I want to search for...
Permit #2022010623
Permit Details
Status: COED
| Parcel Id: 07-11-31-7034-01490-0180 |
| CONDITIONED SPACE: 2295 sqft |
| GARAGE: 538 sqft |
| OPENED PORCH (WITH ROOF) : 201 sqft |
| OPENED PORCH (WITH ROOF) : 229 sqft |
| Total Square Footage: 3263 sqft |
| Block: 01490 |
| Subdivision: 2165 - SECTION 34-EASTHAMPTON |
| Job Phone: 321-501-4617 |
| Location Address: 35 EDITH POPE DR |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 02/17/2022 |
| NOC: RECORDED |
| Applicant name: JAMES FUCETOLA III |
| Owner: PALM COAST COMMUNITIES, LLC |
|
Address PO BOX 22547 SAT SIMONS, GA 31522 |
| Lot: 0180 |
| Contracted Stated Job Value: ¤215,000.00 |
| Job Description: Single Family Residence |
| Type: CN |
Contractor
PALM COAST COMMUNITIES LLC
| Status | Location Address | State License Number | Phone |
| INACTIVE |
PO BOX 22547 PALM COAST, FL 32164 |
CBC1262878 (Exp: 08/31/2026) | 321-501-4617 |
Sub Contractors
WILLIAM FRANK DUDLEY JR.
| Status | Location Address | State License Number | Phone |
| ACTIVE |
P.O. BOX 978 Bunnell, FL 32110 |
EC0003177 (Exp: 08/31/2026) | (386)437-3068 |
JEFFREY TROY SABAKA
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
2191 DEERWOOD ACRES DR ST AUGUSTINE, FL 32084 |
CFC1427439 (Exp: 08/31/2026) | 904-838-2218 | 904-819-0965 |
GARY LLOYD SHEFFIELD
| Status | Location Address | State License Number | Phone |
| ACTIVE |
48 EAGLE LAKES DRIVE FLAGLER BEACH, FL 32136 |
CAC048127 (Exp: 08/31/2026) | 386-597-3280 |
OLEG BELINSKIY
| Status | Location Address | State License Number | Phone |
| ACTIVE |
19 PINE CIRCLE DRIVE19 PALM COAST, FL 32167 |
CCC1325974 (Exp: 08/31/2026) | 386-263-7906 |
Inspection History
| Type | Request Date | Result | Inspector |
| BLD - BUILDING FINAL | 08/09/2022 | FINAL APPROVED | TSTAUFFACHER |
| ROW - FINAL APRON (AFTER POUR) | 08/09/2022 | APPROVED | PFLANAGAN |
| ROW - STORMWATER FINAL | 08/09/2022 | APPROVED - AS NOTED | PFLANAGAN |
| Note: NOTE TO INSPECTOR NEED TO MAKE SURE THAT ALL WATER IS NOT GOING INTO PEP TANK --------------------------------------------------------------------------------------------------------------------------------- 8/9/22 PEP TANK IS FIXED PASSING A NOTED CM NEED TO PUT SOD DOWN IN RIGHT OF WAY BECAUSE OF DUMPSTER AND PORTER JOHN | |||
| U -UTILITY RESIDENTIAL FINAL | 08/09/2022 | FINAL APPROVED | JHARDING |
| ROW FIELD SURVEY /GRADING CERTIFICATION | 08/08/2022 | Disapproved - NO FEE | PFLANAGAN |
| Note: NEED TO MAKE THE DRAINAGE AT PEP TANK GO AROUND IT NOT OVER IT INLESS YOU GET A LID THAT IS SEALED It will not be permissible for any drainage feature to directly discharge into a sanitary system. (C) PEP Tank lid elevations must be greater than the adjacent sod elevation.oDrainage features must be contoured around, not over, the PEP tank lid. Design and Specifications Guidelines for Low Pressure Sewer Systems, FDEP, June 1981, Chapter ,(A)(8) | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 08/08/2022 | APPROVED | PFLANAGAN |
