I want to search for...
Permit #2022030210
Permit Details
Status: COED
| Parcel Id: 25-10-30-4625-00000-0160 |
| CONDITIONED SPACE: 3697 sqft |
| GARAGE: 1063 sqft |
| OPENED PORCH (WITH ROOF) : 1401 sqft |
| OPENED PORCH (WITH ROOF) : 256 sqft |
| Total Square Footage: 6417 sqft |
| Block: 00000 |
| Subdivision: 2251 - NOTTINGHAM PHASE I-II (INFORMAL PLAT) |
| Job Phone: (386)931-2568 |
| Location Address: 4289 OLD KINGS RD N |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 06/16/2022 |
| NOC: RECORDED |
| Applicant name: PETER JOSEPH LYDEN |
| Owner: DAVIS CHARLES |
|
Address 7 LANCASTER LANE PALM COAST, FL 32137 |
| Lot: 0160 |
| Contracted Stated Job Value: ¤550,000.00 |
| Job Description: Single Family Residence |
| Type: CN |
Contractor
DEL CONSTRUCTION INC.
| Status | Location Address | State License Number | Phone |
| INACTIVE |
PO BOX 1009 BUNNELL, FL 32110 |
CBC1253392 (Exp: 08/31/2024) | 386-931-2568 |
Sub Contractors
CHARLES K DAVIS
| Status | Location Address | State License Number | Phone |
| ACTIVE |
3000 E MOODY BLVD BLDG 2 BUNNELL , FL 32110 |
EC13004270 (Exp: 08/31/2026) | 386-931-6614 |
MICHAEL FRANK MORELLO
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
2 HARGROVE GRADE PALM COAST, FL 32164 |
CAC1819466 (Exp: 08/31/2026) | 386-445-5023 | 386-446-4614 |
RUSSELL J CARTER
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
PO BOX 302 DELAND, FL 32721 |
CFC1425938 (Exp: 08/31/2026) | 386-736-4220 | 386-736-4219 |
WILLIAM ROBERT BARRICK
| Status | Location Address | Mailing Address | State License Number | Phone |
| CANCEL |
50 LEANNI WAY PALM COAST, FL 32137 |
STE E2 PALM COAST, FL 32137 |
RC29027799 (Exp: 08/31/2025) | 229-375-9123 |
Inspection History
| Type | Request Date | Result | Inspector |
| BLD - BUILDING FINAL | 03/15/2024 | FINAL APPROVED | AGAETANO |
| Note: 3/14/2024 - PREVIOUS INSPECTION NOTES 3/13/2024 - PREVIOUS INSPECTION NOTES 03-13-2024 1. Pool bath outlet GFCI will not reset. 2. Pool bath bedroom lights and outlets do not work. 3. Main house AHU disconnect height not per code. NEC 404.8 4. Pool house AHU and AC model numbers do not match submitted. 5. 3rd AHU in attic of guest room energy calcs not on site. (There are three AHU and AC units installed). 6. No light in pool room attic for AHU inspection. 7. Seal holes in main house AHU closet. Please submit all correct AHU and AC units energy calcs to the building department and have on site for next inspection. 03-14-2024 Energy calcs rejected. Doors locked. All items will need to be re inspected. | |||
| BLD - BUILDING FINAL | 03/14/2024 | Disapproved -FEE REQUIRED | AGAETANO |
| Note: 3/13/2024 - PREVIOUS INSPECTION NOTES 03-13-2024 1. Pool bath outlet GFCI will not reset. 2. Pool bath bedroom lights and outlets do not work. 3. Main house AHU disconnect height not per code. NEC 404.8 4. Pool house AHU and AC model numbers do not match submitted. 5. 3rd AHU in attic of guest room energy calcs not on site. (There are three AHU and AC units installed). 6. No light in pool room attic for AHU inspection. 7. Seal holes in main house AHU closet. Please submit all correct AHU and AC units energy calcs to the building department and have on site for next inspection. 03-14-2024 Energy calcs rejected. Doors locked. All items will need to be re inspected. | |||
| BLD - BUILDING FINAL | 03/13/2024 | Disapproved - NO FEE | AGAETANO |
| Note: 03-13-2024 1. Pool bath outlet GFCI will not reset. 2. Pool bath bedroom lights and outlets do not work. 3. Main house AHU disconnect height not per code. NEC 404.8 4. Pool house AHU and AC model numbers do not match submitted. 5. 3rd AHU in attic of guest room energy calcs not on site. (There are three AHU and AC units installed). 6. No light in pool room attic for AHU inspection. 7. Seal holes in main house AHU closet. Please submit all correct AHU and AC units energy calcs to the building department and have on site for next inspection. | |||
| ROW - FINAL APRON (AFTER POUR) | 03/13/2024 | APPROVED - AS NOTED | FSLADISH |
| Note: 3/13/24 THE CULVERT PIPE AND MITERED ENDS ELEVATION SHOTS AND SWALE PLAN WERE DETERMINED BY FLAGLER COUNTY FOR THIS PROPERTY. APPROVING THIS AS NOTED THAT FLAGLER COUNTY WAS/IS RESPONSIBLE FOR THE CULVERT AND SWALE ELEVATION AND CONDITION AT THIS ADDRESS. _______________________________________________________________________________________________________________________ Inspector Notes from Inspection 9471 3/12/24 At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. __________________________________________________________________________________________________________________________ Inspector Notes from Inspection 9465 3/12/24 UPON WALKING PROPERTY DRAINAGE WILL WORK AS INDICATED ON SURVEY. At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. ______________________________________________________________________________________________________________________ 3/7/2024 - PREVIOUS INSPECTION NOTES 3/7/24 YOU MUST FIRST SUBMIT AND PASS A FINAL SURVEY INSPECTION BEFORE A FIELD SURVEY INSPECTION CAN BE COMPLETED. I WILL NOT FEE YOU FOR THIS TODAY. PLEASE RESUBMIT YOUR FINAL SURVEY FOR REVIEW. THANK YOU. | |||
