Permit #2022010949

Permit Details

Status: COED

Parcel Id: 07-11-31-7031-00400-0060
CONDITIONED SPACE: 2295 sqft
GARAGE: 538 sqft
OPENED PORCH (WITH ROOF) : 201 sqft
OPENED PORCH (WITH ROOF) : 229 sqft
Total Square Footage: 3263 sqft
Block: 00400
Subdivision: 2166 - SECTION 31-ROYAL PALMS
Job Phone: 321-501-4617
Location Address: 25 RICHMOND DR
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 03/11/2022
NOC: RECORDED
Applicant name: JAMES FUCETOLA III
Owner: PALM COAST COMMUNITIES, LLC

Address

PO BOX 22547

ST SIMONS ISLAND, GA 31522

Lot: 0060
Contracted Stated Job Value: ¤215,000.00
Job Description: Single Family Residence
Type: CN

Contractor

PALM COAST COMMUNITIES LLC
Status Location Address State License Number Phone
INACTIVE

PO BOX 22547

PALM COAST, FL 32164

CBC1262878 (Exp: 08/31/2026) 321-501-4617

Sub Contractors

JEFFREY TROY SABAKA
Status Location Address State License Number Phone Fax
ACTIVE

2191 DEERWOOD ACRES DR

ST AUGUSTINE, FL 32084

CFC1427439 (Exp: 08/31/2026) 904-838-2218 904-819-0965
GARY LLOYD SHEFFIELD
Status Location Address State License Number Phone
ACTIVE

48 EAGLE LAKES DRIVE

FLAGLER BEACH, FL 32136

CAC048127 (Exp: 08/31/2026) 386-597-3280
WILLIAM FRANK DUDLEY JR.
Status Location Address State License Number Phone
ACTIVE

P.O. BOX 978

Bunnell, FL 32110

EC0003177 (Exp: 08/31/2026) (386)437-3068
OLEG BELINSKIY
Status Location Address State License Number Phone
ACTIVE

