Permit #2022051661
Permit Details
Status: COED
| Parcel Id: 07-11-31-7007-00290-0020 |
| CONDITIONED SPACE: 1941 sqft |
| GARAGE: 598 sqft |
| OPENED PORCH (WITH ROOF) : 264 sqft |
| OPENED PORCH (WITH ROOF) : 60 sqft |
| Total Square Footage: 2863 sqft |
| Block: 00290 |
| Subdivision: 2185 - SECTION 7-FLORIDA PARK |
| Job Phone: 386-569-7882 |
| Location Address: 42 FOREST HILL DR |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 06/09/2022 |
| NOC: RECORDED |
| Applicant name: VLADIMIR V PEREPECHKIN |
| Owner: BEACH REALTY OF WESTCHESTER INC |
|
Address 299 YACHT HARBOR DRIVE PALM COAST, FL 32137 |
| Lot: 0020 |
| Contracted Stated Job Value: ¤350,000.00 |
| Job Description: SINGLE RESIDENCE |
| Type: CN |
Contractor
WISE CHOICE CUSTOM HOMES, INC.
| Status | Location Address | State License Number | Phone |
| ACTIVE |
77 SOUTHLAKE DR PALM COAST, FL 32137 |
CRC1328738 (Exp: 08/31/2026) | 386-569-7882 |
Sub Contractors
OLEG BELINSKIY
| Status | Location Address | State License Number | Phone |
| ACTIVE |
19 PINE CIRCLE DRIVE19 PALM COAST, FL 32167 |
CCC1325974 (Exp: 08/31/2026) | 386-263-7906 |
GLEN WILLIAM KEHLE
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
P. O. Box 353511 BUNNELL, FL 32110 |
CFC057241 (Exp: 08/31/2026) | (386) 447-4249 | (386) 437-8488 |
MAXIM BUDNIK
| Status | Location Address | State License Number |
| ACTIVE |
3 WAVECREST PL PALM COAST, FL 32164 |
CAC1818445 (Exp: 08/31/2026) |
MAXIM BUDNIK
| Status | Location Address | State License Number | Phone |
| ACTIVE |
9788 HALSEY RD JACKSONVILLE, FL 32246 |
EC13007415 (Exp: 08/31/2026) | 904-509-7306 |
Inspection History
| Type | Request Date | Result | Inspector |
| BLD - BUILDING FINAL | 04/12/2023 | FINAL APPROVED | AGAETANO |
| Note: 4/11/2023 - PREVIOUS INSPECTION NOTES 4/6/2023 - PREVIOUS INSPECTION NOTES 04-06-2023 1. Gust baths very low water pressure. 2. AHU high voltage wire needs to be sealed. 3. Guest bath at lanai outlet has no power. 4. Broken window front left garage. 04-11-2023 Number sign not posted on house. | |||
| BLD - BUILDING FINAL | 04/11/2023 | Disapproved -FEE REQUIRED | AGAETANO |
| Note: 4/6/2023 - PREVIOUS INSPECTION NOTES 04-06-2023 1. Gust baths very low water pressure. 2. AHU high voltage wire needs to be sealed. 3. Guest bath at lanai outlet has no power. 4. Broken window front left garage. 04-11-2023 Number sign not posted on house. | |||
| BLD - BUILDING FINAL | 04/06/2023 | Disapproved - NO FEE | AGAETANO |
| Note: 04-06-2023 1. Guest baths very low water pressure. 2. AHU high voltage wire needs to be sealed. 3. Guest bath at lanai outlet has no power. 4. Broken window front left garage. | |||
| ROW - STORMWATER FINAL | 04/05/2023 | FINAL APPROVED | EMADISON |
| Note: ** 904/05/23 CORRECTIONS MADE EVERYTHING LOOKS GOOD AT THE TIME OF INSPECTION _________________________________________________________________________________________________________________ 4/4/2023 - PREVIOUS INSPECTION NOTES ** 04/03/23 REMOVE ALL TRASH AND CONSTRUCTION DEBRIS FROM PROPERTY AND LEFT SIDE VACANT HIGH LIGHTED WITH PINK PAINT ____________________________________________________________________________________________________________________________ ** 04/03/23 REMOVE ALL TRASH AND CONSTRUCTION DEBRIS FROM PROPERTY AND LEFT SIDE VACANT | |||
| U -UTILITY RESIDENTIAL FINAL | 04/04/2023 | FINAL APPROVED | DHANEY |
| ROW - STORMWATER FINAL | 04/04/2023 | Disapproved -FEE REQUIRED | EMADISON |