| Note: 8/8/22 TALK CM AND HE IS GOING TO REROUTE THE WATER AROUND PEP TANK PASSING AS NOTED SO THEY CAN CALL ALL THE FINAL INSPECTIONS WE WILL MAKE SURE IT IS DONE BEFORE PASS THE FINAL ROW. ---------------------------------------------------------------------------------------------------------------------------- NEED TO MAKE THE DRAINAGE AT PEP TANK GO AROUND IT NOT OVER IT INLESS YOU GET A LID THAT IS SEALED It will not be permissible for any drainage feature to directly discharge into a sanitary system. (C) PEP Tank lid elevations must be greater than the adjacent sod elevation.oDrainage features must be contoured around, not over, the PEP tank lid. Design and Specifications Guidelines for Low Pressure Sewer Systems, FDEP, June 1981, Chapter ,(A)(8) | |||
| FINAL SURVEY (OFFICE USE ONLY) | 08/08/2022 | APPROVED | PFLANAGAN |
| U-CROSS CONNECTION | 07/29/2022 | APPROVED | DHANEY |
| ELECTRIC - EARLY POWER | 07/19/2022 | APPROVED - AS NOTED | JMUNSON |
| Note: Emailed FPL at 10:09 am | |||
| U - SEWER TIE IN | 07/13/2022 | APPROVED | KSANDOE |
| ROW- PRE-APRON (PRE-POUR) | 06/29/2022 | APPROVED - AS NOTED | PFLANAGAN |
| Note: IT'S THE CONTRACTORS RESPONSIBILITY TO CHECK THE ELEVATION OF CULVERT PIPE BEFORE POUR CONCRETE | |||
| ROW- PRE-APRON (PRE-POUR) | 06/28/2022 | CANCELLED BY APPLICANT | PFLANAGAN |
| PEP TANK INSTALLATION REQUEST | 06/02/2022 | APPROVED | CSTONE |
| INSULATION | 05/26/2022 | APPROVED | JWALKER |
| ALL ROUGH | 05/20/2022 | APPROVED | JWALKER |
| Note: THIS IS A REINSPECTION Contractor asked if inspector could meet at the job to go over what is needed for All rough inspection. | |||
| ALL ROUGH | 05/17/2022 | Disapproved - NO FEE | JWALKER |
| Note: Contractor asked if inspector could meet at the job to go over what is needed for All rough inspection. | |||
| LATH/BRICK/ WATER BARRIER | 05/12/2022 | APPROVED | JWALKER |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 05/06/2022 | APPROVED | DCUSHING |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 05/04/2022 | CANCELLED BY APPLICANT | AWS_IVR |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION THIS IS A REINSPECTION Need a full set of approved drawings and the truss engineering packet on site for inspection. Unable to inspect tie downs, bracing and engineering. Was able to walk roof sheating . Roof sheating passes. inspection Down Cells pass inspection., 4.26.22 - Truss T21 - No strap @ front CMU wall end T03 - No strap @ Front entry CMU wall end 4/29/22 The bearing wall garage area. Missing all SP4 hold down anchors. None of the truss lading on the bearing wall have hold down anchors installed.Have engineer supplies detail for truss to bearing wall connections. As well as bearing wall height and required blocking for wall over 8' Truss TGO1 above the front entry area has no connectors, have engineering provide details on how this gride truss is to connect to the CMU wall. The valley overframing garage area missing H 2.5 anchors. | |||
| ROOF VALLEY & METAL | 05/03/2022 | APPROVED | JWALKER |
| ELECTRIC TEMP POLE | 05/03/2022 | APPROVED - AS NOTED | MKRASKI |
| Note: Emailed FPL @ 2:20 PM | |||
| ELECTRIC TEMP POLE | 04/29/2022 | Disapproved - NO FEE | MKRASKI |
