Permit #2022051004

Permit Details

Status: FINAL

Parcel Id: 10-11-30-5115-00000-0030
Subdivision: -
Job Phone: 352-373-1738
Location Address: 1000 GRAND AVE
Type: FCA - COMMERCIAL FIRE ALARM
Issue Date: 01/05/2023
NOC: RECORDED
Applicant name: BRIAN B KINSELL
Owner: POINTE GRAND PALM COAST LLC

Address

1031 W MORSE BLVD SUITE 240

WINTER PARK, FL 32789

Contracted Stated Job Value: ¤9,500.00
Job Description: BLDG #1 FIRE ALARM SYSTEM
Type: CN

Contractor

GATOR FIRE EXTINGUISHER COMPANY INC
Status Location Address State License Number Phone Fax
ACTIVE

1032 S MAIN STREET

GAINESVILLE, FL 32601

EF0000394 (Exp: 08/31/2026) 352-373-1738 352-338-1079

Inspection History

Type Request Date Result Inspector
FIRE ALARM FINAL 08/24/2023 FINAL APPROVED RMARTIN
FIRE ALARM 1ST ROUGH 01/09/2023 APPROVED RMARTIN

Review History

Department Status Date In Date Out
FI1 COMPLETE 04/06/2023 04/10/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
FI1 COMPLETE 01/05/2023 01/06/2023
Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM
BADMIN INFORMATION 01/05/2023 01/05/2023
Note: Marked INFORMATION By: MARGA DEFREITAS - - MDEFREITAS@PALMCOASTGOV.COM renmae the file name to what they are
FI1 COMPLETE 12/16/2022 01/04/2023
Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM No inspection until plans are revised and approved. An inspection hold will be placed on the permit until such time as the plans are approved. Work can begin but no inspections can be called in or performed prior to approval of plans. WLM 4. Some room names still overlay other information, Please ensure the Room names required by NFPA 72:7.2.1 (3)-(c) do not obscure other pertinent information. (on sheet FA-4) 9. Some Pathways still do not correlate properly between Riser diagram and Floor plan Pathways. Please provide pathway diagrams between the control unit and the supervising station and shared communications equipment (Riser diagrams do not match the floor plan layout) per NFPA 72:7.2.1 (11) (the floor plan circuits and the Riser Diagram are still not matching, (check FCPS 1-1)(floor plan).
FI1 CANCEL 12/15/2022
FI1 HOLD 12/01/2022 12/13/2022
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please provide a written response to each comment below in a response letter and provide clouded response changes on plan sheets and add page locations for each response. 1. OK 2. OK 3. OK 4. Some room names still overlay other information, Please ensure the Room names required by NFPA 72:7.2.1 (3)-(c) do not obscure other pertinent information. 5. OK 6. OK 7. OK 8. OK 9. Some Pathways still do not correlate properly between Riser diagram and Floor plan Pathways. Please provide pathway diagrams between the control unit and the supervising station and shared communications equipment (Riser diagrams do not match the floor plan layout) per NFPA 72:7.2.1 (11) (the floor plan circuits and the Riser Diagram are still not matching, (check all) 10. OK 11. OK 12. OK 13. OK 14. OK
FI1 HOLD 10/07/2022 10/12/2022
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please provide a written response to each comment below in a response letter and provide clouded response changes on plan sheets and add page locations for each response. 1. OK 2. Sheet FA-2 still indicates NFPA 72 (2018), all plan sheets need to indicate NFPA 72 (2016) as requested 3. OK 4. Some room names overlay other information, Please ensure the Room names required by NFPA 72:7.2.1 (3)-(c) do not obscure other pertinent information. 5. OK 6. OK 7. OK 8. OK 9. Please provide pathway diagrams between the control unit and the supervising station and shared communications equipment (Riser diagrams do not match the floor plan layout) per NFPA 72:7.2.1 (11) (the floor plan circuits and the Riser Diagram are still not matching, (check all) 10. Please place the Pathway Classification on the documents and indicate the sheet location in the response letter, and cloud the area on the sheet. For the requested information. Requested prior per NFPA 72:12.3 11. OK 12. OK 13. OK 14. OK
BADMIN INFORMATION 09/22/2022 09/22/2022
Note: Marked INFORMATION By: SCOTT THOMAS - - STHOMAS@PALMCOASTGOV.COM RENAME TO FA1_2-FA-1.PDF, FA1_2-FA-2.PDF, FA3_4-FA-3.PDF, FA3_4-FA-4.PDF
FI1 HOLD 05/17/2022 06/01/2022
Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM Provide response letter detailing corrections and cloud all corrections on plans 1. Please upload plan pages seperately 2. All Pages need to reference NFPA 72 2016 edition. (Some say 2013 and others say 2019) 3. Reference FFPC 7Th Edition 4. Please provide room use identification per NFPA 72:7.2.1 (3)-(c) 5. Please provide Equipment Technical Data Sheets per NFPA 72:7.2.1 (5) 6. Please provide Manufacturers’ published instructions, including operation and maintenance instructions per NFPA 72:7.2.1 (6) 7. Please provide battery capacity and de-rating calculations (where batteries are provided per NFPA 72:7.2.1 (7) 8. Please provide voltage drop calculations for notification appliance circuits per NFPA 72:7.2.1 (8) 9. Please provide pathway diagrams between the control unit and the supervising station and shared communications equipment (Riser diagrams do not match the floor plan layout) per NFPA 72:7.2.1 (11) 10. Please provide pathway classification per NFPA 72:12.3 11. Please make sure the symbols used on the plan pages and the symbol legend are the Symbols directed in NFPA 170 per NFPA 72:7.2.3 12. There are devices on the plans that are not identified in the symbol legend, please ensure all devices have a correlating symbol in the legend. 13. Please identify Required Accessible units for review per FBC 809.5.1.1 14. Need to identify the ADA horn strobes on the floor plans and in riser diagram per Note 5 fire alarm general notes on page (FA-3)

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
EXTENSION ¤40.00 08/17/2023
PLAN REVIEW - REVISION ¤32.50 04/14/2023
SURCHARGE FS 533.721 ¤2.00 01/05/2023
SURCHARGE - FS 468.631 ¤2.00 01/05/2023
INSPECTION - FIRE COMMERCIAL ¤66.00 01/05/2023
PLAN REVIEW - COMMERCIAL ¤115.00 01/05/2023
ADJUSTMENT 50% (¤128.00) 01/05/2023
ADMINISTRATIVE - COMMERCIAL ¤75.00 01/05/2023
Fees Total Due: ¤0.00 Total Paid: ¤204.50