| Note: ** 04/03/23 REMOVE ALL TRASH AND CONSTRUCTION DEBRIS FROM PROPERTY AND LEFT SIDE VACANT HIGH LIGHTED WITH PINK PAINT ____________________________________________________________________________________________________________________________ ** 04/03/23 REMOVE ALL TRASH AND CONSTRUCTION DEBRIS FROM PROPERTY AND LEFT SIDE VACANT | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 04/03/2023 | APPROVED | EMADISON |
| Note: ** 04/03/23 CONDUCTED FINAL SURVEY ON SITE THERE IS AN ELEVATION RISE BEYOND PROPERTY LINE THE DRAINAGE WILL WORK AS NEEDED. ______________________________________________________________________________________________________________________ 3/24/2023 - PREVIOUS INSPECTION NOTES ** 03/24/23 Drainage still needs to go down property line. DRAINAGE CAN FALL ON VACANT LOTS ON SIDES TO MAKE A COMMON SWALE. 3/23/2023 - PREVIOUS INSPECTION NOTES ** 03/23/23 DRAINAGE ON LEFT SIDE OF HOUSE NEEDS TO BE GOING DOWN THE PROPERTY LINE DUE TO VACANT LOT ON LEFT SIDE. | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 04/03/2023 | APPROVED | EMADISON |
| Note: ** 04/03/23 REMOVE ALL TRASH AND CONSTRUCTION DEBRIS FROM PROPERTY AND LEFT SIDE VACANT | |||
| ROW - FINAL APRON (AFTER POUR) | 04/03/2023 | FINAL APPROVED | EMADISON |
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 03/24/2023 | Disapproved -FEE REQUIRED | FSLADISH |
| Note: ** 03/24/23 Drainage still needs to go down property line. DRAINAGE CAN FALL ON VACANT LOTS ON SIDES TO MAKE A COMMON SWALE. 3/23/2023 - PREVIOUS INSPECTION NOTES ** 03/23/23 DRAINAGE ON LEFT SIDE OF HOUSE NEEDS TO BE GOING DOWN THE PROPERTY LINE DUE TO VACANT LOT ON LEFT SIDE. | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 03/23/2023 | Disapproved - NO FEE | FSLADISH |
| Note: ** 03/23/23 DRAINAGE ON LEFT SIDE OF HOUSE NEEDS TO BE GOING DOWN THE PROPERTY LINE DUE TO VACANT LOT ON LEFT SIDE. | |||
| U-CROSS CONNECTION | 02/15/2023 | APPROVED - AS NOTED | DHANEY |
| Note: Yard not installed yet - no cross cn. . | |||
| ELECTRIC - EARLY POWER | 02/13/2023 | APPROVED | AGAETANO |
| Note: 02-13-2023 FPL notified at 11:19 am. Note to builder - a broken window on the front right garage window. | |||
| ROW- PRE-APRON (PRE-POUR) | 02/09/2023 | APPROVED | PFLANAGAN |
| Note: IT'S THE CONTRACTORS RESPONSIBILITY TO CHECK THE CULVERT PIPE ELEVATIONS BEFORE POURING THE CONCRETE FOR THE DRIVEWAY. | |||
| U - SEWER TIE IN | 02/09/2023 | APPROVED - AS NOTED | MGIBSON |
| Note: UTILITY MADE U-SEWER TIE IN , CONTRACTOR NEEDS TO SCHEDULE GRAVITY SEWER FOR 2/13/23 | |||
| GRAVITY SEWER TEST | 01/06/2023 | APPROVED | AGAETANO |
| INSULATION | 12/27/2022 | APPROVED | AGAETANO |
| ALL ROUGH | 12/19/2022 | APPROVED | AGAETANO |
| Note: 12/15/2022 - PREVIOUS INSPECTION NOTES 12/13/2022 - PREVIOUS INSPECTION NOTES 12/12/2022 - PREVIOUS INSPECTION NOTES Need mechanical plans on site for inspection. Entire lenght of seam on dryer duct must be sealed 12-13-2022 Bath adjacent to garage and bath in back need vertical vent mid point bracing. PIPING SUPPORT - MID STORY SUPPRORT (BRACING ON A VERTICAL / HORIZONTAL VENT) TABLE P2605.1 PIPING SUPPORT – 2” AND SMALLER REQUIRE MID POINT BRACING. 10b VERTICAL 12-15-202 Issues have not been resolved. Check all. PIPING SUPPORT - MID STORY SUPPRORT (BRACING ON A VERTICAL / HORIZONTAL VENT) TABLE P2605.1 PIPING SUPPORT – 2” AND SMALLER REQUIRE MID POINT BRACING. 10b VERTICAL | |||
| ALL ROUGH | 12/15/2022 | Disapproved -FEE REQUIRED | AGAETANO |
| Note: 12/13/2022 - PREVIOUS INSPECTION NOTES 12/12/2022 - PREVIOUS INSPECTION NOTES Need mechanical plans on site for inspection. Entire lenght of seam on dryer duct must be sealed 12-13-2022 Bath adjacent to garage and bath in back need vertical vent mid point bracing. PIPING SUPPORT - MID STORY SUPPRORT (BRACING ON A VERTICAL / HORIZONTAL VENT) TABLE P2605.1 PIPING SUPPORT – 2” AND SMALLER REQUIRE MID POINT BRACING. 10b VERTICAL 12-15-202 Issues have not been resolved. Check all. PIPING SUPPORT - MID STORY SUPPRORT (BRACING ON A VERTICAL / HORIZONTAL VENT) TABLE P2605.1 PIPING SUPPORT – 2” AND SMALLER REQUIRE MID POINT BRACING. 10b VERTICAL | |||
