I want to search for...

Permit #2021120479

Permit Details

Status: COED

Parcel Id: 07-11-31-7057-00690-0070
CONDITIONED SPACE: 2517 sqft
GARAGE: 484 sqft
OPENED PORCH (WITH ROOF) : 380 sqft
OPENED PORCH (WITH ROOF) : 146 sqft
Total Square Footage: 3527 sqft
Block: 00690
Subdivision: -
Job Phone: 386-447-7007
Location Address: 150 ULYSSES TR
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 02/10/2022
NOC: RECORDED
Applicant name: MAXIM TARANNIK
Owner: HOU SAING PAUL & DANY CHIM

Address

150 ULYSSES TR

PALM COAST, FL 32164

Lot: 0070
Contracted Stated Job Value: ¤411,500.00
Job Description: Single Family Home
Type: CN

Contractor

GOLDEN MAGNOLIA, INC
Status Location Address State License Number Phone
INACTIVE

1 ROCKEFELLER DRIVE

PALM COAST, FL 32164

RR282811984 (Exp: 08/31/2025) 386-447-7007

Sub Contractors

GARY LLOYD SHEFFIELD
Status Location Address State License Number Phone
ACTIVE

48 EAGLE LAKES DRIVE

FLAGLER BEACH, FL 32136

CAC048127 (Exp: 08/31/2026) 386-597-3280
DUSTIN L ESTEP
Status Location Address State License Number Phone Fax
ACTIVE

2041 N HIAWASSEE RD

APOPKA, FL 32703

CCC1330971 (Exp: 08/31/2026) 407-702-0206 352-988-6629
GLEN WILLIAM KEHLE
Status Location Address State License Number Phone Fax
ACTIVE

P. O. Box 353511

BUNNELL, FL 32110

CFC057241 (Exp: 08/31/2026) (386) 447-4249 (386) 437-8488
FERNANDO MEZA SR
Status Location Address State License Number Phone
ACTIVE