| Note: Temp pole needs bracing | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 04/29/2022 | Disapproved - NO FEE | JWALKER |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION Need a full set of approved drawings and the truss engineering packet on site for inspection. Unable to inspect tie downs, bracing and engineering. Was able to walk roof sheating . Roof sheating passes. inspection Down Cells pass inspection., 4.26.22 - Truss T21 - No strap @ front CMU wall end T03 - No strap @ Front entry CMU wall end 4/29/22 The bearing wall garage area. Missing all SP4 hold down anchors. None of the truss lading on the bearing wall have hold down anchors installed.Have engineer supplies detail for truss to bearing wall connections. As well as bearing wall height and required blocking for wall over 8' Truss TGO1 above the front entry area has no connectors, have engineering provide details on how this gride truss is to connect to the CMU wall. The valley overframing garage area missing H 2.5 anchors. | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 04/26/2022 | Disapproved -FEE REQUIRED | DCUSHING |
| Note: THIS IS A REINSPECTION Need a full set of approved drawings and the truss engineering packet on site for inspection. Unable to inspect tie downs, bracing and engineering. Was able to walk roof sheating . Roof sheating passes. inspection Down Cells pass inspection., 4.26.22 - Truss T21 - No strap @ front CMU wall end T03 - No strap @ Front entry CMU wall end | |||
| WALL SHEATHING | 04/25/2022 | APPROVED | JWALKER |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 04/25/2022 | Disapproved - NO FEE | JWALKER |
| Note: Need a full set of approved drawings and the truss engineering packet on site for inspection. Unable to inspect tie downs, bracing and engineering. Was able to walk roof sheating . Roof sheating passes. inspection Down Cells pass inspection., | |||
| FOUND SURVEY APPROVED (OFFICE) | 04/21/2022 | APPROVED | TBAKER |
| TIE BEAM / LINTEL | 04/11/2022 | APPROVED | LMILLER |
| MONOLITHIC SLAB | 03/29/2022 | APPROVED | RMARTIN |
| GRAVITY SEWER TEST | 03/25/2022 | APPROVED | JWALKER |
| Note: THIS IS A REINSPECTION Cannot pass due to the 3" quarter bend used noted in rough plumbing inspection. The fitting will need to be corrected and system refilled. | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 03/25/2022 | APPROVED | JWALKER |
| Note: THIS IS A REINSPECTION 3" quarter bend cannot be used hoizontal to horizontal | |||
| GRAVITY SEWER TEST | 03/24/2022 | Disapproved - NO FEE | JWALKER |
| Note: Cannot pass due to the 3" quarter bend used noted in rough plumbing inspection. The fitting will need to be corrected and system refilled. | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 03/24/2022 | Disapproved - NO FEE | JWALKER |
| Note: 3" quarter bend cannot be used hoizontal to horizontal | |||
| WATER METER INSTALLATION REQUEST | 03/02/2022 | APPROVED | CSTONE |
| Note: THIS IS A REINSPECTION ADDED ON 2/25/2022 8:19:09 AM lot not cleared | |||
| WATER METER INSTALLATION REQUEST | 02/23/2022 | Disapproved - NO FEE | CSTONE |
| Note: lot not cleared |
Review History
| Department | Status | Date In | Date Out |
| BADMIN | INFORMATION | 07/28/2022 | 07/28/2022 |
| Note: Marked INFORMATION By: LIBBY MUSGROVE - - LMUSGROVE@PALMCOASTGOV.COM Wrong File Name Uploaded file name was not correct - Example: Site plan=site plan (do not add anything to the file names like numbers.) | |||