| U -UTILITY RESIDENTIAL FINAL | 03/13/2024 | APPROVED - AS NOTED | LFITZGERALD |
| Note: sewer is septic tank with drain field | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 03/12/2024 | APPROVED - AS NOTED | FSLADISH |
| Note: 3/12/24 ELEVATION NUMBERS ADJACENT TO STRUCTURE AARE NOW ALL WITHIN COPC PERAMETERS. APPROVING THIS AS NOTED. _______________________________________________________________________________________________________________________ 3/6/2024 - PREVIOUS INSPECTION NOTES 3/6/24 THE ELEVATIONS AGAINST THE STRUCTURE MUST BE A MINIMUM OF 4" BELOW FFE FOR BLOCK AND 6" FOR FRAME. 29.50 0N FRONT RIGHT CORNER OF STRUCTURE FFE IS 29.51.. NEED ELEVATIONS SHOT AT 20 ' INTERVALS ON PROPERTY. Final Survey Must have enough elevations to show Sec 300.01 D3 The interior elevations at no greater than a 20 foot grid. There must be sufficient Sec 300.01D2 drainage flow pattern elevation shots to indicate the intended drainage pattern. Sod elevation Section 300.01 (A)(1)(C)(6) Section 300.01 (A)(1)(C)(6) .Sod elevations adjacent to the structure are 4” below the FFE for block and 6” for wood frame structures Inspector Notes from Inspection 9270 ** 02/09/24 ELEVATION OF CULVERT SET BY FLAGLER COUNTY ALONG WITH SET OFF ROAD | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 03/12/2024 | APPROVED - AS NOTED | FSLADISH |
| Note: 3/12/24 UPON WALKING PROPERTY DRAINAGE WILL WORK AS INDICATED ON SURVEY. At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. ______________________________________________________________________________________________________________________ 3/7/2024 - PREVIOUS INSPECTION NOTES 3/7/24 YOU MUST FIRST SUBMIT AND PASS A FINAL SURVEY INSPECTION BEFORE A FIELD SURVEY INSPECTION CAN BE COMPLETED. I WILL NOT FEE YOU FOR THIS TODAY. PLEASE RESUBMIT YOUR FINAL SURVEY FOR REVIEW. THANK YOU. | |||
| ROW - STORMWATER FINAL | 03/12/2024 | APPROVED - AS NOTED | FSLADISH |
| Note: 3/12/24 At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. __________________________________________________________________________________________________________________________ Inspector Notes from Inspection 9465 3/12/24 UPON WALKING PROPERTY DRAINAGE WILL WORK AS INDICATED ON SURVEY. At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. ______________________________________________________________________________________________________________________ 3/7/2024 - PREVIOUS INSPECTION NOTES 3/7/24 YOU MUST FIRST SUBMIT AND PASS A FINAL SURVEY INSPECTION BEFORE A FIELD SURVEY INSPECTION CAN BE COMPLETED. I WILL NOT FEE YOU FOR THIS TODAY. PLEASE RESUBMIT YOUR FINAL SURVEY FOR REVIEW. THANK YOU. | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 03/07/2024 | Disapproved - NO FEE | FSLADISH |
| Note: 3/7/24 YOU MUST FIRST SUBMIT AND PASS A FINAL SURVEY INSPECTION BEFORE A FIELD SURVEY INSPECTION CAN BE COMPLETED. I WILL NOT FEE YOU FOR THIS TODAY. PLEASE RESUBMIT YOUR FINAL SURVEY FOR REVIEW. THANK YOU. | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 03/06/2024 | Disapproved - NO FEE | FSLADISH |
| Note: 3/6/24 THE ELEVATIONS AGAINST THE STRUCTURE MUST BE A MINIMUM OF 4" BELOW FFE FOR BLOCK AND 6" FOR FRAME. 29.50 0N FRONT RIGHT CORNER OF STRUCTURE FFE IS 29.51.. NEED ELEVATIONS SHOT AT 20 ' INTERVALS ON PROPERTY. Final Survey Must have enough elevations to show Sec 300.01 D3 The interior elevations at no greater than a 20 foot grid. There must be sufficient Sec 300.01D2 drainage flow pattern elevation shots to indicate the intended drainage pattern. Sod elevation Section 300.01 (A)(1)(C)(6) Section 300.01 (A)(1)(C)(6) .Sod elevations adjacent to the structure are 4” below the FFE for block and 6” for wood frame structures Inspector Notes from Inspection 9270 ** 02/09/24 ELEVATION OF CULVERT SET BY FLAGLER COUNTY ALONG WITH SET OFF ROAD | |||
| ROW- PRE-APRON (PRE-POUR) | 02/09/2024 | APPROVED - AS NOTED | EMADISON |
| Note: ** 02/09/24 ELEVATION OF CULVERT SET BY FLAGLER COUNTY ALONG WITH SET OFF ROAD | |||
| U - SEWER TIE IN | 12/22/2023 | APPROVED - AS NOTED | MGIBSON |
| Note: THIS WAS A VIRTUAL INSPECTION | |||
| U-CROSS CONNECTION | 12/22/2023 | APPROVED | DHANEY |
| GRAVITY SEWER TEST | 12/22/2023 | APPROVED - AS NOTED | MGIBSON |
| Note: THIS WAS A VIRTUAL INSPECTION | |||
| ELECTRIC - EARLY POWER | 08/16/2023 | APPROVED | AGAETANO |
