Permit #2022031492

Permit Details

Status: COED

Parcel Id: 39-12-31-0000-04030-0000
Total Square Footage: 13452 sqft
Block: 04030
Subdivision: -
Job Phone: 407-384-1909
Location Address: 511 OLD KINGS RD
Type: CA - COMM ADDITION
Issue Date: 10/13/2022
NOC: RECORDED
Applicant name: RICHARD LEROY HAINES
Owner: SE COMBINED SERVICES OF FLORIDA LLC

Address

1929 ALLEN PARKWAY

HOUSTON, TX 77019

Lot: 0000
Contracted Stated Job Value: ¤1,500,000.00
Job Description: ADDITION - NTERIOR & EXTERIOR RENOVATION " FLAGLER PALMS"
Type: CN

Contractor

RLH CONSTRUCTION LLC
Status Location Address State License Number Phone
INACTIVE

5700 DOT COM CT SUITE 1070

OVIEDO, FL 32765

CGC1521696 (Exp: 08/31/2024) 407-384-1908

Sub Contractors

ROBERT C DRURY
Status Location Address State License Number Phone
INACTIVE

430 ANDALUSIA AVE

, 0

CAC1820800 (Exp: 08/31/2024) 386-679-7090
DAVID SCOTT MORRIS
Status Location Address State License Number Phone
INACTIVE

63 LEIDEL DR

PALM COAST, FL 32137

ER13015750 (Exp: 08/31/2026) 386-569-7262
LEWIS G WALKER
Status Location Address State License Number
INACTIVE

PO BOX 2147

LAKE CITY, FL 32025

CCC1333551 (Exp: 08/31/2024)
JEFFREY DALE KNIGHT
Status Location Address State License Number Phone Fax
INACTIVE