457 CHELSEA PLACE AVE

ORMOND BEACH, FL 32174

EC13003906 (Exp: 08/31/2026) 386-241-5211

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 09/06/2024 FINAL APPROVED BTAYLOR
Note: 8/26/2024 - PREVIOUS INSPECTION NOTES 8/23/2024 - PREVIOUS INSPECTION NOTES R319.1 Address cannot be seen from street. It's laying in the driveway. Need energy calcs on site for inspection. Check garage door bucking anchor detail 8/19/2024 - PREVIOUS INSPECTION NOTES 8-19-24 Wrong lock box code can not access house. 1. No address. 2. No back flow stoppers on water spickets. 3. Bay windows are not even finshed tyvek is still visable. House has not been fully inspected due to house being locked. 8-26-24 1. Rear guest bath not finished. 2. A/C can not be in front of window. 3. No drip pan under air handler. 4 Energy cals do not match.
BLD - BUILDING FINAL 08/26/2024 Disapproved -FEE REQUIRED BTAYLOR
Note: 8/23/2024 - PREVIOUS INSPECTION NOTES R319.1 Address cannot be seen from street. It's laying in the driveway. Need energy calcs on site for inspection. Check garage door bucking anchor detail 8/19/2024 - PREVIOUS INSPECTION NOTES 8-19-24 Wrong lock box code can not access house. 1. No address. 2. No back flow stoppers on water spickets. 3. Bay windows are not even finshed tyvek is still visable. House has not been fully inspected due to house being locked. 8-26-24 1. Rear guest bath not finished. 2. A/C can not be in front of window. 3. No drip pan under air handler. 4 Energy cals do not match.
BLD - BUILDING FINAL 08/23/2024 Disapproved - NO FEE KSANDOE
Note: R319.1 Address cannot be seen from street. It's laying in the driveway. Need energy calcs on site for inspection. Check garage door bucking anchor detail 8/19/2024 - PREVIOUS INSPECTION NOTES 8-19-24 Wrong lock box code can not access house. 1. No address. 2. No back flow stoppers on water spickets. 3. Bay windows are not even finshed tyvek is still visable. House has not been fully inspected due to house being locked.
BLD - BUILDING FINAL 08/19/2024 Disapproved -FEE REQUIRED BTAYLOR
Note: 8-19-24 Wrong lock box code can not access house. 1. No address. 2. No back flow stoppers on water spickets. 3. Bay windows are not even finshed tyvek is still visable. House has not been fully inspected due to house being locked.
ELECTRIC - EARLY POWER 07/15/2024 APPROVED RMARTIN
Note: 7/10/2024 - PREVIOUS INSPECTION NOTES 7/10/24: 1). Missing fixture or blank cover plate for attic light fixture.
ELECTRIC - EARLY POWER 07/10/2024 Disapproved - NO FEE RSIMS
Note: 7/10/24: 1). Missing fixture or blank cover plate for attic light fixture.
ROW - FINAL APRON (AFTER POUR) 03/18/2024 APPROVED TPOLACEK
Note: PIPE IS GOOD, CUTS ARE MADE, CULVERT CLEAR, HOT PATCH COMPLETE. AT THE TIME FROM THE TIME OF THE INSPECTION OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. Inspector Notes from Inspection 9465 THE DRAINAGE IN THE BACK SHOW THE WATER GOING ON TO THE RESERVE PARCEL TO THE RIGHT SO WITH THIS TRUE PASSING AS NOTED THAT IT NOT RUNNING ON TO A PRIVATE PROPERTY IT IS CITY'S DRAINAGE ------------------------------------------------------------------------ 3/4/2024 - PREVIOUS INSPECTION NOTES 3/4/24final survey need to be approved first THIS FINAL SURVEY NEEDS MORE INFO. SUBMIT A NEW ONE ACCORDING TO THE CITY REQUIREMENTS THIS IS A BOUNDARY SURVEY, WE NEED A TOPOGRAPHIC SURVEY ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 3/1/2024 - PREVIOUS INSPECTION NOTES 3/1/24 YOU MUST FIRST SUBMIT AND PASS A FINAL SURVEY INSPECTION BEFORE A FIELD SURVEY INSPECTION CAN BE SCHEDULED AND COMPLETED. PLEASE SUBMIT YOUR FINAL SURVEY FOR REVIEW. I WILL NOT FEE YO TODAY. Inspector Notes from Inspection 9270 6/16/23=AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS BEFORE POURING. MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 6/15/2023 - PREVIOUS INSPECTION NOTES 6/15/23=CULVERT PIPE IS OUT OF TOLERANCE BOTH END. PLEASE RESET THE CULVERT PIPE ACCORDING SWALE PLAN – ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 6/14/2023 - PREVIOUS INSPECTION NOTES Sec 300.E / 300.H NEED TO HAVE A MINIMUM 2" OF CONCRETE OVERT EXPOSED CUTS OF MITERS
