I want to search for...

Permit #2022010413

Permit Details

Status: COED

Parcel Id: 07-11-31-7033-00260-0140
CONDITIONED SPACE: 2137 sqft
GARAGE: 491 sqft
PATIO/DECK (NO ROOF) : 225 sqft
OPENED PORCH (WITH ROOF) : 62 sqft
Total Square Footage: 2915 sqft
Block: 00260
Subdivision: 2184 - SECTION 33-ROYAL PALMS
Job Phone: 386-447-4151
Location Address: 17 RED BARN DR
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 01/26/2022
NOC: RECORDED
Applicant name: GENE WARREN SLONE
Owner: GORDON LESLIE & BEVERLY H&W

Address

15 RED BARN DR

PALM COAST, FL 32164

Lot: 0140
Contracted Stated Job Value: ¤400,000.00
Job Description: SINGLE FAMILY HOME
Type: CN

Contractor

FLORIDA GREEN CONSTRUCTION INC.
Status Location Address State License Number Phone
INACTIVE

870 E RETTA STREET

DELEON SPRINGS, FL 32130

CBC1260957 (Exp: 08/31/2026) 407-580-2657

Sub Contractors

JOHN EDWARD GAMBONE
Status Location Address Mailing Address State License Number Phone
ACTIVE

15 HARGROVE LN

PALM COAST, FL 32137

1G

PALM COAST, FL 32137

EC13006037 (Exp: 08/31/2026) 386-586-9144
ERIC FRANCO
Status Location Address Mailing Address State License Number Phone
INACTIVE

840 DELTONA BLVD

DELTONA, FL 32725

STE F2

DELTONA, FL 32725

CCC1327280 (Exp: 08/31/2026) 386-575-4007
KERRY DWAIN AYLESWORTH II
Status Location Address Mailing Address State License Number Phone
ACTIVE

2820 LEWIS SPEEDWAY

ST AUGUSTINE, FL 32084

STE B

ST AUGUSTINE, FL 32084

CAC1820713 (Exp: 08/31/2026) 904-342-5709
JONATHAN M PEARSON
Status Location Address State License Number Phone Fax
ACTIVE

209 N FORSYTH ST

BUNNELL, FL 32110

CFC1425941 (Exp: 08/31/2026) 386-597-0944 386-437-4996
JAMES DOUGLAS II
Status Location Address State License Number Phone
ACTIVE