923 ASHMEADE CT

PORT ORANGE, FL 32127

CFC057351 (Exp: 08/31/2026) 386-345-3857 386-345-4443

Inspection History

Type Request Date Result Inspector
LDSC- LANDSCAPE FINAL 12/21/2023 APPROVED RPICATAGI
Note: 12/15/2023 2:55:02 PM- PREVIOUS INSPECTION NOTES
U - UTILITY COMMERCIAL FINAL 12/20/2023 FINAL APPROVED LFITZGERALD
BUILDING FINAL 12/20/2023 FINAL APPROVED FWILLIS
FIRE FINAL 12/15/2023 APPROVED RMARTIN
Note: 12/14/2023 - PREVIOUS INSPECTION NOTES 10/19/2023 - PREVIOUS INSPECTION NOTES phase 1 is good
LDSC- LANDSCAPE FINAL 12/15/2023 Disapproved - NO FEE RPICATAGI
Note: LDC Sec. 13.03.02 A -1 requires an 8 feet wide foundation planting with double row of shrubs for 70% of building facade(except for doorways, garage doors, paving etc.) Additional plantings are required in gravel beds of front facade that are north of the main entry and also along the rear facade in gravel beds in order to comply with the referencde code section.
ELECTRIC FINAL 12/15/2023 APPROVED RMARTIN
Note: 12/14/2023 - PREVIOUS INSPECTION NOTES 10/19/2023 - PREVIOUS INSPECTION NOTES phase 1 is good
HVAC FINAL 12/15/2023 FINAL APPROVED CPISCITELLI
Note: 12/14/2023 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 3140 Will look at wrap and grill cconnections on above ceiling inspection 7/5/2023 - PREVIOUS INSPECTION NOTE 6/21/2023 - PREVIOUS INSPECTION NOTES Inspected exhaust duct to roof 5/2/2023 - PREVIOUS INSPECTION NOTES Inspected metal duct to be able to wrap and inspected ductboard trunkline
ELECTRIC FINAL 12/14/2023 CANCELLED BY APPLICANT RMARTIN
Note: 10/19/2023 - PREVIOUS INSPECTION NOTES phase 1 is good
FIRE FINAL 12/14/2023 CANCELLED BY APPLICANT RMARTIN
Note: 10/19/2023 - PREVIOUS INSPECTION NOTES phase 1 is good
HVAC FINAL 12/14/2023 CANCELLED BY APPLICANT CPISCITELLI
Note: Inspector Notes from Inspection 3140 Will look at wrap and grill cconnections on above ceiling inspection 7/5/2023 - PREVIOUS INSPECTION NOTE 6/21/2023 - PREVIOUS INSPECTION NOTES Inspected exhaust duct to roof 5/2/2023 - PREVIOUS INSPECTION NOTES Inspected metal duct to be able to wrap and inspected ductboard trunkline
ABOVE CEILING 12/12/2023 APPROVED RMARTIN
Note: 8/11/2023 - PREVIOUS INSPECTION NOTES phase 1
PLUMBING FINAL 12/11/2023 APPROVED - AS NOTED MGIBSON
Note: 12/1/2023 - PREVIOUS INSPECTION NOTES 1. Men and womes restrooms. The lavatories are to be a minimum of 60" off of the finished wall from side of the toilet to edge of lav. P-604.3.2 2. The baby changing stations are to be a maximum of 3' 10 1/2" to top of the station see page A-400 of the prints. and see FBCA-902.1 advisory 3. The ADA sinage at the restrooms are to be a max distance of 60" to center of the sign off of the finished floor. NEED TO CHANGE PLUMBING CONTRACTOR TO CORECT ONE
HVAC ROUGH 12/06/2023 APPROVED - AS NOTED CPISCITELLI
Note: Will look at wrap and grill cconnections on above ceiling inspection 7/5/2023 - PREVIOUS INSPECTION NOTE 6/21/2023 - PREVIOUS INSPECTION NOTES Inspected exhaust duct to roof 5/2/2023 - PREVIOUS INSPECTION NOTES Inspected metal duct to be able to wrap and inspected ductboard trunkline
PLUMBING FINAL 12/01/2023 Disapproved - NO FEE JWALKER
Note: 1. Men and womes restrooms. The lavatories are to be a minimum of 60" off of the finished wall from side of the toilet to edge of lav. P-604.3.2 2. The baby changing stations are to be a maximum of 3' 10 1/2" to top of the station see page A-400 of the prints. and see FBCA-902.1 advisory 3. The ADA sinage at the restrooms are to be a max distance of 60" to center of the sign off of the finished floor.
PLUMBING FINAL 12/01/2023 APPROVED JWALKER
Note: Disreguard this inspection was appoved accidentially. A new plumbing final has been added.
ELECTRIC 2ND ROUGH 11/28/2023 APPROVED RMARTIN
