Permit #2022051031
Permit Details
Status: FINAL
| Parcel Id: 10-11-30-5115-00000-0030 |
| Subdivision: - |
| Job Phone: 352-373-1738 |
| Location Address: 9000 HILLPOINTE WAY |
| Type: FCA - COMMERCIAL FIRE ALARM |
| Issue Date: 01/11/2023 |
| NOC: RECORDED |
| Applicant name: BRIAN B KINSELL |
| Owner: POINTE GRAND PALM COAST LLC |
|
Address 1031 W MORSE BLVD SUITE 240 WINTER PARK, FL 32789 |
| Contracted Stated Job Value: ¤9,500.00 |
| Job Description: BLDG #9 FIRE ALARM SYSTEM |
| Type: CN |
Contractor
GATOR FIRE EXTINGUISHER COMPANY INC
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
1032 S MAIN STREET GAINESVILLE, FL 32601 |
EF0000394 (Exp: 08/31/2026) | 352-373-1738 | 352-338-1079 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE ALARM FINAL | 08/29/2023 | FINAL APPROVED | RMARTIN |
| FIRE ALARM 1ST ROUGH | 02/13/2023 | APPROVED | RMARTIN |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 04/06/2023 | 04/10/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| FI1 | COMPLETE | 01/10/2023 | 01/11/2023 |
| Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM | |||
| FI1 | CANCEL | 12/16/2022 | |
| FI1 | HOLD | 12/16/2022 | 01/04/2023 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM 4. Some room names still overlay other information, Please ensure the Room names required by NFPA 72:7.2.1 (3)-(c) do not obscure other pertinent information. (on sheet FA-4) 9. Some Pathways still do not correlate properly between Riser diagram and Floor plan Pathways. Please provide pathway diagrams between the control unit and the supervising station and shared communications equipment (Riser diagrams do not match the floor plan layout) per NFPA 72:7.2.1 (11) (the floor plan circuits and the Riser Diagram are still not matching, (check FCPS 1-1)(floor plan and Riser Diagram) | |||
| FI1 | HOLD | 12/01/2022 | 12/12/2022 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please provide a written response to each comment below in a response letter and provide clouded response changes on plan sheets and add page locations for each response. 1. OK 2. OK 3. OK 4. The following note was not corrected in its entirety. Some room names still overlay other information on Sheet FA-4, Please ensure the Room names required by NFPA 72:7.2.1 (3)-(c) do not obscure other pertinent information. 5. OK 6. OK 7. OK 8. OK 9. Response not accepted. Please provide pathway diagrams between the control unit and the supervising station and shared communications equipment (Riser diagrams do not match the floor plan layout) per NFPA 72:7.2.1 (11) (the floor plan circuits and the Riser Diagram are still not matching, (check all) (Please check, all for instance see the FCPS1-1 riser diagram on sheet FA-3 calls for LF devices however the first floor fire alarm plan do not show the LF devices at the end of the line, this may not be the only discrepancy lease check all). 10. OK 11. OK 12. OK 13. OK 14. OK | |||
| FI1 | HOLD | 10/12/2022 | 10/13/2022 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please provide a written response to each comment below in a response letter and provide clouded response changes on plan sheets and add page locations for each response. 1. OK 2. Sheet FA-2 still indicates NFPA 72 (2018), all plan sheets need to indicate NFPA 72 (2016) as requested 3. OK 4. Some room names overlay other information, Please ensure the Room names required by NFPA 72:7.2.1 (3)-(c) do not obscure other pertinent information. 5. OK 6. OK 7. OK 8. OK 9. Please provide pathway diagrams between the control unit and the supervising station and shared communications equipment (Riser diagrams do not match the floor plan layout) per NFPA 72:7.2.1 (11) (the floor plan circuits and the Riser Diagram are still not matching, (check all) 10. Please place the Pathway Classification on the documents and indicate the sheet location in the response letter, and cloud the area on the sheet. For the requested information. Requested prior per NFPA 72:12.3 11. OK 12. OK 13. Please identify required accessible units for review per FBC 809.5.1.1 Your Response letter indicates the ADA and ADA-Hearing Impaired rooms are listed on sheets FA3 and FA4 and Hearing impaired units are supplied with 177cd strobes. (These items were not found on the plan sheets indicated) 14. Your response letter indicates: Note 5 no longer applies to this. Added Note 6 on buildings containing Hearing Impaired Units to clarify the ADA strobes and the operation of them. Note that the layouts of Units 1101 and 1103 in bldgs 1000,2000 and 3000 were revised from horns with 177 cd strobes to individual horns circuited from the Fire Alarm NAC circuit and separately circuited 177 cd strobes. This was required due to the fact that the low frequency horn strobes are not available with 177 cd strobes as a single unit. (no such changes were found on indicated sheets). | |||