19 PINE CIRCLE DRIVE19

PALM COAST, FL 32167

CCC1325974 (Exp: 08/31/2026) 386-263-7906

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 12/14/2022 FINAL APPROVED JWALKER
Note: 12/13/2022 - PREVIOUS INSPECTION NOTES HVAC air handler, rear of AHU has been set tight to the wall no clearance. The right side of the handler does not have the required 3" clearance from the wall. M1305.1.1 Furnaces and air handlers
U -UTILITY RESIDENTIAL FINAL 12/14/2022 FINAL APPROVED LFITZGERALD
Note: 12/13/2022 - PREVIOUS INSPECTION NOTES pep tank with no pump-utility informed
BLD - BUILDING FINAL 12/13/2022 Disapproved - NO FEE JWALKER
Note: HVAC air handler, rear of AHU has been set tight to the wall no clearance. The right side of the handler does not have the required 3" clearance from the wall. M1305.1.1 Furnaces and air handlers
U -UTILITY RESIDENTIAL FINAL 12/13/2022 Disapproved - NO FEE LFITZGERALD
Note: pep tank with no pump-utility informed
ROW FIELD SURVEY /GRADING CERTIFICATION 12/12/2022 APPROVED GBERTOLA
ROW - STORMWATER FINAL 12/12/2022 APPROVED GBERTOLA
Note: AT THE TIME OF THE INSPECTION EVERYTHING LOOK GOOD
ROW - FINAL APRON (AFTER POUR) 12/12/2022 APPROVED GBERTOLA
Note: AT THE TIME OF THE INSPECTION EVERYTHING LOOK GOOD
FINAL SURVEY (OFFICE USE ONLY) 12/12/2022 APPROVED GBERTOLA
U-CROSS CONNECTION 12/09/2022 APPROVED - AS NOTED JHARDING
Note: No cross connections.
ELECTRIC - EARLY POWER 11/29/2022 APPROVED JMUNSON
U - SEWER TIE IN 11/18/2022 APPROVED - AS NOTED MGIBSON
Note: THS WAS A VIRTUAL INSPECTION
ROW- PRE-APRON (PRE-POUR) 11/17/2022 APPROVED GBERTOLA
Note: AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS BEFORE POURING. MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL
PEP TANK INSTALLATION REQUEST 11/02/2022 APPROVED CSTONE
Note: 10/28/2022 3:31:26 PM- PREVIOUS INSPECTION NOTES dumpster needs to move
PEP TANK INSTALLATION REQUEST 10/28/2022 Disapproved - NO FEE CSTONE
Note: dumpster needs to move
INSULATION 10/24/2022 APPROVED JWALKER
Note: 10/20/2022 - PREVIOUS INSPECTION NOTES Meet with contractor . As listed prior the required blocking at the gable ends needs to be installed per MItek truss specs due to missing details in the job prints.
INSULATION 10/20/2022 Disapproved - NO FEE JWALKER
Note: Meet with contractor . As listed prior the required blocking at the gable ends needs to be installed per MItek truss specs due to missing details in the job prints.
LATH/BRICK/ WATER BARRIER 10/19/2022 APPROVED JWALKER
Note: Inspector Notes from Inspection 2420
ALL ROUGH 10/17/2022 APPROVED - AS NOTED JWALKER
Note: 1. Garage bearing wall detail shows Sp2 or 4 at each stud top install missing anchors. Right side of wall. 2. Gable end detail minimum required MII sheet in the mitek truss packet. needs to be installed. Due to missing details on print. 2x blocking and bracing are to be 48" o.c.. Left the detail in the packet drawing circled.
ALL ROUGH 10/12/2022 Disapproved - NO FEE JWALKER
Note: 1 Garage bearing wall detail shows Sp2 or 4 at each stud top and bottom install all missing anchors. 3 Gable end detail minimum required MII sheet in the mitek truss packet. needs to be installed. Due to missing details on print. 2x blocking and bracing are to be 48" o.c.. Left the detail in the packet drawing circled. Check for install at ALL ROUGH. Items listed above have not been corrected. 5' head test not installed. Missing nail plates. Garage wall PVC plumbing line, Master bath 1 1/2 pvc vent line. UFB wire kitchen wall and kneewall. The kitchen wall at the mirowave exhaust duct needs to be supported right side and install Nail plated at the duct top plate.
ROOF VALLEY & METAL 06/24/2022 APPROVED JWALKER
ROOF SHEATHING 06/22/2022 APPROVED JWALKER
Note: THIS IS A REINSPECTION The right and left side hip roofs. The vertically installed sheets are not staggered and run 3 rows high. R803.2.3 Installation. Wood structural panel used as roof sheathing shall be installed with joints staggered.
WALL SHEATHING 06/22/2022 APPROVED JWALKER
ROOF SHEATHING / BRACES/TIES/DOWN CELL 06/22/2022 APPROVED - AS NOTED JWALKER
Note: 1 Garage bearing wall detail shows Sp2 or 4 at each stud top and bottom install all missing anchors. 3 Gable end detail minimum required MII sheet in the mitek truss packet. needs to be installed. Due to missing details on print. 2x blocking and bracing are to be 48" o.c.. Left the detail in the packet drawing circled. Check for install at ALL ROUGH.
ROOF SHEATHING 06/16/2022 Disapproved - NO FEE JWALKER
Note: The right and left side hip roofs. The vertically installed sheets are not staggered and run 3 rows high. R803.2.3 Installation. Wood structural panel used as roof sheathing shall be installed with joints staggered.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 06/16/2022 Disapproved - NO FEE JWALKER
Note: 1 Garage bearing wall detail shows Sp2 or 4 at each stud top and bottom install all missing anchors. 2 Truss TGO1 girder calls for HTU26 truss hanges for the 3 T15 trusses. Marked the engineering packet. 3 Gable end detail minimum required MII sheet in the mitek truss packet. needs to be installed. Due to missing details on print. 2x blocking and bracing are to be 48" o.c.. Left the detail in the packet drawing circled. 4 The right and left side hip roofs. The vertically installed sheets are not staggered and run 3 rows high. R803.2.3 Installation. Wood structural panel used as roof sheathing shall be installed with joints staggered.
WALL SHEATHING 06/16/2022 APPROVED JWALKER
FOUND SURVEY APPROVED (OFFICE) 06/15/2022 APPROVED TBAKER
TIE BEAM / LINTEL 05/31/2022 APPROVED JWALKER
Note: THIS IS A REINSPECTION THIS IS A REINSPECTION Please have a full set of approved prints onsite for inspections. 5/27/22 Down cells have been plywooded up. Unabe to see dowels Remove all plywood from down cells for inspection.
TIE BEAM / LINTEL 05/27/2022 Disapproved -FEE REQUIRED JWALKER
Note: THIS IS A REINSPECTION Please have a full set of approved prints onsite for inspections. 5/27/22 Down cells have been plywooded up. Unabe to see dowels Remove all plywood from down cells for inspection.
TIE BEAM / LINTEL 05/26/2022 Disapproved - NO FEE JWALKER
Note: Please have a full set of approved prints onsite for inspections.
MONOLITHIC SLAB 05/02/2022 APPROVED JWALKER
PLUMBING 1ST ROUGH UNDERGROUND 04/28/2022 APPROVED MGIBSON
GRAVITY SEWER TEST 04/28/2022 APPROVED MGIBSON
WATER METER INSTALLATION REQUEST 04/01/2022 APPROVED CSTONE