Note: 11/21/2023 - PREVIOUS INSPECTION NOTES sofit cans in large room
FRAMING 11/21/2023 APPROVED FWILLIS
ELECTRIC 2ND ROUGH 11/21/2023 PARTIALLY APPROVED RMARTIN
Note: sofit cans in large room
ELECTRIC FINAL 10/19/2023 PARTIALLY APPROVED RMARTIN
Note: phase 1 is good
FIRE FINAL 10/19/2023 PARTIALLY APPROVED RMARTIN
Note: phase 1 is good
HVAC FINAL 10/12/2023 PARTIALLY APPROVED CPISCITELLI
ABOVE CEILING 08/11/2023 PARTIALLY APPROVED RMARTIN
Note: phase 1
ELECTRIC 2ND ROUGH 08/09/2023 APPROVED RMARTIN
LATH/BRICK/WATER BARRIER 08/03/2023 APPROVED FWILLIS
ELECTRIC 2ND ROUGH 07/26/2023 APPROVED RMARTIN
Note: 7/24/2023 - PREVIOUS INSPECTION NOTES 7/24/23 large room by porch 7/20/2023 - PREVIOUS INSPECTION NOTES porch area
ELECTRIC 2ND ROUGH 07/24/2023 PARTIALLY APPROVED RMARTIN
Note: 7/24/23 large room by porch 7/20/2023 - PREVIOUS INSPECTION NOTES porch area
ELECTRIC 2ND ROUGH 07/20/2023 PARTIALLY APPROVED RMARTIN
Note: porch area
HVAC ROUGH 07/05/2023 PARTIALLY APPROVED CPISCITELLI
Note: inspected connections above hard ceiling 6/21/2023 - PREVIOUS INSPECTION NOTES Inspected exhaust duct to roof 5/2/2023 - PREVIOUS INSPECTION NOTES Inspected metal duct to be able to wrap and inspected ductboard trunkline
FRAMING 06/23/2023 APPROVED FWILLIS
Note: 5/25/2023 - PREVIOUS INSPECTION NOTES 5/24/2023 - PREVIOUS INSPECTION NOTES NO ONE ON SITE AT THE TIME OF MY VISIT. ENTRY DOOR WAS LOCKED AND LIGHTS OFF. NO APPROVED DRAWINGS OUTSIDE. 6/23/23 - CHIMNEY IN THE OUTDOOR ROOM. ALSO FRAME INSIDE.
HVAC ROUGH 06/21/2023 PARTIALLY APPROVED CPISCITELLI
Note: Inspected exhaust duct to roof 5/2/2023 - PREVIOUS INSPECTION NOTES Inspected metal duct to be able to wrap and inspected ductboard trunkline
PLUMBING 2ND ROUGH 06/15/2023 APPROVED JWALKER
Note: Check for correct floor drains and trap seals
ROOF IN PROGRESS 06/09/2023 APPROVED FWILLIS
Note: 6/8/2023 - PREVIOUS INSPECTION NOTES 6/9/23 - NEED PRODUCT APPROVAL SHEET AND AFFIDAVIT AT NEXT INSPECTION.
ROOF IN PROGRESS 06/08/2023 CANCELLED BY APPLICANT FWILLIS
INSULATION 06/08/2023 APPROVED FWILLIS
FRAMING 05/25/2023 PARTIALLY APPROVED FWILLIS
Note: 5/24/2023 - PREVIOUS INSPECTION NOTES NO ONE ON SITE AT THE TIME OF MY VISIT. ENTRY DOOR WAS LOCKED AND LIGHTS OFF. NO APPROVED DRAWINGS OUTSIDE.
FRAMING 05/24/2023 Disapproved - NO FEE FWILLIS
Note: NO ONE ON SITE AT THE TIME OF MY VISIT. ENTRY DOOR WAS LOCKED AND LIGHTS OFF. NO APPROVED DRAWINGS OUTSIDE.
CONCRETE FORM WORK 05/19/2023 APPROVED DHANEY
HVAC ROUGH 05/02/2023 PARTIALLY APPROVED CPISCITELLI
Note: Inspected metal duct to be able to wrap and inspected ductboard trunkline
ROOF SHEATHING / BRACE / TIE DOWN 04/26/2023 APPROVED FWILLIS
Note: 4/24/2023 - PREVIOUS INSPECTION NOTES NOT READY YET.
ROOF SHEATHING / BRACE / TIE DOWN 04/24/2023 Disapproved - NO FEE FWILLIS
Note: NOT READY YET. GAVE THE OKAY TO DRY-IN THE ROOF. JUST THE PEEL AND STICK..
LINTEL 04/17/2023 APPROVED FWILLIS
Note: Inspector Notes from Inspection 3280 3/29/23 Please have engineer letter submitted to the building department regarding the compaction testing. 2/27/2023 - PREVIOUS INSPECTION NOTES NEED PROOF OF COMPACTION. INSPECTED FOOTER AND IT IS GOOD.
FOUND SURVEY APPROVED (OFFICE) 04/14/2023 APPROVED DLEAP
MONOLITHIC SLAB 03/30/2023 APPROVED JWALKER
Note: Mono slab at the exterior and the interior footing under shearwall approved
FOOTER 03/29/2023 APPROVED - AS NOTED JWALKER
Note: 3/29/23 Please have engineer letter submitted to the building department regarding the compaction testing. 2/27/2023 - PREVIOUS INSPECTION NOTES NEED PROOF OF COMPACTION. INSPECTED FOOTER AND IT IS GOOD.
PLUMBING 1ST ROUGH 03/16/2023 APPROVED JWALKER
FOOTER 02/27/2023 Disapproved - NO FEE FWILLIS
Note: NEED PROOF OF COMPACTION. INSPECTED FOOTER AND IT IS GOOD.