| Note: 8/14/2023 - PREVIOUS INSPECTION NOTES 11/18/2022 - PREVIOUS INSPECTION NOTES Homeowner requested incorrect inspection. TUG inspection will be added. 08-14-2023 Exterior soffit lights and second floor light not safe off. | |||
| ELECTRIC - EARLY POWER | 08/14/2023 | Disapproved - NO FEE | AGAETANO |
| Note: 11/18/2022 - PREVIOUS INSPECTION NOTES Homeowner requested incorrect inspection. TUG inspection will be added. 08-14-2023 Exterior soffit lights and second floor light not safe off. | |||
| LATH/BRICK/ WATER BARRIER | 06/14/2023 | APPROVED | AGAETANO |
| Note: 6/5/2023 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 2450 05-16-2023 Wall sheathing seams have been sealed. 06-05-2023 Entry doors are not installed. All other areas are approved. Homeowner will schedule an additional lathe/brick inspection folowing the door installation. | |||
| WINDOW NAILING | 06/14/2023 | APPROVED - AS NOTED | AGAETANO |
| Note: 06-14-2023 Back garage door frame installed but not the door. Remaining doors and SGD approved. | |||
| LATH/BRICK/ WATER BARRIER | 06/05/2023 | PARTIALLY APPROVED | AGAETANO |
| Note: Inspector Notes from Inspection 2450 05-16-2023 Wall sheathing seams have been sealed. 06-05-2023 Entry doors are not installed. All other areas are approved. Homeowner will schedule an additional lathe/brick inspection folowing the door installation. Sheet 2A right side of storage in back of home has a missing cell that needs to be filled. 06-07-2023. Homeowner on site. Do not install stucco until cell has been filled. | |||
| INSULATION | 06/02/2023 | APPROVED - AS NOTED | AGAETANO |
| Note: 06-02-2023 Over the garage at the top of the steps an area is missibg sprsy foam insulation. Homeowner will address ASAP Entry doors need to be covered prior to drywall to prevent moisture. Hoeowner wil address ASAP. | |||
| ALL ROUGH | 05/18/2023 | APPROVED - AS NOTED | AGAETANO |
| Note: 05-18-2023 Head test failed. Check at insulation. Window nailing will be added for the 5 entry doors. | |||
| WALL SHEATHING | 05/16/2023 | APPROVED - AS NOTED | AGAETANO |
| Note: 05-16-2023 Wall sheathing seams have been sealed. | |||
| ROOF VALLEY & METAL | 04/06/2023 | APPROVED | AGAETANO |
| Note: Inspector Notes from Inspection 2460 1/30/2023 - PREVIOUS INSPECTION NOTES 01-30-2023 1. P03 Girder has two straps not fastened completely. 2. No address sign. 3. Engineering packet is a mess. Please organize for next inspection. Inspection stopped. 01-31-2023 A01 Missing members. Check at next inspection. | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 01/31/2023 | APPROVED - AS NOTED | AGAETANO |
| Note: 1/30/2023 - PREVIOUS INSPECTION NOTES 01-30-2023 1. P03 Girder has two straps not fastened completely. 2. No address sign. 3. Engineering packet is a mess. Please organize for next inspection. Inspection stopped. 01-31-2023 A01 Missing members. Check at next inspection. | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 01/30/2023 | Disapproved - NO FEE | AGAETANO |
| Note: 01-30-2023 1. P03 Girder has two straps not fastened completely. 2. No address sign. 3. Engineering packet is a mess. Please organize for next inspection. Inspection stopped. | |||
| FOUND SURVEY APPROVED (OFFICE) | 01/27/2023 | APPROVED | TDOAK |
| ELECTRIC - EARLY POWER | 11/18/2022 | CANCELLED BY APPLICANT | AGAETANO |
| Note: Homeowner requested incorrect inspection. TUG inspection will be added. | |||
| ELECTRIC-TUG | 11/18/2022 | APPROVED | AGAETANO |
| TIE BEAM / LINTEL | 10/10/2022 | APPROVED | AGAETANO |
| Note: 10/7/2022 - PREVIOUS INSPECTION NOTES 10/6/2022 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 2250 THIS IS A REINSPECTION 09-13-2022 Jobsite not visible form the road. Called contractor for directions. Contractor was verbally abusive to inspector. Please chave someone on site to meet inspector. 9/13/22 did virtual inspection with contractor in the afternoon 10-6-2022 Please have an Approved set drawings on site for inspection. NEED THE APPROVED DOCUMENTS ON SITE FOR INSPECTION 107.3,1. Drawings in the job box are filled with ants, wet, dirty, and wrinkled. Please have the ants removed from the job box prior to next inspection as well as the aproved drawings on site. 10-7-2022 - Please have an Approved set drawings on site for inspection. NEED THE APPROVED DOCUMENTS ON SITE FOR INSPECTION 107.3,1. | |||
| TIE BEAM / LINTEL | 10/07/2022 | Disapproved -FEE REQUIRED | AGAETANO |