ROW - STORMWATER FINAL 03/18/2024 APPROVED - AS NOTED TPOLACEK
Note: 03/18/24 MUST REMOVE PORTA POTTY FROM SITE . I WILL APPROVE AS NOTED AT TIME OF INSPECTION PORTA POTTY IS IN DRIVEWAY. AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVEDInspector Notes from Inspection 9465 THE DRAINAGE IN THE BACK SHOW THE WATER GOING ON TO THE RESERVE PARCEL TO THE RIGHT SO WITH THIS TRUE PASSING AS NOTED THAT IT NOT RUNNING ON TO A PRIVATE PROPERTY IT IS CITY'S DRAINAGE ------------------------------------------------------------------------ 3/4/2024 - PREVIOUS INSPECTION NOTES 3/4/24final survey need to be approved first THIS FINAL SURVEY NEEDS MORE INFO. SUBMIT A NEW ONE ACCORDING TO THE CITY REQUIREMENTS THIS IS A BOUNDARY SURVEY, WE NEED A TOPOGRAPHIC SURVEY ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 3/1/2024 - PREVIOUS INSPECTION NOTES 3/1/24 YOU MUST FIRST SUBMIT AND PASS A FINAL SURVEY INSPECTION BEFORE A FIELD SURVEY INSPECTION CAN BE SCHEDULED AND COMPLETED. PLEASE SUBMIT YOUR FINAL SURVEY FOR REVIEW. I WILL NOT FEE YO TODAY. Inspector Notes from Inspection 9270 6/16/23=AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS BEFORE POURING. MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 6/15/2023 - PREVIOUS INSPECTION NOTES 6/15/23=CULVERT PIPE IS OUT OF TOLERANCE BOTH END. PLEASE RESET THE CULVERT PIPE ACCORDING SWALE PLAN – ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 6/14/2023 - PREVIOUS INSPECTION NOTES Sec 300.E / 300.H NEED TO HAVE A MINIMUM 2" OF CONCRETE OVERT EXPOSED CUTS OF MITERS
U -UTILITY RESIDENTIAL FINAL 03/18/2024 FINAL APPROVED JHARDING
ROW FIELD SURVEY /GRADING CERTIFICATION 03/15/2024 APPROVED - AS NOTED PFLANAGAN
Note: THE DRAINAGE IN THE BACK SHOW THE WATER GOING ON TO THE RESERVE PARCEL TO THE RIGHT SO WITH THIS TRUE PASSING AS NOTED THAT IT NOT RUNNING ON TO A PRIVATE PROPERTY IT IS CITY'S DRAINAGE ------------------------------------------------------------------------ 3/4/2024 - PREVIOUS INSPECTION NOTES 3/4/24final survey need to be approved first THIS FINAL SURVEY NEEDS MORE INFO. SUBMIT A NEW ONE ACCORDING TO THE CITY REQUIREMENTS THIS IS A BOUNDARY SURVEY, WE NEED A TOPOGRAPHIC SURVEY ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 3/1/2024 - PREVIOUS INSPECTION NOTES 3/1/24 YOU MUST FIRST SUBMIT AND PASS A FINAL SURVEY INSPECTION BEFORE A FIELD SURVEY INSPECTION CAN BE SCHEDULED AND COMPLETED. PLEASE SUBMIT YOUR FINAL SURVEY FOR REVIEW. I WILL NOT FEE YO TODAY. Inspector Notes from Inspection 9270 6/16/23=AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS BEFORE POURING. MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 6/15/2023 - PREVIOUS INSPECTION NOTES 6/15/23=CULVERT PIPE IS OUT OF TOLERANCE BOTH END. PLEASE RESET THE CULVERT PIPE ACCORDING SWALE PLAN – ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 6/14/2023 - PREVIOUS INSPECTION NOTES Sec 300.E / 300.H NEED TO HAVE A MINIMUM 2" OF CONCRETE OVERT EXPOSED CUTS OF MITERS
ROW- FINAL SURVEY/GRADING CERTIFICATION 03/15/2024 APPROVED PFLANAGAN
Note: At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. ------------------------------------------------------------------------------- 3/12/2024 - PREVIOUS INSPECTION NOTES THIS FINAL SURVEY IS INCOMPLETE NEED TO PROVIDE THE FOLLOWING SO IT MEETS CITY'S STANDARDS. 1) NEED TO HAVE TWO INVERTS ELEVATIONS FOR THE CULVERT PIPE ALSO IT NEEDS TO BE WITH TO THE NEAREST .01. 2) THE FFE NEEDS TO BE TO THE NEAREST .01. 3) NEED TO HAVE 10' OFF SET ON ALL ADJACENT LOTS TO DETERMIND IF THE WATER WILL IMPACT THE LOT. 4) NEED TO HAVE CENTERLINE OF ROAD ELEVATIONS 5) NEED TO HAVE ELEVATIONS IN THE ROADSIDE SWALE -------------------------------------------------------------------------------------------------------------- 3/4/2024 - PREVIOUS INSPECTION NOTES THIS FINAL SURVEY NEEDS MORE INFO. SUBMIT A NEW ONE ACCORDING TO THE CITY REQUIREMENTS THIS IS A BOUNDARY SURVEY, WE NEED A TOPOGRAPHIC SURVEY