Review History

Department Status Date In Date Out
BLD COMPLETE 12/18/2023 12/18/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ELEC COMPLETE 12/18/2023 12/18/2023
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
MECH COMPLETE 12/18/2023 12/18/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
PLUM COMPLETE 12/18/2023 12/18/2023
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM
BLD COMPLETE 08/02/2023 08/11/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
BLD COMPLETE 06/12/2023 06/21/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
BLD HOLD 06/05/2023 06/12/2023
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Drawing needs to be signed and sealed with a verfiable signature.
ELEC COMPLETE 06/05/2023 06/06/2023
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
BLD COMPLETE 05/17/2023 06/01/2023
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM
MECH COMPLETE 04/27/2023 05/02/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
PLENG COMPLETE 04/13/2023 04/14/2023
Note: Released By: DENNIS R. LEAP, P.E. - (386)986-2482 - DLEAP@PALMCOASTGOV.COM
BLD COMPLETE 03/30/2023 04/12/2023
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM
BADMIN INFORMATION 09/08/2022 09/08/2022
Note: Marked INFORMATION By: MARGA DEFREITAS - - MDEFREITAS@PALMCOASTGOV.COM THE FIRE SUBCONTRACTOR NEEDS A SEPERATE PERMIT YOU NEED TO SUBMIT A ROOFING SUBCONTRACTOR
BLD COMPLETE 05/10/2022 05/10/2022
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM
BLD HOLD 04/26/2022 04/26/2022
Note: Held By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM Provide shoring plan as noted per FS 553 Sec.79. designed by a licensed Florida Engineer. Harold Allen.
DSD COMPLETE 04/26/2022 04/26/2022
Note: Released By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM
BADMIN HOLD 04/26/2022 04/26/2022
Note: Held By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM A permit application signed by the licensed contractor and includes all subcontractors to be submitted before the permit can be made ready.
ARCHR COMPLETE 04/12/2022 04/13/2022
Note: Released By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM See DSD comments.
DSD HOLD 04/12/2022 04/13/2022
Note: Held By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM 1. Wall colors. a. Light pastel colors and white. Acceptable light pastel colors and white shall have LRV of 80 or greater. b. Earth tones. Earth tones include shades of brown, brown-taupe or sandy-taupe, beige, terra cotta, olive, sage and gray. Acceptable earth tone shades shall have a LRV of 25 or greater. 1. Wall color combinations. b. Multi-family and non-residential buildings may vary wall color vertically between building masses, horizontally between stories, or a combination thereof, but no more than three colors can be used per building. 2. Accent color combinations. Accent colors should offer some contrast, and can therefore be darker, lighter, brighter, or richer than wall colors. However, the main consideration in choosing accent colors shall be compatibility with the wall color. Two accent colors shall be allowed per building. Accent colors shall complement the building's wall color. Accent colors shall not exceed 20 percent of any one elevation. Unpainted natural stone, brick, roof material or natural appearing substitutes are excluded from exterior color requirements.
MECH COMPLETE 04/12/2022 04/14/2022
Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM
PLUM COMPLETE 04/12/2022 04/19/2022
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
BLD COMPLETE 04/12/2022 04/19/2022
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
ELEC COMPLETE 04/12/2022 04/13/2022
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
FI1 COMPLETE 04/12/2022 04/13/2022
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ARCHR HOLD 03/28/2022 03/29/2022
Note: Held By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM Update the "Color Schedule" table on sheet A200.1 with colors to be used for the wall and trim. Add linear width of the addition. Add roof pitch.
BLD HOLD 03/28/2022 04/11/2022
Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code REVIEW COMMENTS: 1. Sheet S2.1 – Existing Construction Note #1, Shore existing roof framing as required. Shoring is to be designed by a licensed Florida Engineer. Provide shoring plan as noted per FS 553 Sec.79. 2. Office space is calculated at 100 sf per occupant. Per Table 1004..5, the correct occupant load is to be calculated at 150 per sf.
DSD HOLD 03/28/2022 03/29/2022
Note: Held By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM On Sheet A010 Provide new pad addition dimensions. Provide new impervious and pervious calculation in percentages. Provide a landscape plan. Add addition height.
ELEC COMPLETE 03/28/2022 03/31/2022
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
FI1 COMPLETE 03/28/2022 04/11/2022
Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please add a Fire Extinguisher (with Cabinet) in the addtion area so that the extinguisher is not obscurted from view per NFPA 10, 6.1.3.1
MECH HOLD 03/28/2022 04/01/2022
Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide Heatload Calculation per C403.2.1 FBC Energy Conservation 2020 7Th edition 2. Tempstar 5 ton system is on a permit that was never finaled. Will the final be under this permit or will the previous contractor be reopening the permit and have it finaled. (Permit # 2021061323)
PLUM HOLD 03/28/2022 04/05/2022
Note: Held By: FRED REODICA - (386)986-4734 - FREODICA@PALMCOASTGOV.COM Provide service sink per FBCP 7th Ed. Sec. 403.1. If it is existing, identify it on plumbing plan for clarity - FBC 7th Ed. Sec. 107.3.
UD1 COMPLETE 03/28/2022 03/29/2022
Note: Released By: CHRIS JOHNSON - (386)986-2384 - CJOHNSON@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
PLAN REVIEW - REVISION ¤32.50 12/27/2023
PLAN REVIEW - REVISION ¤32.50 12/27/2023
CONTRACTOR CHANGE ¤20.00 10/13/2022
3% FIRE IMPACT FEE CREDIT (¤19.34) 10/13/2022
IMPACT FEE FIRE ¤644.80 10/13/2022
SURCHARGE FS 533.721 ¤63.39 10/13/2022
SURCHARGE - FS 468.631 ¤95.08 10/13/2022
SW ENG REVIEW- 40 ¤40.00 10/13/2022
SITE PLAN 30 ¤30.00 10/13/2022
ADJUSTMENT 50% (¤6,150.00) 10/13/2022
ADMINISTRATIVE - COMMERCIAL ¤75.00 10/13/2022
INSPECTION COMMERCIAL ¤10,500.00 10/13/2022
PLAN REVIEW - COMMERCIAL ¤1,725.00 10/13/2022
Fees Total Due: ¤0.00 Total Paid: ¤7,088.93