357 SUNSET AVE

HOLLY HILL, FL 32117

21340 (Exp: 08/31/2026) 386-236-8005

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 12/22/2023 Disapproved - NO FEE JWALKER
Note: 1. Master bath closet the outlet has no power. 2. The gas water heater exhaust duct cannot be aluminum flex. M-802
BLD - BUILDING FINAL 12/22/2023 FINAL APPROVED JWALKER
Note: 12/22/2023 - PREVIOUS INSPECTION NOTES 1. Master bath closet the outlet has no power. 2. The gas water heater exhaust duct cannot be aluminum flex. M-802
TUB SET 12/13/2023 APPROVED MGIBSON
Note: 12/12/2023 - PREVIOUS INSPECTION NOTES House is locked 12/7/2023 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 2075 THIS WAS A VIRTUAL INSPECTION NEED PRESSURE BALANCE VALVE AT TUB SEAL TUB ROUGH BOX, NEED SPECS FOR MASTER SHOWER ALSO ON SITE AT NEXT TUB INSPECTION
TUB SET 12/12/2023 Disapproved - NO FEE KSANDOE
Note: House is locked 12/7/2023 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 2075 THIS WAS A VIRTUAL INSPECTION NEED PRESSURE BALANCE VALVE AT TUB SEAL TUB ROUGH BOX, NEED SPECS FOR MASTER SHOWER ALSO ON SITE AT NEXT TUB INSPECTION
TUB SET 12/07/2023 Disapproved -FEE REQUIRED MGIBSON
Note: Inspector Notes from Inspection 2075 THIS WAS A VIRTUAL INSPECTION NEED PRESSURE BALANCE VALVE AT TUB SEAL TUB ROUGH BOX, NEED SPECS FOR MASTER SHOWER ALSO ON SITE AT NEXT TUB INSPECTION
ROW - STORMWATER FINAL 11/22/2023 APPROVED - AS NOTED FSLADISH
Note: 11/22/23 PREVIOUS CORRECTIONS REQUESTED COMPLETED. At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. _________________________________________________________________________________________________________________________ 11/21/2023 - PREVIOUS INSPECTION NOTES 1) NEED TO CLEAN ALL DIRT OUT OF CULVERTS AND ON MITER ENDS 2) NEED TO PICK UP ALL TRASH IN LOT
U -UTILITY RESIDENTIAL FINAL 11/22/2023 FINAL APPROVED DHANEY
Note: 11/20/2023 - PREVIOUS INSPECTION NOTES Pep panel on house has not been connected to electric source yet .
U -UTILITY RESIDENTIAL FINAL 11/21/2023 Disapproved - NO FEE DHANEY
Note: Pep panel on house has not been connected to electric source yet .
U-CROSS CONNECTION 11/21/2023 APPROVED DHANEY
ROW - FINAL APRON (AFTER POUR) 11/21/2023 APPROVED PFLANAGAN
Note: At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved.
ROW - STORMWATER FINAL 11/21/2023 Disapproved -FEE REQUIRED PFLANAGAN
Note: 1) NEED TO CLEAN ALL DIRT OUT OF CULVERTS AND ON MITER ENDS 2) NEED TO PICK UP ALL TRASH IN LOT
ROW FIELD SURVEY /GRADING CERTIFICATION 11/20/2023 APPROVED GBERTOLA
Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. THIS INCLUDES BUT IS NOT LIMITED TO THE CULVERT PIPE ELEVATION FROM THE TIME OF THE INSPECTION APPROVAL TO THE CONCRETE POUR.
FINAL SURVEY (OFFICE USE ONLY) 11/17/2023 APPROVED GBERTOLA
Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. THIS INCLUDES BUT IS NOT LIMITED TO THE CULVERT PIPE ELEVATION FROM THE TIME OF THE INSPECTION APPROVAL TO THE CONCRETE POUR.
ELECTRIC - EARLY POWER 10/27/2023 APPROVED JWALKER
ROW- PRE-APRON (PRE-POUR) 09/06/2023 APPROVED - AS NOTED FSLADISH
Note: 09/06/23 FAR RIGHT DRIVEWAY APRON WING FORMBOARD NEEDS TO COME UP SLIGHTLY TO MAKE SURE THE FALL IS POSITIVE TO THE ROAD. IT IS BASICALLY A HAIR FROM BEING FLAT. NEEDS TO HAVE A FORWARD PITCH TOWARD THE ROAD. EVERYTHING ELSE LOOKS GOOD SO I WILL APPROVE THIS AS NOTED, IT IS YOUR RESPOSIBILTY TO MAKE SURE THERE IS POSITIVE PITCH. At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. This includes but is not limited to, the Culvert Pipe Elevation from the time of the inspection approval to the concrete pour. AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS BEFORE POURING. MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL
U - SEWER TIE IN 06/13/2023 APPROVED - AS NOTED MGIBSON
Note: THIS WAS A VIRTUAL INSPECTION
GRAVITY SEWER TEST 06/13/2023 APPROVED - AS NOTED MGIBSON
Note: THIS WAS A VIRTUAL INSPECTION
PEP TANK INSTALLATION REQUEST 05/10/2023 APPROVED CSTONE
LATH/BRICK/ WATER BARRIER 04/25/2023 APPROVED JWALKER
GAS ROUGH 04/18/2023 APPROVED JWALKER
