Permit #2022011332
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7034-00100-0080 |
| Block: 00100 |
| Subdivision: 2165 - SECTION 34-EASTHAMPTON |
| Job Phone: (386)246-9986 |
| Location Address: 7 EMERALD LN |
| Type: PO - POOL |
| Issue Date: 03/22/2022 |
| NOC: RECORDED |
| Applicant name: MICHAEL L RYAN |
| Owner: DEALMEIDA ANA P |
|
Address 7 EMERALD LANE PALM COAST, FL 32164 |
| Lot: 0080 |
| Contracted Stated Job Value: ¤43,448.00 |
| Job Description: SWIMMING Pool / Screen Enclosure |
| Type: CN |
Contractor
OHANU WATERS , INC
| Status | Location Address | Mailing Address | State License Number | Phone | Fax |
| INACTIVE |
4490 N US 1 PALM COAST, FL 32164 |
SUITE 109 PALM COAST, FL 32164 |
CPC1457377 (Exp: 08/31/2024) | (386)246-9986 | (386)246-5374 |
Sub Contractors
RICHARD R EDWARDS
| Status | Location Address | State License Number | Phone |
| ACTIVE |
P. O. Box 1637 Bunnell, FL 32110 |
EC13010654 (Exp: 08/31/2026) | (386) 437-1537 |
Inspection History
| Type | Request Date | Result | Inspector |
| POOL FINAL | 12/06/2023 | APPROVED | RSIMS |
| Note: 9/28/2023 - PREVIOUS INSPECTION NOTES 9/28/23: No answer at the door. 1). Remote alarm is not installed as required. (Still sitting in box). 2). Screen enclosure is missing an anchor at 6" away from both sides of each upright as required on plan detail. | |||
| POOL FINAL | 09/28/2023 | Disapproved -FEE REQUIRED | RSIMS |
| Note: 9/28/23: No answer at the door. 1). Remote alarm is not installed as required. (Still sitting in box). 2). Screen enclosure is missing an anchor at 6" away from both sides of each upright as required on plan detail. | |||
| U -UTILITY RESIDENTIAL FINAL | 08/24/2023 | FINAL APPROVED | JHARDING |
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 07/07/2023 | APPROVED | GBERTOLA |
| Note: At the time of the inspection all minimum city requirements were met. It is the builders responsibility to ensure that nothing changes after this Inspection is approved | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 07/07/2023 | APPROVED | GBERTOLA |
| Note: At the time of the inspection all minimum city requirements were met. It is the builders responsibility to ensure that nothing changes after this Inspection is approved | |||
| ROW - FINAL INSPECTION | 07/07/2023 | APPROVED | GBERTOLA |
| Note: At the time of the inspection all minimum city requirements were met. It is the builders responsibility to ensure that nothing changes after this Inspection is approved | |||
| ELECTRIC AND ALARM | 05/19/2023 | APPROVED | RSIMS |
| Note: 5/17/2023 - PREVIOUS INSPECTION NOTES 5/17/23: *** Need a service outlet installed within 10ft or line of sight to the pool equiment. | |||
| ELECTRIC AND ALARM | 05/17/2023 | Disapproved - NO FEE | RSIMS |
| Note: 5/17/23: *** Need a service outlet installed within 10ft or line of sight to the pool equiment. | |||
| POOL DECK | 10/27/2022 | APPROVED | JWALKER |
| Note: 10/25/2022 - PREVIOUS INSPECTION NOTES PRESSURE TEST R4501.12.1 (test not holding) Clearance on rebar from earth 3” FBC R404.1.2.3.7.4 10/27/22 Homeowner was clearing dirt off rebar. Please Ensure any colapsed soil is removed from footing when pumping. | |||
| POOL DECK | 10/25/2022 | Disapproved -FEE REQUIRED | LMILLER |
| Note: PRESSURE TEST R4501.12.1 (test not holding) Clearance on rebar from earth 3” FBC R404.1.2.3.7.4 | |||
| STEEL AND GROUND | 05/11/2022 | APPROVED | JWALKER |
| Note: THIS IS A REINSPECTION Permit packet and and approved drawings need to be onsite for inspections. FCB 107.3.1 The deep end drain lines are not under test. FBC-454.2.12.1 Pressure test. All pool piping shall be tested and proved tight to the satisfaction of the administrative authority, under a static water or air pressure test of not less than 35 psi (241 kPa) for 15 minutes.. | |||
| STEEL AND GROUND | 05/09/2022 | Disapproved - NO FEE | JWALKER |
| Note: Permit packet and and approved drawings need to be onsite for inspections. FCB 107.3.1 The deep end drain lines are not under test. FBC-454.2.12.1 Pressure test. All pool piping shall be tested and proved tight to the satisfaction of the administrative authority, under a static water or air pressure test of not less than 35 psi (241 kPa) for 15 minutes.. |
Review History
| Department | Status | Date In | Date Out |
| ZON | COMPLETE | 02/04/2022 | 02/04/2022 |
| Note: Released By: KATIE TAING - (386)986-3751 - KTAING@PALMCOASTGOV.COM | |||
| ZON | HOLD | 02/02/2022 | 02/02/2022 |
| Note: Held By: KATIE TAING - (386)986-3751 - KTAING@PALMCOASTGOV.COM The pool plan and the screen plan sizes do not match. | |||
| BLD | COMPLETE | 01/28/2022 | 01/31/2022 |
| Note: Released By: FRED REODICA - (386)986-4734 - FREODICA@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 01/28/2022 | 01/31/2022 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 01/28/2022 | 01/31/2022 |
| Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM | |||
| SW1 | COMPLETE | 01/28/2022 | 02/02/2022 |
| Note: Released By: ROBERT GROSS - (386)986-4769 - RGROSS@PALMCOASTGOV.COM | |||
| ZON | HOLD | 01/28/2022 | 01/31/2022 |
| Note: Held By: KATIE TAING - (386)986-3751 - KTAING@PALMCOASTGOV.COM The proposed pool deck exceeds the minimum 10' rear setback. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 12/05/2023 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 05/18/2023 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 03/22/2022 |
| INSPECTION- POOL | ¤160.00 | 03/22/2022 |
| PLAN REVIEW - RESIDENTIAL | ¤65.00 | 03/22/2022 |
| SURCHARGE FS 533.721 | ¤2.92 | 03/22/2022 |
| SURCHARGE - FS 468.631 | ¤4.38 | 03/22/2022 |
| SW ENG INSPECTION 40 | ¤40.00 | 03/22/2022 |
| SW ENG - REVIEW 20 | ¤20.00 | 03/22/2022 |
| SITE PLAN 30 | ¤30.00 | 03/22/2022 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤432.30 |