of the property and also include the street address and tax folio number. • DESCRIPTION OF IMPROVEMENT - this should be a brief description of your project - single family residence, swimming pool, driveway, HVAC, screen enclosure, interior alterations, etc. • CONTRACTOR NAME - The name and address of the contractor – this is to match the application provided by the license holder. • NOTARIZATION – the signed name must be the name on the Notice of Commencement. The notary must print the name of the person’s signature (s) they are notarizing, identify if they are personally known or produce identification, sign their name and place their seal on the document. • NOT LEGIBLE – we are increasingly receiving documents that are not legible. We receive many blurry and / or dark copies. Please be sure your scanned copy is legible or it will not be accepted. The document submitted to the Building Division must match the document that has been recorded. Any changes to the document must be re-recorded. Changes to the recorded copy without being re-recorded are not acceptable. References: Florida Statute 713.13 Notice of Commencement http://www.leg.state.fl.us/Statutes/index.cfm?App_mode=Display_Statute&URL=0700-0799/0713/Sections/0713.13.html Florida Statute 117 Notaries Public http://www.leg.state.fl.us/statutes/index.cfm?App_mode=Display_Statute&URL=0100-0199/0117/0117.html | |||
| BADMIN | COMPLETE | 01/26/2022 | 01/26/2022 |
| Note: Released By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM | |||
| SWALE | COMPLETE | 12/10/2021 | 02/07/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 12/09/2021 | 12/14/2021 |
| Note: Released By: FRED REODICA - (386)986-4734 - FREODICA@PALMCOASTGOV.COM | |||
| CUSVC | COMPLETE | 12/09/2021 | 12/14/2021 |
| Note: Released By: HALEIGH HAND - - | |||
| ELEC | COMPLETE | 12/09/2021 | 12/10/2021 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ENGIN1 | COMPLETE | 12/09/2021 | 12/10/2021 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| LOCATE | COMPLETE | 12/09/2021 | 12/14/2021 |
| Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 12/09/2021 | 12/10/2021 |
| Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM | |||
| SW1 | COMPLETE | 12/09/2021 | 12/16/2021 |
| Note: Released By: KALEN RUTH - (386)566-1273 - KRUTH@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 12/09/2021 | 12/10/2021 |
| Note: Released By: CINDY CHIRI-GONCALVES - - CGONCALVES@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 09/23/2022 |
| IMPACT FEE FIRE | ¤388.65 | 09/23/2022 |
| IMPACT FEE PARKS | ¤1,455.13 | 09/23/2022 |
| SW ENG REINSPECTION 30 | ¤30.00 | 09/23/2022 |
| IMPACT FEE TRANSPORTATION | ¤1,718.00 | 09/23/2022 |
| WATER -IRRIGATION INSPECTION | ¤25.00 | 01/20/2022 |
| SURCHARGE FS 533.721 | ¤8.43 | 01/20/2022 |
| SURCHARGE - FS 468.631 | ¤12.65 | 01/20/2022 |
| SW ENG - FOUNDATION SURVEY | ¤20.00 | 01/20/2022 |
| SW ENG INSPECTION 80 | ¤80.00 | 01/20/2022 |
| SW ENG PRE APRON | ¤30.00 | 01/20/2022 |
| SW ENG - REVIEW 20 | ¤20.00 | 01/20/2022 |
| SW ENG RES REVIEW 200 | ¤200.00 | 01/20/2022 |
| SEWER CREDIT | (¤1,342.00) | 01/20/2022 |
| SEWER INSPECTION | ¤25.00 | 01/20/2022 |
| SEWER CAPITAL FACILITY | ¤4,939.76 | 01/20/2022 |
| WATER CAPITAL FACILITY FEE | ¤3,626.50 | 01/20/2022 |
| SITE PLAN 30 | ¤30.00 | 01/20/2022 |
| IMPACT FEE SCHOOL | ¤3,600.00 | 01/20/2022 |
| CONNECTION FEES | ¤1,077.88 | 01/20/2022 |
| METER - DEPOSIT | ¤60.00 | 01/20/2022 |
| WATER- TURN ON | ¤25.00 | 01/20/2022 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 01/20/2022 |
| INSPECTION - RESIDENTIAL | ¤594.00 | 01/20/2022 |
| PLAN REVIEW - RESIDENTIAL | ¤168.01 | 01/20/2022 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤16,862.01 |