Permit #2022051661

Permit Details

Status: COED

Parcel Id: 07-11-31-7007-00290-0020
CONDITIONED SPACE: 1941 sqft
GARAGE: 598 sqft
OPENED PORCH (WITH ROOF) : 264 sqft
OPENED PORCH (WITH ROOF) : 60 sqft
Total Square Footage: 2863 sqft
Block: 00290
Subdivision: 2185 - SECTION 7-FLORIDA PARK
Job Phone: 386-569-7882
Location Address: 42 FOREST HILL DR
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 06/09/2022
NOC: RECORDED
Applicant name: VLADIMIR V PEREPECHKIN
Owner: BEACH REALTY OF WESTCHESTER INC

Address

299 YACHT HARBOR DRIVE

PALM COAST, FL 32137

Lot: 0020
Contracted Stated Job Value: ¤350,000.00
Job Description: SINGLE RESIDENCE
Type: CN

Contractor

WISE CHOICE CUSTOM HOMES, INC.
Status Location Address State License Number Phone
ACTIVE

77 SOUTHLAKE DR

PALM COAST, FL 32137

CRC1328738 (Exp: 08/31/2026) 386-569-7882

Sub Contractors

OLEG BELINSKIY
Status Location Address State License Number Phone
ACTIVE

19 PINE CIRCLE DRIVE19

PALM COAST, FL 32167

CCC1325974 (Exp: 08/31/2026) 386-263-7906
GLEN WILLIAM KEHLE
Status Location Address State License Number Phone Fax
ACTIVE

P. O. Box 353511

BUNNELL, FL 32110

CFC057241 (Exp: 08/31/2026) (386) 447-4249 (386) 437-8488
MAXIM BUDNIK
Status Location Address State License Number
ACTIVE

3 WAVECREST PL

PALM COAST, FL 32164

CAC1818445 (Exp: 08/31/2026)
MAXIM BUDNIK
Status Location Address State License Number Phone
ACTIVE