ROW- FINAL SURVEY/GRADING CERTIFICATION 03/12/2024 Disapproved -FEE REQUIRED PFLANAGAN
Note: THIS FINAL SURVEY IS INCOMPLETE NEED TO PROVIDE THE FOLLOWING SO IT MEETS CITY'S STANDARDS. 1) NEED TO HAVE TWO INVERTS ELEVATIONS FOR THE CULVERT PIPE ALSO IT NEEDS TO BE WITH TO THE NEAREST .01. 2) THE FFE NEEDS TO BE TO THE NEAREST .01. 3) NEED TO HAVE 10' OFF SET ON ALL ADJACENT LOTS TO DETERMIND IF THE WATER WILL IMPACT THE LOT. 4) NEED TO HAVE CENTERLINE OF ROAD ELEVATIONS 5) NEED TO HAVE ELEVATIONS IN THE ROADSIDE SWALE -------------------------------------------------------------------------------------------------------------- 3/4/2024 - PREVIOUS INSPECTION NOTES THIS FINAL SURVEY NEEDS MORE INFO. SUBMIT A NEW ONE ACCORDING TO THE CITY REQUIREMENTS THIS IS A BOUNDARY SURVEY, WE NEED A TOPOGRAPHIC SURVEY
ROW- FINAL SURVEY/GRADING CERTIFICATION 03/04/2024 Disapproved - NO FEE GBERTOLA
Note: THIS FINAL SURVEY NEEDS MORE INFO. SUBMIT A NEW ONE ACCORDING TO THE CITY REQUIREMENTS THIS IS A BOUNDARY SURVEY, WE NEED A TOPOGRAPHIC SURVEY
ROW FIELD SURVEY /GRADING CERTIFICATION 03/04/2024 Disapproved -FEE REQUIRED GBERTOLA
Note: 3/4/24final survey need to be approved first THIS FINAL SURVEY NEEDS MORE INFO. SUBMIT A NEW ONE ACCORDING TO THE CITY REQUIREMENTS THIS IS A BOUNDARY SURVEY, WE NEED A TOPOGRAPHIC SURVEY ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 3/1/2024 - PREVIOUS INSPECTION NOTES 3/1/24 YOU MUST FIRST SUBMIT AND PASS A FINAL SURVEY INSPECTION BEFORE A FIELD SURVEY INSPECTION CAN BE SCHEDULED AND COMPLETED. PLEASE SUBMIT YOUR FINAL SURVEY FOR REVIEW. I WILL NOT FEE YO TODAY. Inspector Notes from Inspection 9270 6/16/23=AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS BEFORE POURING. MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 6/15/2023 - PREVIOUS INSPECTION NOTES 6/15/23=CULVERT PIPE IS OUT OF TOLERANCE BOTH END. PLEASE RESET THE CULVERT PIPE ACCORDING SWALE PLAN – ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 6/14/2023 - PREVIOUS INSPECTION NOTES Sec 300.E / 300.H NEED TO HAVE A MINIMUM 2" OF CONCRETE OVERT EXPOSED CUTS OF MITERS
ROW FIELD SURVEY /GRADING CERTIFICATION 03/01/2024 Disapproved - NO FEE FSLADISH
Note: 3/1/24 YOU MUST FIRST SUBMIT AND PASS A FINAL SURVEY INSPECTION BEFORE A FIELD SURVEY INSPECTION CAN BE SCHEDULED AND COMPLETED. PLEASE SUBMIT YOUR FINAL SURVEY FOR REVIEW. I WILL NOT FEE YO TODAY. Inspector Notes from Inspection 9270 6/16/23=AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS BEFORE POURING. MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 6/15/2023 - PREVIOUS INSPECTION NOTES 6/15/23=CULVERT PIPE IS OUT OF TOLERANCE BOTH END. PLEASE RESET THE CULVERT PIPE ACCORDING SWALE PLAN – ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 6/14/2023 - PREVIOUS INSPECTION NOTES Sec 300.E / 300.H NEED TO HAVE A MINIMUM 2" OF CONCRETE OVERT EXPOSED CUTS OF MITERS
ROW- PRE-APRON (PRE-POUR) 06/16/2023 APPROVED - AS NOTED GBERTOLA
Note: 6/16/23=AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS BEFORE POURING. MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 6/15/2023 - PREVIOUS INSPECTION NOTES 6/15/23=CULVERT PIPE IS OUT OF TOLERANCE BOTH END. PLEASE RESET THE CULVERT PIPE ACCORDING SWALE PLAN – ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 6/14/2023 - PREVIOUS INSPECTION NOTES Sec 300.E / 300.H NEED TO HAVE A MINIMUM 2" OF CONCRETE OVERT EXPOSED CUTS OF MITERS
ROW- PRE-APRON (PRE-POUR) 06/15/2023 Disapproved -FEE REQUIRED GBERTOLA
Note: 6/15/23=CULVERT PIPE IS OUT OF TOLERANCE BOTH END. PLEASE RESET THE CULVERT PIPE ACCORDING SWALE PLAN – ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 6/14/2023 - PREVIOUS INSPECTION NOTES Sec 300.E / 300.H NEED TO HAVE A MINIMUM 2" OF CONCRETE OVERT EXPOSED CUTS OF MITERS
ROW- PRE-APRON (PRE-POUR) 06/14/2023 Disapproved -FEE REQUIRED PFLANAGAN
Note: Sec 300.E / 300.H NEED TO HAVE A MINIMUM 2" OF CONCRETE OVERT EXPOSED CUTS OF MITERS