| Note: 10/6/2022 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 2250 THIS IS A REINSPECTION 09-13-2022 Jobsite not visible form the road. Called contractor for directions. Contractor was verbally abusive to inspector. Please chave someone on site to meet inspector. 9/13/22 did virtual inspection with contractor in the afternoon 10-6-2022 Please have an Approved set drawings on site for inspection. NEED THE APPROVED DOCUMENTS ON SITE FOR INSPECTION 107.3,1. Drawings in the job box are filled with ants, wet, dirty, and wrinkled. Please have the ants removed from the job box prior to next inspection as well as the aproved drawings on site. 10-7-2022 - Please have an Approved set drawings on site for inspection. NEED THE APPROVED DOCUMENTS ON SITE FOR INSPECTION 107.3,1. | |||
| TIE BEAM / LINTEL | 10/06/2022 | Disapproved -FEE REQUIRED | AGAETANO |
| Note: Inspector Notes from Inspection 2250 THIS IS A REINSPECTION 09-13-2022 Jobsite not visible form the road. Called contractor for directions. Contractor was verbally abusive to inspector. Please chave someone on site to meet inspector. 9/13/22 did virtual inspection with contractor in the afternoon 10-6-2022 Please have an Approved set drawings on site for inspection. NEED THE APPROVED DOCUMENTS ON SITE FOR INSPECTION 107.3,1. Drawings in the job box are filled with ants, wet, dirty, and wrinkled. Please have the ants removed from the job box prior to next inspection as well as the aproved drawings on site. | |||
| MONOLITHIC SLAB | 09/14/2022 | APPROVED - AS NOTED | RMARTIN |
| Note: THIS IS A REINSPECTION 09-13-2022 Jobsite not visible form the road. Called contractor for directions. Contractor was verbally abusive to inspector. Please chave someone on site to meet inspector. 9/13/22 did virtual inspection with contractor in the afternoon | |||
| MONOLITHIC SLAB | 09/13/2022 | Disapproved - NO FEE | AGAETANO |
| Note: 09-13-2022 Jobsite not visible form the road. Called contractor for directions. Contractor was verbally abusive to inspector. Please chave someone on site to meet inspector. 09-13-2022 Inspector wet back out and ;ocated job site. Compaction test not on site. Spoke to homeowner and he stated that he did not obtain one. Inspection stopped. | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 09/08/2022 | APPROVED | MGIBSON |
| WATER METER INSTALLATION REQUEST | 07/13/2022 | APPROVED | CSTONE |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 03/14/2024 | 03/14/2024 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| BADMIN | INFORMATION | 03/13/2024 | 03/13/2024 |
| Note: Marked INFORMATION By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM Documents/Files named incorrectly o Please rename your files in accordance with the naming convention outlined in our ‘document requirements’ located on the permit portal page http://docs.palmcoastgov.com/departments/building/online/document-requirements.pdf o It is important that all submittals follow the guidelines for efficient plan review and record retention accuracy. o You may add to your file name AFTER the above naming convention has been met. Examples Document type: Plans File name : Given sheet name A.1 / Plans Document type: Foundation Survey File name: Foundation Survey Document type: Manufactures Specifications File Name: Pool Alarm Document type: Manufactures Specifications File Name: Generator Revisions and corrections should follow the same criteria and should use the same name as the original originally identified. (no – new, revised, second submittal, updated) | |||
| BADMIN | INFORMATION | 12/27/2023 | 12/27/2023 |
| Note: Marked INFORMATION By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM Documents/Files named incorrectly o Please rename your files in accordance with the naming convention outlined in our ‘document requirements’ located on the permit portal page http://docs.palmcoastgov.com/departments/building/online/document-requirements.pdf o It is important that all submittals follow the guidelines for efficient plan review and record retention accuracy. o You may add to your file name AFTER the above naming convention has been met. Examples Document type: Plans File name : Given sheet name / Plans Document type: Foundation Survey File name: Foundation Survey Document type: Manufactures Specifications File Name: Pool Alarm Document type: Manufactures Specifications File Name: Generator | |||
| ZON | COMPLETE | 12/27/2023 | 12/27/2023 |
| Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 01/30/2023 | 01/31/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 01/26/2023 | 01/27/2023 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM Building Plan Review not required. | |||
| ELEC | COMPLETE | 01/26/2023 | 01/27/2023 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| MECH | HOLD | 01/26/2023 | 01/27/2023 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide updated Duct layout 2. Energy Calcs need to be signed by the builder | |||
| ZON | HOLD | 01/24/2023 | 01/24/2023 |
| Note: Held By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM REPEAT COMMENT: Setbacks on the Foundation Survey submitted are not legible. Please submit a more clear copy for review. | |||
