Permit #2022060417

Permit Details

Status: COED

Parcel Id: 07-11-31-7007-00520-0040
CONDITIONED SPACE: 2403 sqft
GARAGE: 726 sqft
SCREEN PORCH (SOLID ROOF) : 345 sqft
PATIO/DECK (NO ROOF) : 59 sqft
Total Square Footage: 3533 sqft
Block: 00520
Subdivision: 2185 - SECTION 7-FLORIDA PARK
Job Phone: 386-237-8427
Location Address: 2 FREEMAN LN
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 07/06/2022
NOC: RECORDED
Applicant name: JAY DARREN CURBOW
Owner: DITHOMAS DONNA

Address

4513 6TH LANE SW

VERO BEACH, FL 32968

Lot: 0040
Contracted Stated Job Value: ¤280,780.83
Job Description: Single Family Residence
Type: CN

Contractor

BLUE WATER HOMES INC
Status Location Address State License Number Phone
ACTIVE

4881 PALM COAST PARKWAY NW UNIT 1

PALM COAST, FL 32137

CBC1258679 (Exp: 08/31/2026) 386-445-3405

Sub Contractors

WILLIAM FRANK DUDLEY JR.
Status Location Address State License Number Phone
ACTIVE

P.O. BOX 978

Bunnell, FL 32110

EC0003177 (Exp: 08/31/2026) (386)437-3068
JEFFREY TROY SABAKA
Status Location Address State License Number Phone Fax
ACTIVE

2191 DEERWOOD ACRES DR

ST AUGUSTINE, FL 32084

CFC1427439 (Exp: 08/31/2026) 904-838-2218 904-819-0965
JACK DOUGLAS LANIER
Status Location Address State License Number Phone Fax
ACTIVE

485 COMMERCE WAY

LONGWOOD , FL 32750

CCC058022 (Exp: 08/31/2026) (321)441-2300 (321)441-2313
BRETT CHRISTIAN GIBSON
Status Location Address State License Number Phone
ACTIVE

250 SEGOVIA RD

ST AUGUSTINE, FL 32086

CAC1818423 (Exp: 08/31/2026) 904-229-8131
RICHARD H SIMMONS JR
Status Location Address State License Number Phone Fax
CANCEL