| ENGIN1 | COMPLETE | 04/21/2022 | 04/21/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 04/21/2022 | 04/21/2022 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 02/14/2022 | 02/15/2022 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 02/14/2022 | 02/15/2022 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 02/14/2022 | 02/15/2022 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| BLD | HOLD | 01/14/2022 | 01/14/2022 |
| Note: Held By: FRED REODICA - (386)986-4734 - FREODICA@PALMCOASTGOV.COM 1. Sheet 1of 6: a. Provide components and cladding pressure zones per FBCR 7th Ed. Figure R301.2 (7). 2. Product Approval Specification Sheet per F.S. 553.842: a. FL 10852 - for wood connectors shows (2) same numbers which are incorrect. Delete these FL No. and keep the correct FL 10456. | |||
| CUSVC | COMPLETE | 01/14/2022 | 01/19/2022 |
| Note: Released By: HALEIGH HAND - - | |||
| ELEC | HOLD | 01/14/2022 | 01/19/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM Need service outlet by A/C unit NEC 2017 210.63 | |||
| ENGIN1 | COMPLETE | 01/14/2022 | 01/14/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| LOCATE | COMPLETE | 01/14/2022 | 01/21/2022 |
| Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 01/14/2022 | 01/18/2022 |
| Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM | |||
| SW1 | COMPLETE | 01/14/2022 | 01/20/2022 |
| Note: Released By: KALEN RUTH - (386)566-1273 - KRUTH@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 01/14/2022 | 01/14/2022 |
| Note: Released By: CINDY CHIRI-GONCALVES - - CGONCALVES@PALMCOASTGOV.COM | |||
| SWALE | COMPLETE | 01/14/2022 | 03/10/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 08/09/2022 |
| WATER -IRRIGATION INSPECTION | ¤25.00 | 03/28/2022 |
| METER - DEPOSIT | ¤60.00 | 03/28/2022 |
| WATER-METER | ¤467.09 | 03/28/2022 |
| WATER- TURN ON | ¤25.00 | 03/28/2022 |
| WATER- TURN ON | ¤25.00 | 02/17/2022 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 02/17/2022 |
| INSPECTION - RESIDENTIAL | ¤808.50 | 02/17/2022 |
| PLAN REVIEW - RESIDENTIAL | ¤229.32 | 02/17/2022 |
| METER - DEPOSIT | ¤60.00 | 02/17/2022 |
| 3% PARKS IMPACT FEE CREDIT | (¤43.65) | 02/17/2022 |
| SURCHARGE FS 533.721 | ¤11.26 | 02/17/2022 |
| SURCHARGE - FS 468.631 | ¤16.89 | 02/17/2022 |
| SW ENG - FOUNDATION SURVEY | ¤20.00 | 02/17/2022 |
| SW ENG INSPECTION 80 | ¤80.00 | 02/17/2022 |
| SW ENG PRE APRON | ¤30.00 | 02/17/2022 |
| SW ENG - REVIEW 20 | ¤20.00 | 02/17/2022 |
| SW ENG RES REVIEW 200 | ¤200.00 | 02/17/2022 |
| 3% TRANS IMPACT FEE CREDIT | (¤52.92) | 02/17/2022 |
| SEWER CREDIT | (¤2,465.75) | 02/17/2022 |
| SEWER INSPECTION | ¤25.00 | 02/17/2022 |
| SEWER CAPITAL FACILITY | ¤4,939.76 | 02/17/2022 |
| WATER CAPITAL FACILITY FEE | ¤3,626.50 | 02/17/2022 |
| SITE PLAN 30 | ¤30.00 | 02/17/2022 |
| CONNECTION FEES | ¤1,077.88 | 02/17/2022 |
| 3% FIRE IMPACT FEE CREDIT | (¤11.66) | 02/17/2022 |
| IMPACT FEE FIRE | ¤388.65 | 02/17/2022 |
| IMPACT FEE PARKS | ¤1,455.13 | 02/17/2022 |
| IMPACT FEE SCHOOL | ¤3,600.00 | 02/17/2022 |
| IMPACT FEE TRANSPORTATION | ¤1,764.00 | 02/17/2022 |
| WATER -IRRIGATION INSPECTION | ¤25.00 | 02/17/2022 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤16,506.00 |