| ENGIN1 | COMPLETE | 01/24/2023 | 01/24/2023 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 01/24/2023 | 01/24/2023 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| ENGIN1 | COMPLETE | 01/20/2023 | 01/23/2023 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| ZON | HOLD | 01/20/2023 | 01/20/2023 |
| Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Setbacks on the Foundation Survey submitted are not legible. Please submit a more clear copy for review. | |||
| SW1 | COMPLETE | 06/10/2022 | 06/15/2022 |
| Note: Released By: ROBERT GROSS - (386)986-4769 - RGROSS@PALMCOASTGOV.COM After further reveiw this ROW and culvert will be inspected and approved by the County and not the City. Therefore no proposed Culvert elevations will be mandatory in this instance. | |||
| SW1 | HOLD | 06/02/2022 | 06/09/2022 |
| Note: Held By: EDWARD MADISON - - EMADISON@PALMCOASTGOV.COM NEED TO INDICATE IF THERE IS A DRIVEWAY CULVERT , WHAT TYPE IT ISAND INVERT NUMBERS FOR FLOW OF DRAINAGE | |||
| ELEC | COMPLETE | 06/02/2022 | 06/03/2022 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 06/02/2022 | 06/02/2022 |
| Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 05/24/2022 | 05/24/2022 |
| Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM | |||
| SW1 | HOLD | 05/24/2022 | 05/26/2022 |
| Note: Held By: ROBERT GROSS - (386)986-4769 - RGROSS@PALMCOASTGOV.COM Culvert Pipe in the swale is near the road side needs to be shown on the plans if there exists one or clearly indicated the type size and elevation of the proposed intallation of one. | |||
| ENGIN1 | COMPLETE | 05/24/2022 | 05/24/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 05/24/2022 | 05/25/2022 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| ZON | HOLD | 05/17/2022 | 05/17/2022 |
| Note: Scanned copy of site plan is not clear. Setbacks and notes are very hard to read. Please put the driveway notes on the site plan and not the landscape plan" REL_REMARKS_new="Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Scanned copy of site plan is not clear. Setbacks and notes are very hard to read. | |||
| MECH | HOLD | 05/17/2022 | 05/18/2022 |
| Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM 1.Remove minisplit from electrical plans and submit new electrical plan. (Not done from previous hold comments) | |||
| ENGIN1 | COMPLETE | 05/17/2022 | 05/17/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| SW1 | HOLD | 05/17/2022 | 05/24/2022 |
| Note: Held By: EDWARD MADISON - - EMADISON@PALMCOASTGOV.COM unable to read site plan need to submit a clear and legible site plan | |||
| BLD | COMPLETE | 04/27/2022 | 04/28/2022 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 04/27/2022 | 04/28/2022 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ZON | HOLD | 04/27/2022 | 04/28/2022 |
| Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Same landscape plan submitted... Landscape plan must show all tree types and their locations within the building area. Show the credited tree locations. Your natural marked areas looks good. Pines do not count as credited trees. Foundation plantings must be at least 3 gallon in size. Site plan/survey must show the width and material of driveway in right of way. It can not be gravel at right of way. Not on the landscape plan. 1.Driveways shall be completely paved. However, on one-acre or larger lots, where the garage is located at least 100 feet from the right-of-way, the pavement area may be limited as follows: Only the 20 feet closest to the garage, the driveway apron area within the right-of-way, and other portions of the driveway that are visible from the right-of-way and within 100 feet of the right-of-way, are required to be paved. The unpaved driveway area shall be of a stabilized material that will support emergency vehicles and meet City standards, such as graded and compacted asphalt milling or similar material. Pervious and permeable pavers and pavement which meet City standards are allowed and are acceptable Green Building materials.2.Garages must have a driveway extending for a minimum of 20 feet in front of each garage door. The driveway shall be at least the width of the garage door(s), with a minimum width of ten feet, to allow for safe access. For the 20 feet of the driveway that is closest to the garage, driveways for one and two-car garages shall have a minimum width of 16 feet, and driveways for three-car or larger garages shall have a minimum width of 24 feet.3.Residential driveways entering the public right-of-way shall be a minimum of ten feet wide at the right-of-way line and 16 feet wide at the roadway edge. | |||
| MECH | HOLD | 04/27/2022 | 04/28/2022 |
| Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM 1.Remove minisplit from electrical plans. 2. Truss engineering details for weight of AHU in attic needs to be signed and sealed per 105.3.1.2 FBC Building 2020 7th edition | |||
| SW1 | COMPLETE | 04/27/2022 | 05/04/2022 |
| Note: Released By: PARREN FLANAGAN - (386)986-2392 - PFLANAGAN@PALMCOASTGOV.COM | |||
| BLD | HOLD | 04/21/2022 | 04/21/2022 |
| Note: Held By: FRED REODICA - (386)986-4734 - FREODICA@PALMCOASTGOV.COM Previous comments of the same date are not correct: Repeat Comments: 2. b. FL 48495 - garage doors - change the FL No. to 15279.37 from the specification list. Submitted copy is correct. 2c. Provide missing FL numbers for wood anchors, wood connectors, truss plates. lintels and soffits. 3. Roofing Worksheet: a. FL 11915 -R1- underlayment - cannot be found on approval listing. | |||
| MECH | HOLD | 04/20/2022 | 04/21/2022 |
| Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM 2. Plans show minisplit for pool house. Energy Calcs have a unitary ducted system. Revise to match. 3. If there is a unitary system in attic of pool house, provide truss engineering details showing trusses can support the added weight from air handler per 107 FBC 2020 7Th edition 4. Duct Layout needs to be larger. Unable to read when expanded (Third Request) | |||
| ELEC | HOLD | 04/20/2022 | 04/21/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Update all code years on bottom right hand corner of the electgrical page. 2. Freezer outlet needs to be GFCI protected. NEC 2017 210.8 3. If there are recessed can in the garage you need to submit the manifacurte specs that say they are fire rated. FRC 2020 302.5.3. There is no legend on the electrical page to show what they are. 4. Need correct outlet spacing in Bed 2,3,4 and Gym NEC 2017 210.52 3rd REQUEST | |||
| BLD | HOLD | 04/20/2022 | 04/21/2022 |
| Note: Held By: FRED REODICA - (386)986-4734 - FREODICA@PALMCOASTGOV.COM 2. Product approval specification sheet per F.S. 553.842: Repeat Comment a. OK b. FL 48495 - garage doors - cannot be found on approval listing. c. FL-8153 - single hung windows - provide specific number as there are (2) different models to choose. d. FL 1450 - fixed windows - provide specific number as there are different models to choose. e. Provide missing FL numbers for wood anchors, wood connectors, truss plates. lintels and soffits. 3. Roofing Worksheet: a. FL 11915 -R1- underlayment= cannot be found on approval listing. | |||
| ZON | HOLD | 04/20/2022 | 04/21/2022 |
| Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Landscape plan must show all tree types and their locations within the building area. Your natural marked area looks good. If using Zoysia sod irrigation must be installed Site plan/survey must show the width and material of driveway. Please show the width and length at the garage entry. Not on the landscape plan 1.Driveways shall be completely paved. However, on one-acre or larger lots, where the garage is located at least 100 feet from the right-of-way, the pavement area may be limited as follows: Only the 20 feet closest to the garage, the driveway apron area within the right-of-way, and other portions of the driveway that are visible from the right-of-way and within 100 feet of the right-of-way, are required to be paved. The unpaved driveway area shall be of a stabilized material that will support emergency vehicles and meet City standards, such as graded and compacted asphalt milling or similar material. Pervious and permeable pavers and pavement which meet City standards are allowed and are acceptable Green Building materials.2.Garages must have a driveway extending for a minimum of 20 feet in front of each garage door. The driveway shall be at least the width of the garage door(s), with a minimum width of ten feet, to allow for safe access. For the 20 feet of the driveway that is closest to the garage, driveways for one and two-car garages shall have a minimum width of 16 feet, and driveways for three-car or larger garages shall have a minimum width of 24 feet.3.Residential driveways entering the public right-of-way shall be a minimum of ten feet wide at the right-of-way line and 16 feet wide at the roadway edge. | |||
| SW1 | HOLD | 04/20/2022 | 04/27/2022 |
| Note: Held By: PARREN FLANAGAN - - PFLANAGAN@PALMCOASTGOV.COM NOTHING CHANGED PLEASE SEE NOTES ON ALL OTHER HOLDS | |||
| ENGIN1 | COMPLETE | 04/20/2022 | 04/21/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| ELEC | HOLD | 03/23/2022 | 03/23/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Update all code years on bottom right hand corner of the electgrical page. 2. Freezer outlet needs to be GFCI protected. NEC 2017 210.8 3. If there are recessed can in the garage you need to submit the manifacurte specs that say they are fire rated. FRC 2020 302.5.3. There is no legend on the electrical page to show what they are. 4. Need correct outlet spacing in Bed 2,3,4 and Gym NEC 2017 210.52 2nd REQUEST | |||