U-CROSS CONNECTION 06/05/2023 APPROVED - AS NOTED JHARDING
Note: No irrigation, no cross connections.
GRAVITY SEWER TEST 06/05/2023 APPROVED MGIBSON
Note: Inspector Notes from Inspection 2060 REMOVE ALL HARDPAN BEFORE BACKFILLING PLUMBING DITCHES, WILL CHECK AT SLAB INSPECTION
U - SEWER TIE IN 06/05/2023 APPROVED MGIBSON
LATH/BRICK/ WATER BARRIER 04/24/2023 APPROVED FWILLIS
Note: 4/10/2023 - PREVIOUS INSPECTION NOTES 4-10-23 1. Haven't started.
LATH/BRICK/ WATER BARRIER 04/10/2023 Disapproved -FEE REQUIRED BTAYLOR
Note: 4-10-23 1. Haven't started.
INSULATION 04/03/2023 APPROVED BTAYLOR
ALL ROUGH 03/29/2023 APPROVED BTAYLOR
Note: 3/23/2023 - PREVIOUS INSPECTION NOTES 1/25/2023 - PREVIOUS INSPECTION NOTES need plans on site for inspection 107.3 3-23-23 1. Exhaust fans not wired in. 2. Water lines in room by garage need nail plates.
ALL ROUGH 03/23/2023 Disapproved - NO FEE BTAYLOR
Note: 1/25/2023 - PREVIOUS INSPECTION NOTES need plans on site for inspection 107.3 3-23-23 1. Exhaust fans not wired in. 2. Water lines in room by garage need nail plates.
ALL ROUGH 01/25/2023 Disapproved -FEE REQUIRED LMILLER
Note: need plans on site for inspection 107.3
ROOF VALLEY & METAL 12/13/2022 APPROVED BTAYLOR
ROOF SHEATHING / BRACES/TIES/DOWN CELL 11/28/2022 APPROVED BTAYLOR
Note: 11/2/2022 - PREVIOUS INSPECTION NOTES 11/2/2022: INSPECTION STOPPED - NOT A COMPLETE INSPECTION 1). Truss T24 is damaged & the simpson straps are not installed per manufacturer's requirement. 2). Garage door PT framing not installed per plan detail. * Engineer's letter for alternate strap detail has been accepted but not approved as of 11:18hrs. today. 10/24/2022 - PREVIOUS INSPECTION NOTES 10/20/2022 - PREVIOUS INSPECTION NOTES 10/12/2022 - PREVIOUS INSPECTION NOTES 10/11/2022 - PREVIOUS INSPECTION NOTES 10/5/2022 - PREVIOUS INSPECTION NOTES 10/4/2022 - PREVIOUS INSPECTION NOTES 10-4-22 House needs to be walked before calling in inspection. 1. Straps not attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again. 10-5-22 House needs to be walked before calling in inspection. 1. Straps not attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again. 10-11-22 Need to have project manger meet inspector on site to discuss issues. 10-20-22 House not ready Need to have project manger meet inspector on site to discuss issues. 10-24-22 It's not the inspectors job to make a punch list. House is still not ready.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 11/02/2022 Disapproved -FEE REQUIRED RSIMS
Note: 11/2/2022: INSPECTION STOPPED - NOT A COMPLETE INSPECTION 1). Truss T24 is damaged & the simpson straps are not installed per manufacturer's requirement. 2). Garage door PT framing not installed per plan detail. * Engineer's letter for alternate strap detail has been accepted but not approved as of 11:18hrs. today. 10/24/2022 - PREVIOUS INSPECTION NOTES 10/20/2022 - PREVIOUS INSPECTION NOTES 10/12/2022 - PREVIOUS INSPECTION NOTES 10/11/2022 - PREVIOUS INSPECTION NOTES 10/5/2022 - PREVIOUS INSPECTION NOTES 10/4/2022 - PREVIOUS INSPECTION NOTES 10-4-22 House needs to be walked before calling in inspection. 1. Straps not attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again. 10-5-22 House needs to be walked before calling in inspection. 1. Straps not attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again. 10-11-22 Need to have project manger meet inspector on site to discuss issues. 10-20-22 House not ready Need to have project manger meet inspector on site to discuss issues. 10-24-22 It's not the inspectors job to make a punch list. House is still not ready.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 10/24/2022 Disapproved -FEE REQUIRED BTAYLOR