P. O. Box 1963

Bunnell, FL 32110

ER0011613 (Exp: 08/31/2008) (386) 437-0607 (386)437-1847

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 06/09/2023 FINAL APPROVED AGAETANO
Note: 6/8/2023 - PREVIOUS INSPECTION NOTES 6/2/2023 - PREVIOUS INSPECTION NOTES 06-08-2023
U-CROSS CONNECTION 06/09/2023 APPROVED DHANEY
BLD - BUILDING FINAL 06/08/2023 Disapproved - NO FEE AGAETANO
Note: 6/2/2023 - PREVIOUS INSPECTION NOTES 06-08-2023 1. Entry hall lights not working. 2. No switched receptacle in master bed or guest bed. 3. No lanai lights. 4. Disposal not working. 5. Holes in garage walls. Inspection stopped.
BLD - BUILDING FINAL 06/02/2023 CANCELLED BY APPLICANT AGAETANO
U -UTILITY RESIDENTIAL FINAL 05/15/2023 FINAL APPROVED DHANEY
ROW- FINAL SURVEY/GRADING CERTIFICATION 05/12/2023 APPROVED EMADISON
ROW - FINAL APRON (AFTER POUR) 05/12/2023 FINAL APPROVED EMADISON
ROW FIELD SURVEY /GRADING CERTIFICATION 05/12/2023 APPROVED EMADISON
ROW - STORMWATER FINAL 05/12/2023 FINAL APPROVED EMADISON
U - SEWER TIE IN 04/14/2023 APPROVED - AS NOTED MGIBSON
Note: THIS WAS A VIRTUAL INSPECTION
U-CROSS CONNECTION 04/14/2023 CANCELLED BY APPLICANT WEB
ELECTRIC - EARLY POWER 04/12/2023 APPROVED - AS NOTED AGAETANO
Note: 4/11/2023 - PREVIOUS INSPECTION NOTES 4/10/2023 - PREVIOUS INSPECTION NOTES 4/10/2023-R319.1 Address identification. Buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than 4 inches (102 mm) in height with a stroke width of not less than 0.5 inch (12.7 mm)n 04-11-2023 Panel not flush with drywall. Life safety. 04-12-2023 FPL notified at 10:22am
ELECTRIC - EARLY POWER 04/11/2023 Disapproved - NO FEE AGAETANO
Note: 4/10/2023 - PREVIOUS INSPECTION NOTES 4/10/2023-R319.1 Address identification. Buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than 4 inches (102 mm) in height with a stroke width of not less than 0.5 inch (12.7 mm)n 04-11-2023 Panel not flush with drywall. Life safety.
ELECTRIC - EARLY POWER 04/10/2023 Disapproved - NO FEE JSTEWART
Note: 4/10/2023-R319.1 Address identification. Buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than 4 inches (102 mm) in height with a stroke width of not less than 0.5 inch (12.7 mm)n
ROW- PRE-APRON (PRE-POUR) 03/29/2023 APPROVED PFLANAGAN
Note: IT'S THE CONTRACTORS RESPONSIBILITY TO CHECK THE CULVERT PIPE ELEVATIONS BEFORE POURING THE CONCRETE FOR THE DRIVEWAY. ----------------------------------------------------------------------------------------------------- 3/28/2023 - PREVIOUS INSPECTION NOTES 1) CULVERT PIPE IS STILL TO FAR FROM EDGE OF PAVEMENT NEEDS TO BE 8' FROM EDGE OF PAVEMENT TO THE CENTER OF CULVERT. 2) THE FACE BOARD ALONG EDGE OF PAVEMENT HAS BEEN KNOCK DOWN. ------------------------------------------------------------------------------------------- 3/27/2023 - PREVIOUS INSPECTION NOTES THE LEFT SIDE OF CULVERT IS TO FAR OFF OF EDGE OF PAVEMENT. THE CULVERT PIPE NEED TO BE ONLY 8' FROM CENTER OF CULVERT PIPE TO THE EDGE OF PAVEMENT.
ROW- PRE-APRON (PRE-POUR) 03/28/2023 Disapproved -FEE REQUIRED PFLANAGAN
Note: 1) CULVERT PIPE IS STILL TO FAR FROM EDGE OF PAVEMENT NEEDS TO BE 8' FROM EDGE OF PAVEMENT TO THE CENTER OF CULVERT. 2) THE FACE BOARD ALONG EDGE OF PAVEMENT HAS BEEN KNOCK DOWN. ------------------------------------------------------------------------------------------- 3/27/2023 - PREVIOUS INSPECTION NOTES THE LEFT SIDE OF CULVERT IS TO FAR OFF OF EDGE OF PAVEMENT. THE CULVERT PIPE NEED TO BE ONLY 8' FROM CENTER OF CULVERT PIPE TO THE EDGE OF PAVEMENT.
ROW- PRE-APRON (PRE-POUR) 03/27/2023 Disapproved -FEE REQUIRED PFLANAGAN
Note: THE LEFT SIDE OF CULVERT IS TO FAR OFF OF EDGE OF PAVEMENT. THE CULVERT PIPE NEED TO BE ONLY 8' FROM CENTER OF CULVERT PIPE TO THE EDGE OF PAVEMENT.
INSULATION 01/27/2023 APPROVED AGAETANO
LATH/BRICK/ WATER BARRIER 01/25/2023 APPROVED AGAETANO
