I want to search for...
Permit #2022060563
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7014-00020-0120 |
| Block: 00020 |
| Subdivision: 2202 - SECTION 14-COUNTRY CLUB COVE |
| Job Phone: 321-247-6073 |
| Location Address: 9 COTTON CT |
| Type: SLRE - SOLAR ELECTRIC - PHOTOVOLTAIC |
| Issue Date: 06/10/2022 |
| NOC: RECORDED |
| Applicant name: CAMERON CHRISTENSEN |
| Owner: SANDERS FRANK SCOTT & KIMBERLY ANNE H&W |
|
Address 1384 TALL MAPLE LOOP OVIEDO, FL 32765 |
| Lot: 0120 |
| Contracted Stated Job Value: ¤129,729.00 |
| Job Description: SOLAR PANELS ON ROOFTOP |
| Type: CN |
Contractor
MOMENTUM SOLAR,LLC
| Status | Location Address | Mailing Address | State License Number | Phone |
| INACTIVE |
8248 PARKLINE BOULEVARD ORLANDO, FL 32809 |
STE 100 ORLANDO, FL 32809 |
CVC57036 (Exp: 08/31/2026) | 321-247-6073 |
Sub Contractors
MATTHEW FRANZ
| Status | Location Address | Mailing Address | State License Number | Phone |
| INACTIVE |
8248 PARKLINE BOULEVARD ORLANDO, FL 32809 |
STE 100 ORLANDO, FL 32809 |
EC13008217 (Exp: 08/31/2026) | 732-902-6224 |
Inspection History
| Type | Request Date | Result | Inspector |
| SOLAR ELECTRIC FINAL | 07/19/2022 | FINAL APPROVED | JMUNSON |
| Note: THIS IS A REINSPECTION THIS IS A REINSPECTION Need access to service disconnect indoor panel. 07-06-2022 - ELECTRICAL PHOTOVOLTAIC – NEC 2017 – 690.13 PAGE 563 PHOTOVOLAIC SYSTEMS . Disconnect needed between 200AMP electrical panel and the Eaton 200AMP fusible AC disconnect. | |||
| SOLAR ELECTRIC FINAL | 07/06/2022 | Disapproved -FEE REQUIRED | AGAETANO |
| Note: THIS IS A REINSPECTION Need access to service disconnect indoor panel. 07-06-2022 - ELECTRICAL PHOTOVOLTAIC – NEC 2017 – 690.13 PAGE 563 PHOTOVOLAIC SYSTEMS . Disconnect needed between 200AMP electrical panel and the Eaton 200AMP fusible AC disconnect. | |||
| SOLAR ELECTRIC FINAL | 07/01/2022 | Disapproved - NO FEE | AGAETANO |
| Note: Need access to service disconnect indoor panel. |
Review History
| Department | Status | Date In | Date Out |
| BADMIN | INFORMATION | 06/13/2022 | 06/13/2022 |
| Note: Marked INFORMATION By: SCOTT THOMAS - - STHOMAS@PALMCOASTGOV.COM REMOVE 'FRANK SANDERS' FROM FILE NAME. RENAME TO NOC.PDF | |||
| BLD | COMPLETE | 06/09/2022 | 06/09/2022 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 06/09/2022 | 06/09/2022 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 07/11/2022 |
| SURCHARGE FS 533.721 | ¤3.97 | 06/10/2022 |
| SURCHARGE - FS 468.631 | ¤5.96 | 06/10/2022 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 06/10/2022 |
| INSPECTION - RESIDENTIAL | ¤357.50 | 06/10/2022 |
| SOLAR PLAN REVIEW | ¤65.00 | 06/10/2022 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤502.43 |