Note: 10/20/2022 - PREVIOUS INSPECTION NOTES 10/12/2022 - PREVIOUS INSPECTION NOTES 10/11/2022 - PREVIOUS INSPECTION NOTES 10/5/2022 - PREVIOUS INSPECTION NOTES 10/4/2022 - PREVIOUS INSPECTION NOTES 10-4-22 House needs to be walked before calling in inspection. 1. Straps not attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again. 10-5-22 House needs to be walked before calling in inspection. 1. Straps not attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again. 10-11-22 Need to have project manger meet inspector on site to discuss issues. 10-20-22 House not ready Need to have project manger meet inspector on site to discuss issues. 10-24-22 It's not the inspectors job to make a punch list. House is still not ready.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 10/20/2022 Disapproved -FEE REQUIRED BTAYLOR
Note: 10/12/2022 - PREVIOUS INSPECTION NOTES 10/11/2022 - PREVIOUS INSPECTION NOTES 10/5/2022 - PREVIOUS INSPECTION NOTES 10/4/2022 - PREVIOUS INSPECTION NOTES 10-4-22 House needs to be walked before calling in inspection. 1. Straps not attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again. 10-5-22 House needs to be walked before calling in inspection. 1. Straps not attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again. 10-11-22 Need to have project manger meet inspector on site to discuss issues. 10-20-22 House not ready Need to have project manger meet inspector on site to discuss issues.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 10/12/2022 CANCELLED BY APPLICANT BTAYLOR
Note: 10/11/2022 - PREVIOUS INSPECTION NOTES 10/5/2022 - PREVIOUS INSPECTION NOTES 10/4/2022 - PREVIOUS INSPECTION NOTES 10-4-22 House needs to be walked before calling in inspection. 1. Straps not attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again. 10-5-22 House needs to be walked before calling in inspection. 1. Straps not attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again. 10-11-22 Need to have project manger meet inspector on site to discuss issues.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 10/11/2022 Disapproved -FEE REQUIRED BTAYLOR
Note: 10/5/2022 - PREVIOUS INSPECTION NOTES 10/4/2022 - PREVIOUS INSPECTION NOTES 10-4-22 House needs to be walked before calling in inspection. 1. Straps not attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again. 10-5-22 House needs to be walked before calling in inspection. 1. Straps not attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again. 10-11-22 Need to have project manger meet inspector on site to discuss issues.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 10/05/2022 Disapproved -FEE REQUIRED BTAYLOR
Note: 10/4/2022 - PREVIOUS INSPECTION NOTES 10-4-22 House needs to be walked before calling in inspection. 1. Straps not attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again. 10-5-22 House needs to be walked before calling in inspection. 1. Straps not attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 10/04/2022 Disapproved -FEE REQUIRED BTAYLOR
Note: 10-4-22 House needs to be walked before calling in inspection. 1. Straps nat attached to trusses. 2. Buckets not nailed. Inspection stopped need to start inspection over when called in again.
TIE BEAM / LINTEL 07/27/2022 APPROVED DCUSHING
Note: THIS IS A REINSPECTION Multiple dowels mssing and need to be drilled/block has already been marked
TIE BEAM / LINTEL 07/25/2022 Disapproved -FEE REQUIRED TSTAUFFACHER
Note: Multiple dowels mssing and need to be drilled/block has already been marked
FOUND SURVEY APPROVED (OFFICE) 04/26/2022 APPROVED TBAKER
MONOLITHIC SLAB 03/22/2022 APPROVED TSTAUFFACHER
Note: THIS IS A REINSPECTION Two pieces of vertical steel missing, marked with highlighter on plans
MONOLITHIC SLAB 03/21/2022 Disapproved - NO FEE TSTAUFFACHER
Note: Two pieces of vertical steel missing, marked with highlighter on plans
PLUMBING 1ST ROUGH UNDERGROUND 03/17/2022 APPROVED - AS NOTED MGIBSON
Note: REMOVE ALL HARDPAN BEFORE BACKFILLING PLUMBING DITCHES, WILL CHECK AT SLAB INSPECTION
WATER METER INSTALLATION REQUEST 03/02/2022 APPROVED CSTONE
Note: THIS IS A REINSPECTION ADDED ON 2/23/2022 8:07:23 AM dirt pile in way
WATER METER INSTALLATION REQUEST 02/22/2022 Disapproved - NO FEE CSTONE
Note: dirt pile in way