Note: 1/24/2023 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 2420 Inspector Notes from Inspection 2460 11/7/2022 - PREVIOUS INSPECTION NOTES 10/20/2022 - PREVIOUS INSPECTION NOTES 10-20-2022 1. A1 Utility room, 2 x 6 wall indicates 2 x to be 16 on center. Not 16 on center. 2. A1 Utility and garage bearing walls indicate anchors to be 32" on center. Not 32" on center. 3. A1 Covered porch indicates 2 x 12 flitch. Flitch not installed. Please install or submit a revision to the building department for review. 4. A1 Covered porch, please provide nailing pattern for 2 x 12 header. Back of header side is not nailed completely and gaps in the header. 5. A1 Note 22. Garage entry 2 x 12 header not built as per plans. No flitch. 6. Truss layout does not match engineering packet. 7. Inspection stopped. 11-7-2022 Please provide Approved revised drawings on site for all inspections. 11-22-2022 1. Please have an full, approved, large, readable set of revised drawings on site for inspection. Details are too small to read. 2. A6 Section at headers. Please have a full, approved, large, readable. set of drawings on site for all nspections to avoid any further fees. Please provide nailing pattern for lanai triple header. Check at next nspection. 3. Missing stud in garage bearing wall. 01-09-2023 1. Mid point bracing. PIPING SUPPORT - MID STORY SUPPRORT (BRACING ON A VERTICAL / HORIZONTAL VENT) TABLE P2605.1 PIPING SUPPORT – 2” AND SMALLER REQUIRE MID POINT BRACING. 10b VERTICAL 2. Shield plates not completely covering the garage water lines.NAIL PLATES FOR PLUMBING P2603.2.1 PROTECTION AGAINST PHYSICAL DAMAGE 01-24-2023 ADDRESS MUST BE POSTED AND PLAINLY VISIBLE TO INSPECTORS. IF ADDRESS IS NOT PLAINLY VISIBLE, INSPECTORS WILL NOT PERFORM INSPECTIONS AND A REINSPECTION FEE WILL BE ISSUED. Florida Building Code-Building Section 501.2. R319.1 Residential R319.1 Address identification. Buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than 4 inches (102 mm) in height with a stroke width of not less than 0.5 inch (12.7 mm). Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building address cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. Address identification shall be maintained.
LATH/BRICK/ WATER BARRIER 01/24/2023 Disapproved -FEE REQUIRED AGAETANO
Note: Inspector Notes from Inspection 2420 Inspector Notes from Inspection 2460 11/7/2022 - PREVIOUS INSPECTION NOTES 10/20/2022 - PREVIOUS INSPECTION NOTES 10-20-2022 1. A1 Utility room, 2 x 6 wall indicates 2 x to be 16 on center. Not 16 on center. 2. A1 Utility and garage bearing walls indicate anchors to be 32" on center. Not 32" on center. 3. A1 Covered porch indicates 2 x 12 flitch. Flitch not installed. Please install or submit a revision to the building department for review. 4. A1 Covered porch, please provide nailing pattern for 2 x 12 header. Back of header side is not nailed completely and gaps in the header. 5. A1 Note 22. Garage entry 2 x 12 header not built as per plans. No flitch. 6. Truss layout does not match engineering packet. 7. Inspection stopped. 11-7-2022 Please provide Approved revised drawings on site for all inspections. 11-22-2022 1. Please have an full, approved, large, readable set of revised drawings on site for inspection. Details are too small to read. 2. A6 Section at headers. Please have a full, approved, large, readable. set of drawings on site for all nspections to avoid any further fees. Please provide nailing pattern for lanai triple header. Check at next nspection. 3. Missing stud in garage bearing wall. 01-09-2023 1. Mid point bracing. PIPING SUPPORT - MID STORY SUPPRORT (BRACING ON A VERTICAL / HORIZONTAL VENT) TABLE P2605.1 PIPING SUPPORT – 2” AND SMALLER REQUIRE MID POINT BRACING. 10b VERTICAL 2. Shield plates not completely covering the garage water lines.NAIL PLATES FOR PLUMBING P2603.2.1 PROTECTION AGAINST PHYSICAL DAMAGE 01-24-2023 ADDRESS MUST BE POSTED AND PLAINLY VISIBLE TO INSPECTORS. IF ADDRESS IS NOT PLAINLY VISIBLE, INSPECTORS WILL NOT PERFORM INSPECTIONS AND A REINSPECTION FEE WILL BE ISSUED. Florida Building Code-Building Section 501.2. R319.1 Residential R319.1 Address identification. Buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than 4 inches (102 mm) in height with a stroke width of not less than 0.5 inch (12.7 mm). Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building address cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. Address identification shall be maintained.
ALL ROUGH 01/09/2023 APPROVED - AS NOTED AGAETANO