Note: 4/12/2023 - PREVIOUS INSPECTION NOTES 4/4/2023 - PREVIOUS INSPECTION NOTES NO TEST ON GUAGE AND NOT BONDED BOND WIRE NOT RAN STILL
INSULATION 04/14/2023 APPROVED TSTAUFFACHER
Note: 4/12/2023 - PREVIOUS INSPECTION NOTES 4/12/23: This house only has spray foam insulation on roof sheathing and at garage wall. No fire blocking is complete yet. 1). 5ft. head pressure is still not holding. 2). Gas pipe along trusses is still not supported/anchored as required. Inspector Notes from Inspection 2420 1. 5' head test not holding water. 2. Gas piping no pressure on the test gauge. 3. Bath fan exhaust ducts need to be lifted off the ceiling for insulation fill and supported minimum of 4' o.c. 4. Install nail plates. Right side of kitchen window and right side bathroom at the top chords to protect the wiring. 5. The gas piping installed is not matching the approved gas riser. Please submitt a revison to the building department showing pipe size, length and material for appliances. The pipe will also need to be supported where it runs on the ceiling trusses. Please have revision submitted before insulation inspection. 6. Adding a tub set inspection for the jetted tub.
INSULATION 04/12/2023 Disapproved -FEE REQUIRED RSIMS
Note: 4/12/23: This house only has spray foam insulation on roof sheathing and at garage wall. No fire blocking is complete yet. 1). 5ft. head pressure is still not holding. 2). Gas pipe along trusses is still not supported/anchored as required. Inspector Notes from Inspection 2420 1. 5' head test not holding water. 2. Gas piping no pressure on the test gauge. 3. Bath fan exhaust ducts need to be lifted off the ceiling for insulation fill and supported minimum of 4' o.c. 4. Install nail plates. Right side of kitchen window and right side bathroom at the top chords to protect the wiring. 5. The gas piping installed is not matching the approved gas riser. Please submitt a revison to the building department showing pipe size, length and material for appliances. The pipe will also need to be supported where it runs on the ceiling trusses. Please have revision submitted before insulation inspection. 6. Adding a tub set inspection for the jetted tub.
GAS ROUGH 04/12/2023 Disapproved - NO FEE MGIBSON
Note: 4/4/2023 - PREVIOUS INSPECTION NOTES NO TEST ON GUAGE AND NOT BONDED BOND WIRE NOT RAN STILL
ALL ROUGH 04/05/2023 APPROVED - AS NOTED JWALKER
Note: 1. 5' head test not holding water. 2. Gas piping no pressure on the test gauge. 3. Bath fan exhaust ducts need to be lifted off the ceiling for insulation fill and supported minimum of 4' o.c. 4. Install nail plates. Right side of kitchen window and right side bathroom at the top chords to protect the wiring. 5. The gas piping installed is not matching the approved gas riser. Please submitt a revison to the building department showing pipe size, length and material for appliances. The pipe will also need to be supported where it runs on the ceiling trusses. Please have revision submitted before insulation inspection. 6. Adding a tub set inspection for the jetted tub.
GAS ROUGH 04/04/2023 Disapproved -FEE REQUIRED MGIBSON
Note: NO TEST ON GUAGE AND NOT BONDED
ELECTRIC-TUG 11/30/2022 APPROVED JMUNSON
WALL SHEATHING 07/21/2022 APPROVED JWALKER
ROOF SHEATHING / BRACES/TIES/DOWN CELL 07/21/2022 APPROVED - AS NOTED JWALKER
Note: Front entry, rear porch install blocking and hold down anchor / straps where the ridge board falls on the roof decking. Install support under over framed ridge above garage area. Rear. Truss T15 missing engineering, rear porch area. Missing hold down ties at truss JC1 and 3 left front garage.
ROOF VALLEY & METAL 07/13/2022 APPROVED JWALKER
ROOF SHEATHING 07/06/2022 APPROVED JWALKER
TIE BEAM / LINTEL 05/12/2022 APPROVED JWALKER
FOUND SURVEY APPROVED (OFFICE) 03/29/2022 APPROVED TBAKER
MONOLITHIC SLAB 02/25/2022 APPROVED JWALKER
PLUMBING 1ST ROUGH UNDERGROUND 02/22/2022 APPROVED MGIBSON
ELECTRIC TEMP POLE 02/08/2022 APPROVED - AS NOTED JMUNSON
Note: Emailed FPL at 8:47 am
WATER METER INSTALLATION REQUEST 01/31/2022 APPROVED CSTONE