Review History

Department Status Date In Date Out
MECH COMPLETE 08/28/2024 09/04/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
BLD COMPLETE 11/22/2022 11/23/2022
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
BLD HOLD 10/28/2022 10/31/2022
Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code PLAN REVIEW COMMENTS: 1. Provide truss reactions and profiles for review. [A] 107.2
ENGIN1 COMPLETE 04/26/2022 04/26/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON COMPLETE 04/26/2022 04/26/2022
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
ZON COMPLETE 01/24/2022 01/24/2022
Note: Released By: CINDY CHIRI-GONCALVES - - CGONCALVES@PALMCOASTGOV.COM
BLD COMPLETE 01/24/2022 01/24/2022
Note: Released By: FRED REODICA - (386)986-4734 - FREODICA@PALMCOASTGOV.COM
ENGIN1 COMPLETE 01/24/2022 01/24/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
SW1 COMPLETE 01/24/2022 01/31/2022
Note: Released By: KALEN RUTH - (386)566-1273 - KRUTH@PALMCOASTGOV.COM
ZON HOLD 01/06/2022 01/06/2022
Note: Held By: CINDY CHIRI-GONCALVES - - CGONCALVES@PALMCOASTGOV.COM repeat comment Drive width Please provide the width of the drive way in front of the garage doorand the distance from garage door to turn around. Please look at site plan.
ELEC COMPLETE 01/06/2022 01/07/2022
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
BLD HOLD 01/06/2022 01/10/2022
Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM 1. Product approval specification sheet per F.S. 553.842: Second Request a. OK b. Asphalt shingles and underlayment FL Numbers do not match with those FL Numbers shown on Roofing Worksheet. Revised Product Approval calls out Owns Corning Roofing Shingles. Roofing Worksheet calls-out Certainteed.
SWALE COMPLETE 12/10/2021 02/08/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
BLD HOLD 12/09/2021 12/15/2021
Note: Held By: FRED REODICA - (386)986-4734 - FREODICA@PALMCOASTGOV.COM 1. Product approval specification sheet per F.S. 553.842: a. Garage door - FL 14170.9 shows design pressure (DP) in PSF is less than the required DP indicated on Sheet 1 of 10. b. Asphalt shingles and underlayment FL Numbers do not match with those FL Numbers shown on Roofing Worksheet.
CUSVC COMPLETE 12/09/2021 12/14/2021
Note: Released By: HALEIGH HAND - -
ELEC HOLD 12/09/2021 12/10/2021
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM Submit electric load calcs
ENGIN1 COMPLETE 12/09/2021 12/10/2021
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
LOCATE COMPLETE 12/09/2021 12/14/2021
Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM
MECH COMPLETE 12/09/2021 12/10/2021
Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM
SW1 COMPLETE 12/09/2021 12/16/2021
Note: Released By: KALEN RUTH - (386)566-1273 - KRUTH@PALMCOASTGOV.COM
ZON HOLD 12/09/2021 12/10/2021
Note: Held By: CINDY CHIRI-GONCALVES - - CGONCALVES@PALMCOASTGOV.COM Site plan: Set backs not clear in rear of home . drive way width not clear