Note: Inspector Notes from Inspection 2460 11/7/2022 - PREVIOUS INSPECTION NOTES 10/20/2022 - PREVIOUS INSPECTION NOTES 10-20-2022 1. A1 Utility room, 2 x 6 wall indicates 2 x to be 16 on center. Not 16 on center. 2. A1 Utility and garage bearing walls indicate anchors to be 32" on center. Not 32" on center. 3. A1 Covered porch indicates 2 x 12 flitch. Flitch not installed. Please install or submit a revision to the building department for review. 4. A1 Covered porch, please provide nailing pattern for 2 x 12 header. Back of header side is not nailed completely and gaps in the header. 5. A1 Note 22. Garage entry 2 x 12 header not built as per plans. No flitch. 6. Truss layout does not match engineering packet. 7. Inspection stopped. 11-7-2022 Please provide Approved revised drawings on site for all inspections. 11-22-2022 1. Please have an full, approved, large, readable set of revised drawings on site for inspection. Details are too small to read. 2. A6 Section at headers. Please have a full, approved, large, readable. set of drawings on site for all nspections to avoid any further fees. Please provide nailing pattern for lanai triple header. Check at next nspection. 3. Missing stud in garage bearing wall. 01-09-2023 1. Mid point bracing. PIPING SUPPORT - MID STORY SUPPRORT (BRACING ON A VERTICAL / HORIZONTAL VENT) TABLE P2605.1 PIPING SUPPORT – 2” AND SMALLER REQUIRE MID POINT BRACING. 10b VERTICAL 2. Shield plates not completely covering the garage water lines.NAIL PLATES FOR PLUMBING P2603.2.1 PROTECTION AGAINST PHYSICAL DAMAGE
ROOF SHEATHING / BRACES/TIES/DOWN CELL 11/22/2022 APPROVED - AS NOTED AGAETANO
Note: 11/7/2022 - PREVIOUS INSPECTION NOTES 10/20/2022 - PREVIOUS INSPECTION NOTES 10-20-2022 1. A1 Utility room, 2 x 6 wall indicates 2 x to be 16 on center. Not 16 on center. 2. A1 Utility and garage bearing walls indicate anchors to be 32" on center. Not 32" on center. 3. A1 Covered porch indicates 2 x 12 flitch. Flitch not installed. Please install or submit a revision to the building department for review. 4. A1 Covered porch, please provide nailing pattern for 2 x 12 header. Back of header side is not nailed completely and gaps in the header. 5. A1 Note 22. Garage entry 2 x 12 header not built as per plans. No flitch. 6. Truss layout does not match engineering packet. 7. Inspection stopped. 11-7-2022 Please provide Approved revised drawings on site for all inspections. 11-22-2022 1. Please have an full, approved, large, readable set of revised drawings on site for inspection. Details are too small to read. 2. A6 Section at headers. Please have a full, approved, large, readable. set of drawings on site for all nspections to avoid any further fees. Please provide nailing pattern for lanai triple header. Check at next nspection. 3. Missing stud in garage bearing wall.
ROOF SHEATHING 11/07/2022 APPROVED AGAETANO
ROOF VALLEY & METAL 11/07/2022 APPROVED AGAETANO
ROOF SHEATHING / BRACES/TIES/DOWN CELL 11/07/2022 Disapproved -FEE REQUIRED AGAETANO
Note: 10/20/2022 - PREVIOUS INSPECTION NOTES 10-20-2022 1. A1 Utility room, 2 x 6 wall indicates 2 x to be 16 on center. Not 16 on center. 2. A1 Utility and garage bearing walls indicate anchors to be 32" on center. Not 32" on center. 3. A1 Covered porch indicates 2 x 12 flitch. Flitch not installed. Please install or submit a revision to the building department for review. 4. A1 Covered porch, please provide nailing pattern for 2 x 12 header. Back of header side is not nailed completely and gaps in the header. 5. A1 Note 22. Garage entry 2 x 12 header not built as per plans. No flitch. 6. Truss layout does not match engineering packet. 7. Inspection stopped. 11-7-2022 Please provide Approved revised drawings on site for all inspections.
WALL SHEATHING 11/04/2022 APPROVED AGAETANO
ROOF SHEATHING / BRACES/TIES/DOWN CELL 10/20/2022 Disapproved -FEE REQUIRED AGAETANO
Note: 10-20-2022 1. A1 Utility room, 2 x 6 wall indicates 2 x to be 16 on center. Not 16 on center. 2. A1 Utility and garage bearing walls indicate anchors to be 32" on center. Not 32" on center. 3. A1 Covered porch indicates 2 x 12 flitch. Flitch not installed. Please install or submit a revision to the building department for review. 4. A1 Covered porch, please provide nailing pattern for 2 x 12 header. Back of header side is not nailed completely and gaps in the header. 5. A1 Note 22. Garage entry 2 x 12 header not built as per plans. No flitch. 6. Truss layout does not match engineering packet. 7. Inspection stopped.
TIE BEAM / LINTEL 09/12/2022 APPROVED AGAETANO
Note: THIS IS A REINSPECTION 09-09-2022 A6 indicates two rebar at garage door head. Only one installed.
TIE BEAM / LINTEL 09/09/2022 Disapproved - NO FEE AGAETANO
Note: 09-09-2022 A6 indicates two rebar at garage door head. Both garage doors have only one.
FOUND SURVEY APPROVED (OFFICE) 09/07/2022 APPROVED TBAKER
MONOLITHIC SLAB 08/24/2022 APPROVED AGAETANO
PLUMBING 1ST ROUGH UNDERGROUND 08/16/2022 APPROVED MGIBSON
GRAVITY SEWER TEST 08/16/2022 APPROVED MGIBSON
WATER METER INSTALLATION REQUEST 07/15/2022 APPROVED TCHURCHILL