9788 HALSEY RD

JACKSONVILLE, FL 32246

EC13007415 (Exp: 08/31/2026) 904-509-7306

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 04/12/2023 FINAL APPROVED AGAETANO
Note: 4/11/2023 - PREVIOUS INSPECTION NOTES 4/6/2023 - PREVIOUS INSPECTION NOTES 04-06-2023 1. Gust baths very low water pressure. 2. AHU high voltage wire needs to be sealed. 3. Guest bath at lanai outlet has no power. 4. Broken window front left garage. 04-11-2023 Number sign not posted on house.
BLD - BUILDING FINAL 04/11/2023 Disapproved -FEE REQUIRED AGAETANO
Note: 4/6/2023 - PREVIOUS INSPECTION NOTES 04-06-2023 1. Gust baths very low water pressure. 2. AHU high voltage wire needs to be sealed. 3. Guest bath at lanai outlet has no power. 4. Broken window front left garage. 04-11-2023 Number sign not posted on house.
BLD - BUILDING FINAL 04/06/2023 Disapproved - NO FEE AGAETANO
Note: 04-06-2023 1. Guest baths very low water pressure. 2. AHU high voltage wire needs to be sealed. 3. Guest bath at lanai outlet has no power. 4. Broken window front left garage.
ROW - STORMWATER FINAL 04/05/2023 FINAL APPROVED EMADISON
Note: ** 904/05/23 CORRECTIONS MADE EVERYTHING LOOKS GOOD AT THE TIME OF INSPECTION _________________________________________________________________________________________________________________ 4/4/2023 - PREVIOUS INSPECTION NOTES ** 04/03/23 REMOVE ALL TRASH AND CONSTRUCTION DEBRIS FROM PROPERTY AND LEFT SIDE VACANT HIGH LIGHTED WITH PINK PAINT ____________________________________________________________________________________________________________________________ ** 04/03/23 REMOVE ALL TRASH AND CONSTRUCTION DEBRIS FROM PROPERTY AND LEFT SIDE VACANT
U -UTILITY RESIDENTIAL FINAL 04/04/2023 FINAL APPROVED DHANEY
ROW - STORMWATER FINAL 04/04/2023 Disapproved -FEE REQUIRED EMADISON
Note: ** 04/03/23 REMOVE ALL TRASH AND CONSTRUCTION DEBRIS FROM PROPERTY AND LEFT SIDE VACANT HIGH LIGHTED WITH PINK PAINT ____________________________________________________________________________________________________________________________ ** 04/03/23 REMOVE ALL TRASH AND CONSTRUCTION DEBRIS FROM PROPERTY AND LEFT SIDE VACANT
ROW- FINAL SURVEY/GRADING CERTIFICATION 04/03/2023 APPROVED EMADISON
Note: ** 04/03/23 CONDUCTED FINAL SURVEY ON SITE THERE IS AN ELEVATION RISE BEYOND PROPERTY LINE THE DRAINAGE WILL WORK AS NEEDED. ______________________________________________________________________________________________________________________ 3/24/2023 - PREVIOUS INSPECTION NOTES ** 03/24/23 Drainage still needs to go down property line. DRAINAGE CAN FALL ON VACANT LOTS ON SIDES TO MAKE A COMMON SWALE. 3/23/2023 - PREVIOUS INSPECTION NOTES ** 03/23/23 DRAINAGE ON LEFT SIDE OF HOUSE NEEDS TO BE GOING DOWN THE PROPERTY LINE DUE TO VACANT LOT ON LEFT SIDE.
ROW FIELD SURVEY /GRADING CERTIFICATION 04/03/2023 APPROVED EMADISON
Note: ** 04/03/23 REMOVE ALL TRASH AND CONSTRUCTION DEBRIS FROM PROPERTY AND LEFT SIDE VACANT
ROW - FINAL APRON (AFTER POUR) 04/03/2023 FINAL APPROVED EMADISON
ROW- FINAL SURVEY/GRADING CERTIFICATION 03/24/2023 Disapproved -FEE REQUIRED FSLADISH
Note: ** 03/24/23 Drainage still needs to go down property line. DRAINAGE CAN FALL ON VACANT LOTS ON SIDES TO MAKE A COMMON SWALE. 3/23/2023 - PREVIOUS INSPECTION NOTES ** 03/23/23 DRAINAGE ON LEFT SIDE OF HOUSE NEEDS TO BE GOING DOWN THE PROPERTY LINE DUE TO VACANT LOT ON LEFT SIDE.
ROW- FINAL SURVEY/GRADING CERTIFICATION 03/23/2023 Disapproved - NO FEE FSLADISH
Note: ** 03/23/23 DRAINAGE ON LEFT SIDE OF HOUSE NEEDS TO BE GOING DOWN THE PROPERTY LINE DUE TO VACANT LOT ON LEFT SIDE.
U-CROSS CONNECTION 02/15/2023 APPROVED - AS NOTED DHANEY
Note: Yard not installed yet - no cross cn. .
ELECTRIC - EARLY POWER 02/13/2023 APPROVED AGAETANO
Note: 02-13-2023 FPL notified at 11:19 am. Note to builder - a broken window on the front right garage window.
ROW- PRE-APRON (PRE-POUR) 02/09/2023 APPROVED PFLANAGAN
Note: IT'S THE CONTRACTORS RESPONSIBILITY TO CHECK THE CULVERT PIPE ELEVATIONS BEFORE POURING THE CONCRETE FOR THE DRIVEWAY.
U - SEWER TIE IN 02/09/2023 APPROVED - AS NOTED MGIBSON
Note: UTILITY MADE U-SEWER TIE IN , CONTRACTOR NEEDS TO SCHEDULE GRAVITY SEWER FOR 2/13/23
GRAVITY SEWER TEST 01/06/2023 APPROVED AGAETANO