| ALL ROUGH | 12/13/2022 | Disapproved -FEE REQUIRED | AGAETANO |
| Note: 12/12/2022 - PREVIOUS INSPECTION NOTES Need mechanical plans on site for inspection. Entire lenght of seam on dryer duct must be sealed 12-13-2022 Bath adjacent to garage and bath in back need vertical vent mid point bracing. PIPING SUPPORT - MID STORY SUPPRORT (BRACING ON A VERTICAL / HORIZONTAL VENT) TABLE P2605.1 PIPING SUPPORT – 2” AND SMALLER REQUIRE MID POINT BRACING. 10b VERTICAL | |||
| ALL ROUGH | 12/12/2022 | Disapproved - NO FEE | KSANDOE |
| Note: Need mechanical plans on site for inspection. Entire lenght of seam on dryer duct must be sealed | |||
| LATH/BRICK/ WATER BARRIER | 12/12/2022 | APPROVED | KSANDOE |
| WALL SHEATHING | 12/05/2022 | APPROVED | AGAETANO |
| ROOF VALLEY & METAL | 11/02/2022 | APPROVED | AGAETANO |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 10/25/2022 | APPROVED | AGAETANO |
| Note: 10/21/2022 - PREVIOUS INSPECTION NOTES 10/17/2022 - PREVIOUS INSPECTION NOTES 10-17-2022 1. Multiple straps not fastened on trusses. Check all. 2. A13 member missed. 3. A15 engineering packet sheet does not match truss installed. Please submit a revision to the buuilding department. 4. Please provide a large readable truss layout for inspection. 5. Please provide bearing wall locations and details. 6. Roof sheathing not fastened completely. Check all. 10-21-2022 1. Sheet 6/7 2F indicates on two details 2 x 6 studs. 2 x 4 installed. Please provide engineering or install as per plan. | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 10/21/2022 | Disapproved -FEE REQUIRED | AGAETANO |
| Note: 10/17/2022 - PREVIOUS INSPECTION NOTES 10-17-2022 1. Multiple straps not fastened on trusses. Check all. 2. A13 member missed. 3. A15 engineering packet sheet does not match truss installed. Please submit a revision to the buuilding department. 4. Please provide a large readable truss layout for inspection. 5. Please provide bearing wall locations and details. 6. Roof sheathing not fastened completely. Check all. 10-21-2022 1. Sheet 6/7 2F indicates on two details 2 x 6 studs. 2 x 4 installed. Please provide engineering or install as per plan. | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 10/17/2022 | Disapproved -FEE REQUIRED | AGAETANO |
| Note: 10-17-2022 1. Multiple straps not fastened on trusses. Check all. 2. A13 member missed. 3. A15 engineering packet sheet does not match truss installed. Please submit a revision to the buuilding department. 4. Please provide a large readable truss layout for inspection. 5. Please provide bearing wall locations and details. 6. Roof sheathing not fastened completely. Check all. | |||
| TIE BEAM / LINTEL | 09/19/2022 | APPROVED | AGAETANO |
| FOUND SURVEY APPROVED (OFFICE) | 09/09/2022 | APPROVED | TBAKER |
| MONOLITHIC SLAB | 07/28/2022 | APPROVED | AGAETANO |
| PLUMBING 1ST ROUGH UNDERGROUND | 07/26/2022 | APPROVED | MGIBSON |
Review History
| Department | Status | Date In | Date Out |
| ENGIN1 | COMPLETE | 09/08/2022 | 09/09/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 09/08/2022 | 09/08/2022 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| CUSVC | HOLD | 06/07/2022 | 06/07/2022 |
| Note: Held By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM MISSING UTILITY APPLICATION | |||
| CUSVC | COMPLETE | 06/07/2022 | 06/09/2022 |