Review History

Department Status Date In Date Out
MECH COMPLETE 11/27/2023 11/28/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ENGIN1 COMPLETE 07/26/2023 07/26/2023
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
SW1 COMPLETE 07/26/2023 07/31/2023
Note: Released By: ROBERT GROSS - (386)986-4769 - RGROSS@PALMCOASTGOV.COM
ZON COMPLETE 07/26/2023 07/26/2023
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
BLD COMPLETE 02/09/2023 02/14/2023
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
ENGIN1 COMPLETE 03/25/2022 03/29/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON COMPLETE 03/25/2022 03/25/2022
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
BLD COMPLETE 01/11/2022 01/13/2022
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
CUSVC COMPLETE 01/11/2022 01/18/2022
Note: Released By: HALEIGH HAND - -
ELEC COMPLETE 01/11/2022 01/12/2022
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ENGIN1 COMPLETE 01/11/2022 01/11/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
LOCATE COMPLETE 01/11/2022 01/12/2022
Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM
MECH COMPLETE 01/11/2022 01/12/2022
Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM
SW1 COMPLETE 01/11/2022 01/19/2022
Note: Released By: KALEN RUTH - (386)566-1273 - KRUTH@PALMCOASTGOV.COM
ZON COMPLETE 01/11/2022 01/11/2022
Note: Released By: CINDY CHIRI-GONCALVES - - CGONCALVES@PALMCOASTGOV.COM
SWALE COMPLETE 01/11/2022 03/09/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
PLAN REVIEW - REVISION ¤32.50 12/13/2023
REINSPECTION RESIDENTIAL ¤40.00 12/13/2023
REINSPECTION RESIDENTIAL ¤40.00 12/13/2023
REINSPECTION RESIDENTIAL ¤40.00 12/13/2023
SW ENG REINSPECTION 20 ¤20.00 12/13/2023
CONTRACTOR CHANGE ¤20.00 02/09/2023
3% FIRE IMPACT FEE CREDIT (¤11.66) 01/26/2022
IMPACT FEE FIRE ¤388.65 01/26/2022
IMPACT FEE PARKS ¤1,455.13 01/26/2022
IMPACT FEE SCHOOL ¤3,600.00 01/26/2022
IMPACT FEE TRANSPORTATION ¤1,764.00 01/26/2022
WATER -IRRIGATION INSPECTION ¤25.00 01/26/2022
3% PARKS IMPACT FEE CREDIT (¤43.65) 01/26/2022
SURCHARGE FS 533.721 ¤15.10 01/26/2022
SURCHARGE - FS 468.631 ¤22.65 01/26/2022
SW ENG - FOUNDATION SURVEY ¤20.00 01/26/2022
SW ENG INSPECTION 80 ¤80.00 01/26/2022
SW ENG PRE APRON ¤30.00 01/26/2022
CONNECTION FEES ¤1,077.88 01/26/2022
METER - DEPOSIT ¤60.00 01/26/2022
WATER- TURN ON ¤25.00 01/26/2022
ADMINISTRATIVE RESIDENTIAL ¤30.00 01/26/2022
INSPECTION - RESIDENTIAL ¤1,100.00 01/26/2022
PLAN REVIEW - RESIDENTIAL ¤312.00 01/26/2022
SW ENG - REVIEW 20 ¤20.00 01/26/2022
SW ENG RES REVIEW 200 ¤200.00 01/26/2022
3% TRANS IMPACT FEE CREDIT (¤52.92) 01/26/2022
SEWER CREDIT (¤1,342.00) 01/26/2022
SEWER INSPECTION ¤25.00 01/26/2022
SEWER CAPITAL FACILITY ¤4,939.76 01/26/2022
WATER CAPITAL FACILITY FEE ¤3,626.50 01/26/2022
SITE PLAN 30 ¤30.00 01/26/2022
Fees Total Due: ¤0.00 Total Paid: ¤17,588.94