INSULATION 12/27/2022 APPROVED AGAETANO
ALL ROUGH 12/19/2022 APPROVED AGAETANO
Note: 12/15/2022 - PREVIOUS INSPECTION NOTES 12/13/2022 - PREVIOUS INSPECTION NOTES 12/12/2022 - PREVIOUS INSPECTION NOTES Need mechanical plans on site for inspection. Entire lenght of seam on dryer duct must be sealed 12-13-2022 Bath adjacent to garage and bath in back need vertical vent mid point bracing. PIPING SUPPORT - MID STORY SUPPRORT (BRACING ON A VERTICAL / HORIZONTAL VENT) TABLE P2605.1 PIPING SUPPORT – 2” AND SMALLER REQUIRE MID POINT BRACING. 10b VERTICAL 12-15-202 Issues have not been resolved. Check all. PIPING SUPPORT - MID STORY SUPPRORT (BRACING ON A VERTICAL / HORIZONTAL VENT) TABLE P2605.1 PIPING SUPPORT – 2” AND SMALLER REQUIRE MID POINT BRACING. 10b VERTICAL
ALL ROUGH 12/15/2022 Disapproved -FEE REQUIRED AGAETANO
Note: 12/13/2022 - PREVIOUS INSPECTION NOTES 12/12/2022 - PREVIOUS INSPECTION NOTES Need mechanical plans on site for inspection. Entire lenght of seam on dryer duct must be sealed 12-13-2022 Bath adjacent to garage and bath in back need vertical vent mid point bracing. PIPING SUPPORT - MID STORY SUPPRORT (BRACING ON A VERTICAL / HORIZONTAL VENT) TABLE P2605.1 PIPING SUPPORT – 2” AND SMALLER REQUIRE MID POINT BRACING. 10b VERTICAL 12-15-202 Issues have not been resolved. Check all. PIPING SUPPORT - MID STORY SUPPRORT (BRACING ON A VERTICAL / HORIZONTAL VENT) TABLE P2605.1 PIPING SUPPORT – 2” AND SMALLER REQUIRE MID POINT BRACING. 10b VERTICAL
ALL ROUGH 12/13/2022 Disapproved -FEE REQUIRED AGAETANO
Note: 12/12/2022 - PREVIOUS INSPECTION NOTES Need mechanical plans on site for inspection. Entire lenght of seam on dryer duct must be sealed 12-13-2022 Bath adjacent to garage and bath in back need vertical vent mid point bracing. PIPING SUPPORT - MID STORY SUPPRORT (BRACING ON A VERTICAL / HORIZONTAL VENT) TABLE P2605.1 PIPING SUPPORT – 2” AND SMALLER REQUIRE MID POINT BRACING. 10b VERTICAL
ALL ROUGH 12/12/2022 Disapproved - NO FEE KSANDOE
Note: Need mechanical plans on site for inspection. Entire lenght of seam on dryer duct must be sealed
LATH/BRICK/ WATER BARRIER 12/12/2022 APPROVED KSANDOE
WALL SHEATHING 12/05/2022 APPROVED AGAETANO
ROOF VALLEY & METAL 11/02/2022 APPROVED AGAETANO
ROOF SHEATHING / BRACES/TIES/DOWN CELL 10/25/2022 APPROVED AGAETANO
Note: 10/21/2022 - PREVIOUS INSPECTION NOTES 10/17/2022 - PREVIOUS INSPECTION NOTES 10-17-2022 1. Multiple straps not fastened on trusses. Check all. 2. A13 member missed. 3. A15 engineering packet sheet does not match truss installed. Please submit a revision to the buuilding department. 4. Please provide a large readable truss layout for inspection. 5. Please provide bearing wall locations and details. 6. Roof sheathing not fastened completely. Check all. 10-21-2022 1. Sheet 6/7 2F indicates on two details 2 x 6 studs. 2 x 4 installed. Please provide engineering or install as per plan.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 10/21/2022 Disapproved -FEE REQUIRED AGAETANO
Note: 10/17/2022 - PREVIOUS INSPECTION NOTES 10-17-2022 1. Multiple straps not fastened on trusses. Check all. 2. A13 member missed. 3. A15 engineering packet sheet does not match truss installed. Please submit a revision to the buuilding department. 4. Please provide a large readable truss layout for inspection. 5. Please provide bearing wall locations and details. 6. Roof sheathing not fastened completely. Check all. 10-21-2022 1. Sheet 6/7 2F indicates on two details 2 x 6 studs. 2 x 4 installed. Please provide engineering or install as per plan.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 10/17/2022 Disapproved -FEE REQUIRED AGAETANO
Note: 10-17-2022 1. Multiple straps not fastened on trusses. Check all. 2. A13 member missed. 3. A15 engineering packet sheet does not match truss installed. Please submit a revision to the buuilding department. 4. Please provide a large readable truss layout for inspection. 5. Please provide bearing wall locations and details. 6. Roof sheathing not fastened completely. Check all.
TIE BEAM / LINTEL 09/19/2022 APPROVED AGAETANO
FOUND SURVEY APPROVED (OFFICE) 09/09/2022 APPROVED TBAKER
MONOLITHIC SLAB 07/28/2022 APPROVED AGAETANO
PLUMBING 1ST ROUGH UNDERGROUND 07/26/2022 APPROVED MGIBSON