| MECH | HOLD | 03/23/2022 | 03/23/2022 |
| Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM .Energy Calcs need to be signed by the builder per 107.1 FBC Residential 2020 7th edition 2. Plans show minisplit for pool house. Energy Calcs have a unitary ducted system. Revise to match. 3. If there is a unitary system in attic of pool house, provide truss engineering details showing trusses can support the added weight from air handler per 107 FBC 2020 7Th edition 4. Duct Layout needs to be larger. Unable to read when expanded (Second Request) | |||
| BLD | HOLD | 03/23/2022 | 03/23/2022 |
| Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM 1. OK 2. Product approval specification sheet per F.S. 553.842: Repeat Comment a. OK b. FL 48495 - garage doors - cannot be found on approval listing. c. FL-8153 - single hung windows - provide specific number as there are (2) different models to choose. d. FL 1450 - fixed windows - provide specific number as there are different models to choose. e. Provide missing FL numbers for wood anchors, wood connectors, truss plates. lintels and soffits. 3. Roofing Worksheet: a. FL 11915 -R1- underlayment= cannot be found on approval listing. | |||
| ZON | HOLD | 03/23/2022 | 03/23/2022 |
| Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM REPEAT COMMENT: Landscape plan must show all required shrubs with gallon sizes and tree types within the building area. If leaving areas natural please note that as well. 16 shrubs required. Minimum of 8 in front and four along each side wrapping corners. Landscape plan must state sod type and if irrigation will be installed. AC pad must be screened with 7 gallon shrubs please note that on landscape plan. This lot must have a total of 88 trees. So please show natural areas on landscape plan. Site plan survey must show the width and material of driveway. Please show the width and length at the garage entry. 1.Driveways shall be completely paved. However, on one-acre or larger lots, where the garage is located at least 100 feet from the right-of-way, the pavement area may be limited as follows: Only the 20 feet closest to the garage, the driveway apron area within the right-of-way, and other portions of the driveway that are visible from the right-of-way and within 100 feet of the right-of-way, are required to be paved. The unpaved driveway area shall be of a stabilized material that will support emergency vehicles and meet City standards, such as graded and compacted asphalt milling or similar material. Pervious and permeable pavers and pavement which meet City standards are allowed and are acceptable Green Building materials.2.Garages must have a driveway extending for a minimum of 20 feet in front of each garage door. The driveway shall be at least the width of the garage door(s), with a minimum width of ten feet, to allow for safe access. For the 20 feet of the driveway that is closest to the garage, driveways for one and two-car garages shall have a minimum width of 16 feet, and driveways for three-car or larger garages shall have a minimum width of 24 feet.3.Residential driveways entering the public right-of-way shall be a minimum of ten feet wide at the right-of-way line and 16 feet wide at the roadway edge. | |||
| SW1 | HOLD | 03/23/2022 | 03/28/2022 |
| Note: Held By: PARREN FLANAGAN - - PFLANAGAN@PALMCOASTGOV.COM driveway needs to be in front of your property not going off into city owned easementeasement Lot drainage features and patterns must be clearly depicted and include flow arrows.(A) | |||
| PLFM | CANCEL | 03/07/2022 | 03/08/2022 |
| BLD | HOLD | 03/03/2022 | 03/03/2022 |
| Note: Held By: FRED REODICA - (386)986-4734 - FREODICA@PALMCOASTGOV.COM 1. Sheet 2B indicates Floor Plan and Roof plan. Revise for clarity -FBC 7th Ed. Sec. 107.3. 2. Product approval specification sheet per F.S. 553.842: a. FL 21-0205.03 - sliding glass door - cannot be found on approval listing. b. FL 48495 - garage doors - cannot be found on approval listing. c. FL-8153 - single hung windows - provide specific number as there are (2) different models to choose. d. FL 1450 - fixed windows - provide specific number as there are different models to choose. e. Provide missing FL numbers for wood anchors, wood connectors, truss plates. lintels and soffits. 3. Roofing Worksheet: a. FL 11915 -R1- underlayment= cannot be found on approval listing. | |||
| CUSVC | COMPLETE | 03/03/2022 | 03/11/2022 |
| Note: Released By: ALYSSA ROSCOE - - | |||