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
CONTRACTOR CHANGE ¤20.00 09/06/2024
CONTRACTOR CHANGE ¤20.00 09/06/2024
CONTRACTOR CHANGE ¤40.00 09/06/2024
CONTRACTOR CHANGE ¤20.00 09/06/2024
PLAN REVIEW - REVISION ¤32.50 09/06/2024
PLAN REVIEW - REVISION ¤32.50 09/06/2024
REINSPECTION RESIDENTIAL ¤40.00 09/06/2024
REINSPECTION RESIDENTIAL ¤40.00 09/06/2024
REINSPECTION RESIDENTIAL ¤40.00 09/06/2024
REINSPECTION RESIDENTIAL ¤40.00 09/06/2024
REINSPECTION RESIDENTIAL ¤40.00 09/06/2024
REINSPECTION RESIDENTIAL ¤40.00 09/06/2024
REINSPECTION RESIDENTIAL ¤40.00 09/06/2024
REINSPECTION RESIDENTIAL ¤40.00 09/06/2024
REINSPECTION RESIDENTIAL ¤40.00 09/06/2024
REINSPECTION RESIDENTIAL ¤40.00 09/06/2024
REINSPECTION RESIDENTIAL ¤40.00 09/06/2024
SW ENG REINSPECTION 20 ¤20.00 09/06/2024
SW ENG REINSPECTION 30 ¤30.00 09/06/2024
SW ENG REINSPECTION 30 ¤30.00 09/06/2024
EXTENSION ¤40.00 09/06/2024
INSPECTION - RESIDENTIAL ¤1,133.00 02/10/2022
PLAN REVIEW - RESIDENTIAL ¤321.36 02/10/2022
METER - DEPOSIT ¤60.00 02/10/2022
WATER- TURN ON ¤25.00 02/10/2022
ADMINISTRATIVE RESIDENTIAL ¤30.00 02/10/2022
SW ENG - REVIEW 20 ¤20.00 02/10/2022
SW ENG RES REVIEW 200 ¤200.00 02/10/2022
3% TRANS IMPACT FEE CREDIT (¤51.54) 02/10/2022
SEWER CREDIT (¤1,466.00) 02/10/2022
SEWER INSPECTION ¤25.00 02/10/2022
SEWER CAPITAL FACILITY ¤4,939.76 02/10/2022
WATER CAPITAL FACILITY FEE ¤3,626.50 02/10/2022
SITE PLAN 30 ¤30.00 02/10/2022
CONNECTION FEES ¤1,077.88 02/10/2022
3% FIRE IMPACT FEE CREDIT (¤11.66) 02/10/2022
IMPACT FEE FIRE ¤388.65 02/10/2022
IMPACT FEE PARKS ¤1,455.13 02/10/2022
IMPACT FEE SCHOOL ¤3,600.00 02/10/2022
IMPACT FEE TRANSPORTATION ¤1,718.00 02/10/2022
WATER -IRRIGATION INSPECTION ¤25.00 02/10/2022
3% PARKS IMPACT FEE CREDIT (¤43.65) 02/10/2022
SURCHARGE FS 533.721 ¤15.53 02/10/2022
SURCHARGE - FS 468.631 ¤23.30 02/10/2022
SW ENG - FOUNDATION SURVEY ¤20.00 02/10/2022
SW ENG INSPECTION 80 ¤80.00 02/10/2022
SW ENG PRE APRON ¤30.00 02/10/2022
Fees Total Due: ¤0.00 Total Paid: ¤17,996.26