Review History

Department Status Date In Date Out
ENGIN1 COMPLETE 06/15/2022 06/15/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON COMPLETE 06/15/2022 06/15/2022
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
BADMIN INFORMATION 06/13/2022 06/13/2022
Note: Marked INFORMATION By: SCOTT THOMAS - - STHOMAS@PALMCOASTGOV.COM rename to foundation survey.pdf only
ELEC COMPLETE 03/03/2022 03/03/2022
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ZON COMPLETE 02/24/2022 02/24/2022
Note: Released By: CINDY CHIRI-GONCALVES - - CGONCALVES@PALMCOASTGOV.COM
BLD COMPLETE 02/24/2022 02/24/2022
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
ELEC HOLD 02/24/2022 02/24/2022
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM Need outlet by A/C NEC 2017 210.63. Outlet on the plan says 220 volt it has to be a 120 volt. 2nd REQUEST
SW1 COMPLETE 02/24/2022 03/02/2022
Note: Released By: KALEN RUTH - (386)566-1273 - KRUTH@PALMCOASTGOV.COM
BLD HOLD 01/21/2022 01/24/2022
Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code-Residential REVIEW COMMENTS: 1. Provide design pressures for windows and doors per R301.2
CUSVC COMPLETE 01/21/2022 01/26/2022
Note: Released By: HALEIGH HAND - -
ELEC HOLD 01/21/2022 01/24/2022
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM Need outlet by A/C NEC 2017 210.63
ENGIN1 COMPLETE 01/21/2022 01/21/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
LOCATE COMPLETE 01/21/2022 01/24/2022
Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM
MECH COMPLETE 01/21/2022 01/21/2022
Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM
SW1 HOLD 01/21/2022 01/28/2022
Note: Held By: PARREN FLANAGAN - - PFLANAGAN@PALMCOASTGOV.COM
ZON HOLD 01/21/2022 01/24/2022
Note: Held By: CINDY CHIRI-GONCALVES - - CGONCALVES@PALMCOASTGOV.COM entrance walk way is missing on siteplan. Also include the dimenisons
SWALE COMPLETE 01/21/2022 03/21/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 12/14/2022
CONNECTION FEES ¤1,077.88 03/11/2022
3% FIRE IMPACT FEE CREDIT (¤11.66) 03/11/2022
IMPACT FEE FIRE ¤388.65 03/11/2022
IMPACT FEE PARKS ¤1,455.13 03/11/2022
IMPACT FEE SCHOOL ¤3,600.00 03/11/2022
IMPACT FEE TRANSPORTATION ¤1,764.00 03/11/2022
WATER -IRRIGATION INSPECTION ¤25.00 03/11/2022
3% PARKS IMPACT FEE CREDIT (¤43.65) 03/11/2022
SURCHARGE FS 533.721 ¤11.26 03/11/2022
SURCHARGE - FS 468.631 ¤16.89 03/11/2022
SW ENG - FOUNDATION SURVEY ¤20.00 03/11/2022
SW ENG INSPECTION 80 ¤80.00 03/11/2022
SW ENG PRE APRON ¤30.00 03/11/2022
SW ENG - REVIEW 20 ¤20.00 03/11/2022
SW ENG RES REVIEW 200 ¤200.00 03/11/2022
3% TRANS IMPACT FEE CREDIT (¤52.92) 03/11/2022
SEWER CREDIT (¤2,129.67) 03/11/2022
SEWER INSPECTION ¤25.00 03/11/2022
SEWER CAPITAL FACILITY ¤4,939.76 03/11/2022
WATER CREDIT (¤463.43) 03/11/2022
WATER CAPITAL FACILITY FEE ¤3,626.50 03/11/2022
SITE PLAN 30 ¤30.00 03/11/2022
METER - DEPOSIT ¤60.00 03/11/2022
WATER- TURN ON ¤25.00 03/11/2022
ADMINISTRATIVE RESIDENTIAL ¤30.00 03/11/2022
INSPECTION - RESIDENTIAL ¤808.50 03/11/2022
PLAN REVIEW - RESIDENTIAL ¤229.32 03/11/2022
Fees Total Due: ¤0.00 Total Paid: ¤15,801.56