Review History

Department Status Date In Date Out
ENGIN1 COMPLETE 09/08/2022 09/09/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON COMPLETE 09/08/2022 09/08/2022
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
CUSVC HOLD 06/07/2022 06/07/2022
Note: Held By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM MISSING UTILITY APPLICATION
CUSVC COMPLETE 06/07/2022 06/09/2022
Note: Released By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM
ELEC COMPLETE 06/07/2022 06/07/2022
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
BLD COMPLETE 06/07/2022 06/08/2022
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
CUSVC HOLD 06/06/2022 06/06/2022
Note: Held By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM NEED A UTILITY APPLICATION
CUSVC HOLD 06/03/2022 06/03/2022
Note: Held By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM Need to upload Utility Application
CUSVC HOLD 06/02/2022 06/02/2022
Note: Held By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM Need a Utility application filled out.
BLD HOLD 05/31/2022 06/02/2022
Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code – Residential REVIEW COMMENTS: 1. Provide Product Approval for the following; Per F.S. 471.025 and F.A.C. 61 G15-23.005. Per F.S. a. Truss Plate b. Garage Door
CUSVC HOLD 05/31/2022 06/01/2022
Note: Held By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM No Utility application is filled out.
ELEC HOLD 05/31/2022 05/31/2022
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Submit electric load calcs. 2. Outlets in garage, outside, laundry, bathroom, kitchen need to be GFCI protected. NEC 2017 210.8 3. Need outlet by sink in spare bathroom. NEC 2017 210.52 (D)
ENGIN1 COMPLETE 05/31/2022 05/31/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
LOCATE COMPLETE 05/31/2022 06/07/2022
Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM
MECH COMPLETE 05/31/2022 05/31/2022
Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM
SW1 COMPLETE 05/31/2022 06/07/2022
Note: Released By: EDWARD MADISON - - EMADISON@PALMCOASTGOV.COM
ZON COMPLETE 05/31/2022 06/01/2022
Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM
SWALE COMPLETE 05/31/2022 08/15/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 04/12/2023
REINSPECTION RESIDENTIAL ¤40.00 04/12/2023
REINSPECTION RESIDENTIAL ¤40.00 04/12/2023
REINSPECTION RESIDENTIAL ¤40.00 04/12/2023
REINSPECTION RESIDENTIAL ¤40.00 04/12/2023
SW ENG REINSPECTION 20 ¤20.00 04/12/2023
SW ENG - REVIEW 20 ¤20.00 06/09/2022
SW ENG RES REVIEW 200 ¤200.00 06/09/2022
3% TRANS IMPACT FEE CREDIT (¤52.92) 06/09/2022
SEWER CREDIT (¤32.06) 06/09/2022
SEWER INSPECTION ¤25.00 06/09/2022
SEWER CAPITAL FACILITY ¤4,939.76 06/09/2022
WATER CAPITAL FACILITY FEE ¤3,626.50 06/09/2022
SITE PLAN 30 ¤30.00 06/09/2022
WATER- TURN ON ¤25.00 06/09/2022
ADMINISTRATIVE RESIDENTIAL ¤30.00 06/09/2022
INSPECTION - RESIDENTIAL ¤962.50 06/09/2022
PLAN REVIEW - RESIDENTIAL ¤273.00 06/09/2022
CONNECTION FEES ¤1,077.88 06/09/2022
3% FIRE IMPACT FEE CREDIT (¤11.66) 06/09/2022
IMPACT FEE FIRE ¤388.65 06/09/2022
IMPACT FEE PARKS ¤1,455.13 06/09/2022
IMPACT FEE SCHOOL ¤3,600.00 06/09/2022
IMPACT FEE TRANSPORTATION ¤1,764.00 06/09/2022
WATER -IRRIGATION INSPECTION ¤25.00 06/09/2022
3% PARKS IMPACT FEE CREDIT (¤43.65) 06/09/2022
SURCHARGE FS 533.721 ¤10.49 06/09/2022
SURCHARGE - FS 468.631 ¤15.73 06/09/2022
SW ENG - FOUNDATION SURVEY ¤20.00 06/09/2022
SW ENG INSPECTION 80 ¤80.00 06/09/2022
SW ENG PRE APRON ¤30.00 06/09/2022
Fees Total Due: ¤0.00 Total Paid: ¤18,678.35