| FI1 | HOLD | 10/07/2022 | 10/12/2022 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM The response letter requested below was not uploaded please upload the letter as requested with clouded corrections Provide response letter detailing corrections and cloud all corrections on plans 1. All Pages need to reference NFPA 72 2016 edition. (Some say 2013 and others say 2019) 2. Reference FFPC 7Th Edition 3. Please provide room use identification per NFPA 72:7.2.1 (3)-(c) 4. Please provide Equipment Technical Data Sheets per NFPA 72:7.2.1 (5) 5. Please provide Manufacturers’ published instructions, including operation and maintenance instructions per NFPA 72:7.2.1 (6) 6. Please provide battery capacity and de-rating calculations (where batteries are provided per NFPA 72:7.2.1 (7) 7. Please provide voltage drop calculations for notification appliance circuits per NFPA 72:7.2.1 (8) 8. Please provide pathway diagrams between the control unit and the supervising station and shared communications equipment (Riser diagrams do not match the floor plan layout) per NFPA 72:7.2.1 (11) 9. Please provide pathway classification per NFPA 72:12.3 10. Please make sure the symbols used on the plan pages and the symbol legend are the Symbols directed in NFPA 170 per NFPA 72:7.2.3 11.There are devices on the plans that are not identified in the symbol legend, please ensure all devices have a correlating symbol in the legend. 12. Please identify Required Accessible units for review per FBC 809.5.1.1 13. Need to identify the ADA horn strobes on the floor plans and in riser diagram per Note 5 fire alarm general notes on page (FA-3) | |||
| BADMIN | INFORMATION | 09/22/2022 | 09/22/2022 |
| Note: Marked INFORMATION By: SCOTT THOMAS - - STHOMAS@PALMCOASTGOV.COM RENAME TO FA1_2-FA-1.PDF, FA1_2-FA-2.PDF, FA3_4-FA-3.PDF, FA3_4-FA-4.PDF | |||
| FI1 | HOLD | 05/17/2022 | 06/01/2022 |
| Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM Provide response letter detailing corrections and cloud all corrections on plans 1. All Pages need to reference NFPA 72 2016 edition. (Some say 2013 and others say 2019) 2. Reference FFPC 7Th Edition 3. Please provide room use identification per NFPA 72:7.2.1 (3)-(c) 4. Please provide Equipment Technical Data Sheets per NFPA 72:7.2.1 (5) 5. Please provide Manufacturers’ published instructions, including operation and maintenance instructions per NFPA 72:7.2.1 (6) 6. Please provide battery capacity and de-rating calculations (where batteries are provided per NFPA 72:7.2.1 (7) 7. Please provide voltage drop calculations for notification appliance circuits per NFPA 72:7.2.1 (8) 8. Please provide pathway diagrams between the control unit and the supervising station and shared communications equipment (Riser diagrams do not match the floor plan layout) per NFPA 72:7.2.1 (11) 9. Please provide pathway classification per NFPA 72:12.3 10. Please make sure the symbols used on the plan pages and the symbol legend are the Symbols directed in NFPA 170 per NFPA 72:7.2.3 11.There are devices on the plans that are not identified in the symbol legend, please ensure all devices have a correlating symbol in the legend. 12. Please identify Required Accessible units for review per FBC 809.5.1.1 13. Need to identify the ADA horn strobes on the floor plans and in riser diagram per Note 5 fire alarm general notes on page (FA-3) |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| PLAN REVIEW - REVISION | ¤32.50 | 04/14/2023 |
| SURCHARGE FS 533.721 | ¤2.56 | 01/11/2023 |
| SURCHARGE - FS 468.631 | ¤3.88 | 01/11/2023 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 01/11/2023 |
| INSPECTION - FIRE COMMERCIAL | ¤66.00 | 01/11/2023 |
| PLAN REVIEW - COMMERCIAL | ¤115.00 | 01/11/2023 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤294.94 |