| ELEC | HOLD | 03/03/2022 | 03/03/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Update all code years on bottom right hand corner of the electgrical page. 2. Freezer outlet needs to be GFCI protected. NEC 2017 210.8 3. If there are recessed can in the garage you need to submit the manifacurte specs that say they are fire rated. FRC 2020 302.5.3. There is no legend on the electrical page to show what they are. 4. Need correct outlet spacing in Bed 2,3,4 and Gym NEC 2017 210.52 | |||
| ENGIN1 | COMPLETE | 03/03/2022 | 03/03/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| LOCATE | COMPLETE | 03/03/2022 | 03/07/2022 |
| Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM | |||
| MECH | HOLD | 03/03/2022 | 03/03/2022 |
| Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM 1.Energy Calcs need to be signed by the builder per 107.1 FBC Residential 2020 7th edition 2. Plans show minisplit for pool house. Energy Calcs have a unitary ducted system. Revise to match. 3. If there is a unitary system in attic of pool house, provide truss engineering details showing trusses can support the added weight from air handler per 107 FBC 2020 7Th edition 4. Duct Layout needs to be larger. Unable to read when expanded | |||
| SW1 | HOLD | 03/03/2022 | 03/08/2022 |
| Note: Held By: KALEN RUTH - (386)566-1273 - KRUTH@PALMCOASTGOV.COM driveway needs to be in front of your property not going off into city owned easementeasement | |||
| ZON | HOLD | 03/03/2022 | 03/07/2022 |
| Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Landscape plan must show all required shrubs with gallon sizes and tree types within the building area. If leaving areas natural please note that as well. 16 shrubs required. Minimum of 8 in front and four along each side wrapping corners. Landscape plan must state sod type and if irrigation will be installed. AC pad must be screened with 7 gallon shrubs please note that on landscape plan. This lot must have a total of 88 trees. So please show natural areas on landscape plan. Site plan survey must show the width and material of driveway. Please show the width and length at the garage entry. 1.Driveways shall be completely paved. However, on one-acre or larger lots, where the garage is located at least 100 feet from the right-of-way, the pavement area may be limited as follows: Only the 20 feet closest to the garage, the driveway apron area within the right-of-way, and other portions of the driveway that are visible from the right-of-way and within 100 feet of the right-of-way, are required to be paved. The unpaved driveway area shall be of a stabilized material that will support emergency vehicles and meet City standards, such as graded and compacted asphalt milling or similar material. Pervious and permeable pavers and pavement which meet City standards are allowed and are acceptable Green Building materials.2.Garages must have a driveway extending for a minimum of 20 feet in front of each garage door. The driveway shall be at least the width of the garage door(s), with a minimum width of ten feet, to allow for safe access. For the 20 feet of the driveway that is closest to the garage, driveways for one and two-car garages shall have a minimum width of 16 feet, and driveways for three-car or larger garages shall have a minimum width of 24 feet.3.Residential driveways entering the public right-of-way shall be a minimum of ten feet wide at the right-of-way line and 16 feet wide at the roadway edge. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| CONTRACTOR CHANGE | ¤20.00 | 03/04/2024 |
| CONTRACTOR CHANGE | ¤20.00 | 03/04/2024 |
| PLAN REVIEW - REVISION | ¤32.50 | 03/04/2024 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 03/04/2024 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 03/04/2024 |
| CONNECTION FEES | ¤25.00 | 06/16/2022 |
| WATER-METER | ¤467.09 | 06/16/2022 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 06/16/2022 |
| INSPECTION - RESIDENTIAL | ¤1,512.50 | 06/16/2022 |
| PLAN REVIEW - RESIDENTIAL | ¤429.00 | 06/16/2022 |
| 3% FIRE IMPACT FEE CREDIT | (¤11.66) | 06/16/2022 |
| IMPACT FEE FIRE | ¤388.65 | 06/16/2022 |
| IMPACT FEE PARKS | ¤1,455.13 | 06/16/2022 |
| IMPACT FEE SCHOOL | ¤3,600.00 | 06/16/2022 |
| IMPACT FEE TRANSPORTATION | ¤3,224.00 | 06/16/2022 |
| 3% PARKS IMPACT FEE CREDIT | (¤43.65) | 06/16/2022 |
| SURCHARGE FS 533.721 | ¤16.13 | 06/16/2022 |
| SURCHARGE - FS 468.631 | ¤24.19 | 06/16/2022 |
| SW ENG - FOUNDATION SURVEY | ¤20.00 | 06/16/2022 |
| SW ENG INSPECTION 80 | ¤80.00 | 06/16/2022 |
| SW ENG PRE APRON | ¤30.00 | 06/16/2022 |
| SW ENG - REVIEW 20 | ¤20.00 | 06/16/2022 |
| SW ENG RES REVIEW 200 | ¤200.00 | 06/16/2022 |
| 3% TRANS IMPACT FEE CREDIT | (¤96.72) | 06/16/2022 |
| WATER CAPITAL FACILITY FEE | ¤3,626.50 | 06/16/2022 |
| SITE PLAN 30 | ¤30.00 | 06/16/2022 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤15,178.66 |