I want to search for...
Permit #2022041272
Permit Details
Status: COED
| Parcel Id: 07-11-31-7004-00080-0030 |
| Block: 00080 |
| Subdivision: 2203 - SECTION 4-COUNTRY CLUB COVE |
| Job Phone: 904-759-6435 |
| Location Address: 9 CLARIDGE CT N |
| Type: RF - REROOF |
| Issue Date: 04/25/2022 |
| NOC: RECORDED |
| Applicant name: DAVID GLENN ENGLAND |
| Owner: DANYUS MICHAEL & PATRICIA M |
|
Address 9 CLARIDGE COURT NORTH PALM COAST, FL 32137 |
| Lot: 0030 |
| Contracted Stated Job Value: ¤8,000.00 |
| Job Description: re-roof |
| Type: CN |
Contractor
ENGLAND CLASSIC ROOFING INC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
PO BOX 840006 ST AUGUSTINE, FL 32080 |
CCC1330631 (Exp: 08/31/2026) | 904-759-6435 |
Inspection History
| Type | Request Date | Result | Inspector |
| ROOF FINAL | 06/06/2022 | FINAL APPROVED | MKRASKI |
| ROOF IN PROGRESS- MIDROOF | 06/02/2022 | APPROVED | LMILLER |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION not ready still stripping 6-1-22 1. Revision needed for type of shingles and underlayment. (gaf was used for both) 2. underlayment was not lapped properly to achieve double coverage per manufacturer specs. (all shingles will need to be removed and place new underlayment per code and manufacutrer specs). (do not place any shingled in the areas where shigngle were removed prior to next midroof inspection). 3. underlayment overlaps need to be nailed 6 inches OC max, and 12 inch max OC in the field (recall midroof when shingles have been removed, new underlayment applied per specs, and have up to 25 percent shingles attached. 6-2-22 notes above resolved | |||
| ROOF IN PROGRESS- MIDROOF | 06/01/2022 | Disapproved -FEE REQUIRED | LMILLER |
| Note: THIS IS A REINSPECTION not ready still stripping 6-1-22 1. Revision needed for type of shingles and underlayment. (gaf was used for both) 2. underlayment was not lapped properly to achieve double coverage per manufacturer specs. (all shingles will need to be removed and place new underlayment per code and manufacutrer specs). (do not place any shingled in the areas where shigngle were removed prior to next midroof inspection). 3. underlayment overlaps need to be nailed 6 inches OC max, and 12 inch max OC in the field (recall midroof when shingles have been removed, new underlayment applied per specs, and have up to 25 percent shingles attached. | |||
| ROOF AFFIDAVIT | 05/31/2022 | APPROVED | STHOMAS |
| ROOF IN PROGRESS- MIDROOF | 05/31/2022 | Disapproved - NO FEE | LMILLER |
| Note: not ready still stripping |
Review History
| Department | Status | Date In | Date Out |
| BADMIN | INFORMATION | 06/02/2022 | 06/02/2022 |
| Note: Marked INFORMATION By: MARGA DEFREITAS - - MDEFREITAS@PALMCOASTGOV.COM IF YOU ARE CHANGING THE PRODUCT APPFOVAL NUMBERS YOU WILL NEED TO SUBMIT A NEW ROOFING WORKSHEET | |||
| BLD | COMPLETE | 06/02/2022 | 06/02/2022 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| PLAN REVIEW - REVISION | ¤32.50 | 06/02/2022 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 06/02/2022 |
| SURCHARGE FS 533.721 | ¤2.00 | 04/25/2022 |
| SURCHARGE - FS 468.631 | ¤2.00 | 04/25/2022 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 04/25/2022 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 04/25/2022 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤166.50 |