| Note: Released By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM | |||
| ELEC | COMPLETE | 06/07/2022 | 06/07/2022 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 06/07/2022 | 06/08/2022 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM | |||
| CUSVC | HOLD | 06/06/2022 | 06/06/2022 |
| Note: Held By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM NEED A UTILITY APPLICATION | |||
| CUSVC | HOLD | 06/03/2022 | 06/03/2022 |
| Note: Held By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM Need to upload Utility Application | |||
| CUSVC | HOLD | 06/02/2022 | 06/02/2022 |
| Note: Held By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM Need a Utility application filled out. | |||
| BLD | HOLD | 05/31/2022 | 06/02/2022 |
| Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code – Residential REVIEW COMMENTS: 1. Provide Product Approval for the following; Per F.S. 471.025 and F.A.C. 61 G15-23.005. Per F.S. a. Truss Plate b. Garage Door | |||
| CUSVC | HOLD | 05/31/2022 | 06/01/2022 |
| Note: Held By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM No Utility application is filled out. | |||
| ELEC | HOLD | 05/31/2022 | 05/31/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Submit electric load calcs. 2. Outlets in garage, outside, laundry, bathroom, kitchen need to be GFCI protected. NEC 2017 210.8 3. Need outlet by sink in spare bathroom. NEC 2017 210.52 (D) | |||
| ENGIN1 | COMPLETE | 05/31/2022 | 05/31/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| LOCATE | COMPLETE | 05/31/2022 | 06/07/2022 |
| Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 05/31/2022 | 05/31/2022 |
| Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM | |||
| SW1 | COMPLETE | 05/31/2022 | 06/07/2022 |
| Note: Released By: EDWARD MADISON - - EMADISON@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 05/31/2022 | 06/01/2022 |
| Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM | |||
| SWALE | COMPLETE | 05/31/2022 | 08/15/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 04/12/2023 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 04/12/2023 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 04/12/2023 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 04/12/2023 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 04/12/2023 |
| SW ENG REINSPECTION 20 | ¤20.00 | 04/12/2023 |
| SW ENG - REVIEW 20 | ¤20.00 | 06/09/2022 |
| SW ENG RES REVIEW 200 | ¤200.00 | 06/09/2022 |
| 3% TRANS IMPACT FEE CREDIT | (¤52.92) | 06/09/2022 |
| SEWER CREDIT | (¤32.06) | 06/09/2022 |
| SEWER INSPECTION | ¤25.00 | 06/09/2022 |
| SEWER CAPITAL FACILITY | ¤4,939.76 | 06/09/2022 |
| WATER CAPITAL FACILITY FEE | ¤3,626.50 | 06/09/2022 |
| SITE PLAN 30 | ¤30.00 | 06/09/2022 |
| WATER- TURN ON | ¤25.00 | 06/09/2022 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 06/09/2022 |
| INSPECTION - RESIDENTIAL | ¤962.50 | 06/09/2022 |
| PLAN REVIEW - RESIDENTIAL | ¤273.00 | 06/09/2022 |
| CONNECTION FEES | ¤1,077.88 | 06/09/2022 |
| 3% FIRE IMPACT FEE CREDIT | (¤11.66) | 06/09/2022 |
| IMPACT FEE FIRE | ¤388.65 | 06/09/2022 |
| IMPACT FEE PARKS | ¤1,455.13 | 06/09/2022 |
| IMPACT FEE SCHOOL | ¤3,600.00 | 06/09/2022 |
| IMPACT FEE TRANSPORTATION | ¤1,764.00 | 06/09/2022 |
| WATER -IRRIGATION INSPECTION | ¤25.00 | 06/09/2022 |
| 3% PARKS IMPACT FEE CREDIT | (¤43.65) | 06/09/2022 |
| SURCHARGE FS 533.721 | ¤10.49 | 06/09/2022 |
| SURCHARGE - FS 468.631 | ¤15.73 | 06/09/2022 |
| SW ENG - FOUNDATION SURVEY | ¤20.00 | 06/09/2022 |
| SW ENG INSPECTION 80 | ¤80.00 | 06/09/2022 |
| SW ENG PRE APRON | ¤30.00 | 06/09/2022 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤18,678.35 |