Review History

Department Status Date In Date Out
BLD COMPLETE 11/15/2022 11/15/2022
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
BLD COMPLETE 10/27/2022 10/28/2022
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
ENGIN1 COMPLETE 09/07/2022 09/07/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON COMPLETE 09/07/2022 09/07/2022
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
ELEC COMPLETE 06/21/2022 06/21/2022
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
MECH COMPLETE 06/21/2022 06/21/2022
Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM
ZON COMPLETE 06/21/2022 06/21/2022
Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM
BLD COMPLETE 06/21/2022 06/21/2022
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
PLENV COMPLETE 06/09/2022 06/17/2022
Note: Released By: JORDAN MYERS, C.F.M - (386)986-2320 - JMYERS@PALMCOASTGOV.COM Staff conducted a site visit on 6/17/22 and found no Gopher Tortoise or their burrows. Staff suggests placing silt fence as soon as possible to prevent tortoise from moving into the lot.
BLD HOLD 06/07/2022 06/10/2022
Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code – Residential REVIEW COMMENTS: 1. Provide Product Approval for Wood Connectors and Wood Anchors. Per F.S. 471.025 and F.A.C. 61 G15-23.005.
CUSVC COMPLETE 06/07/2022 06/09/2022
Note: Released By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM
ELEC HOLD 06/07/2022 06/07/2022
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM Electric load calcs do not match the square footage of the home
ENGIN1 COMPLETE 06/07/2022 06/07/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
LOCATE COMPLETE 06/07/2022 06/08/2022
Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM
MECH HOLD 06/07/2022 06/07/2022
Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM Provide return air in Master Bedroom on duct layout
SW1 COMPLETE 06/07/2022 06/14/2022
Note: Released By: PARREN FLANAGAN - (386)986-2392 - PFLANAGAN@PALMCOASTGOV.COM
ZON HOLD 06/07/2022 06/09/2022
Note: Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM Banding around Windows and doors All windows and doors facing public right of way must have banding. Please add banding to the right side of home
SWALE COMPLETE 06/07/2022 08/30/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
PLAN REVIEW - REVISION ¤32.50 05/26/2023
PLAN REVIEW - REVISION ¤32.50 05/26/2023
REINSPECTION RESIDENTIAL ¤40.00 05/26/2023
REINSPECTION RESIDENTIAL ¤40.00 05/26/2023
REINSPECTION RESIDENTIAL ¤40.00 05/26/2023
CONTRACTOR CHANGE ¤40.00 05/26/2023
SW ENG REINSPECTION 30 ¤30.00 05/26/2023
SW ENG REINSPECTION 30 ¤30.00 05/26/2023
SW ENG - REVIEW 20 ¤20.00 07/06/2022
SW ENG RES REVIEW 200 ¤200.00 07/06/2022
3% TRANS IMPACT FEE CREDIT (¤52.92) 07/06/2022
SEWER CREDIT (¤1,342.00) 07/06/2022
SEWER INSPECTION ¤25.00 07/06/2022
SEWER CAPITAL FACILITY ¤4,939.76 07/06/2022
WATER CAPITAL FACILITY FEE ¤3,626.50 07/06/2022
SITE PLAN 30 ¤30.00 07/06/2022
3% FIRE IMPACT FEE CREDIT (¤11.66) 07/06/2022
IMPACT FEE FIRE ¤388.65 07/06/2022
IMPACT FEE PARKS ¤1,455.13 07/06/2022
IMPACT FEE SCHOOL ¤3,600.00 07/06/2022
IMPACT FEE TRANSPORTATION ¤1,764.00 07/06/2022
WATER -IRRIGATION INSPECTION ¤25.00 07/06/2022
3% PARKS IMPACT FEE CREDIT (¤43.65) 07/06/2022
SURCHARGE FS 533.721 ¤9.44 07/06/2022
SURCHARGE - FS 468.631 ¤14.17 07/06/2022
SW ENG - FOUNDATION SURVEY ¤20.00 07/06/2022
SW ENG INSPECTION 80 ¤80.00 07/06/2022
SW ENG PRE APRON ¤30.00 07/06/2022
CONNECTION FEES ¤1,077.88 07/06/2022
WATER- TURN ON ¤25.00 07/06/2022
ADMINISTRATIVE RESIDENTIAL ¤30.00 07/06/2022
INSPECTION - RESIDENTIAL ¤860.75 07/06/2022
PLAN REVIEW - RESIDENTIAL ¤244.14 07/06/2022
Fees Total Due: ¤0.00 Total Paid: ¤17,300.19