Permit #2022060806

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7023-00330-0180
CONDITIONED SPACE: 1900 sqft
GARAGE: 471 sqft
OPENED PORCH (WITH ROOF) : 24 sqft
OPENED PORCH (WITH ROOF) : 144 sqft
Total Square Footage: 2539 sqft
Block: 00330
Subdivision: 2191 - SECTION 23-WYNNFIELD
Job Phone: 912-258-2201
Location Address: 27 WHIPPOORWILL DR
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 07/28/2022
NOC: RECORDED
Applicant name: JAMES FUCETOLA III
Owner: PALM COAST COMMUNITIES LLC

Address

PO BOX 22547

ST SIMONS ISLAND, GA 31522

Lot: 0180
Contracted Stated Job Value: ¤170,000.00
Job Description: Single Family Residence
Type: CN

Contractor

PALM COAST COMMUNITIES LLC
Status Location Address State License Number Phone
INACTIVE

PO BOX 22547

PALM COAST, FL 32164

CBC1262878 (Exp: 08/31/2026) 321-501-4617

Sub Contractors

JEFFREY TROY SABAKA
Status Location Address State License Number Phone Fax
ACTIVE

2191 DEERWOOD ACRES DR

ST AUGUSTINE, FL 32084

CFC1427439 (Exp: 08/31/2026) 904-838-2218 904-819-0965
OLEG BELINSKIY
Status Location Address State License Number Phone
ACTIVE

19 PINE CIRCLE DRIVE19

PALM COAST, FL 32167

CCC1325974 (Exp: 08/31/2026) 386-263-7906
GARY LLOYD SHEFFIELD
Status Location Address State License Number Phone
ACTIVE

48 EAGLE LAKES DRIVE

FLAGLER BEACH, FL 32136

CAC048127 (Exp: 08/31/2026) 386-597-3280
WILLIAM FRANK DUDLEY JR.
Status Location Address State License Number Phone
ACTIVE

P.O. BOX 978

Bunnell, FL 32110

EC0003177 (Exp: 08/31/2026) (386)437-3068

Inspection History

Type Request Date Result Inspector
ROW - STORMWATER FINAL 05/15/2023 APPROVED GBERTOLA
Note: 05/15/23=CORRECTION WERE MADE AT THE TIME OF THE INSPECTION EVERYTHING LOOK GOOD
BLD - BUILDING FINAL 05/12/2023 FINAL APPROVED MKRASKI
Note:
BLD - BUILDING FINAL 05/11/2023 Disapproved - NO FEE MKRASKI
Note: 1. AHU plenum going into ceiling must be sealed 2. Insulation coming out of several supply vents
ROW - STORMWATER FINAL 05/11/2023 Disapproved -FEE REQUIRED GBERTOLA
Note: 5/11/23 NEED TO REPAIR THE SWALE ON THE LEFT SIDE FACING THE HOUSE PICTURE ATTACHED 5/9/23=NOTHING HAS BEEN DONE SINCE THE LAST INSPECTION, NEED TO READ THE INPECTOR NOTE ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 5/9/2023 - PREVIOUS INSPECTION NOTES 05/9/23= NOTHING HAS BEEN DONE SINCE THE LAST INSPECTION, NEED TO READ THE INPECTOR NOTE NEED TO CLEAN THE CULVERT PIPES REMOVE ALL THE DIRT . ADD ANOTHER ROW THE SOD AROUND THE PEPE TANK YOU ARE DIRECTING ALL THE STORMWATER INTO THE PEP TANK ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 05/08/23 NEED TO SOD AND MATCH EXISTING GRADE AREA ON THE LEFT SIDE SWALE OUTLINED IN PINK PAINT. NEED TO ADD A ROW OR POSSIBLY TWO OF SOD IN THE REAR AT PROPERTY LINE WHERE BARE AREAS ARE ON SLOPE AND AT AJOINING PROPERTY MARKED IN PINK PAINT BEFORE FINAL ROW APPROVAL.
ROW - STORMWATER FINAL 05/09/2023 Disapproved -FEE REQUIRED GBERTOLA
Note: 05/9/23= NOTHING HAS BEEN DONE SINCE THE LAST INSPECTION, NEED TO READ THE INPECTOR NOTE NEED TO CLEAN THE CULVERT PIPES REMOVE ALL THE DIRT . ADD ANOTHER ROW THE SOD AROUND THE PEPE TANK YOU ARE DIRECTING ALL THE STORMWATER INTO THE PEP TANK ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 05/08/23 NEED TO SOD AND MATCH EXISTING GRADE AREA ON THE LEFT SIDE SWALE OUTLINED IN PINK PAINT. NEED TO ADD A ROW OR POSSIBLY TWO OF SOD IN THE REAR AT PROPERTY LINE WHERE BARE AREAS ARE ON SLOPE AND AT AJOINING PROPERTY MARKED IN PINK PAINT BEFORE FINAL ROW APPROVAL.
U -UTILITY RESIDENTIAL FINAL 05/09/2023 FINAL APPROVED LFITZGERALD
ROW - FINAL APRON (AFTER POUR) 05/08/2023 APPROVED FSLADISH
Note: 05/08/23 PIPE IS GOOD. LOOKED GOOD AT TIME OF INSPECTION. Inspector Notes from Inspection 9465 05/08/23 NEED TO SOD AND MATCH EXISTING GRADE AREA ON THE LEFT SIDE SWALE OUTLINED IN PINK PAINT. NEED TO ADD A ROW OR POSSIBLY TWO OF SOD IN THE REAR AT PROPERTY LINE WHERE BARE AREAS ARE ON SLOPE AND AT AJOINING PROPERTY MARKED IN PINK PAINT BEFORE FINAL ROW APPROVAL.
ROW FIELD SURVEY /GRADING CERTIFICATION 05/08/2023 APPROVED - AS NOTED FSLADISH
Note: 05/08/23 NEED TO SOD AND MATCH EXISTING GRADE AREA ON THE LEFT SIDE SWALE OUTLINED IN PINK PAINT. NEED TO ADD A ROW OR POSSIBLY TWO OF SOD IN THE REAR AT PROPERTY LINE WHERE BARE AREAS ARE ON SLOPE AND AT AJOINING PROPERTY MARKED IN PINK PAINT BEFORE FINAL ROW APPROVAL.
FINAL SURVEY (OFFICE USE ONLY) 05/08/2023 APPROVED FSLADISH
U-CROSS CONNECTION 05/02/2023 APPROVED - AS NOTED LFITZGERALD
Note: has potable irrigation with dbl check installed-no cross connection
ELECTRIC - EARLY POWER 03/27/2023 APPROVED - AS NOTED MKRASKI
Note: Emailed FPL @ 3:45 PM
ELECTRIC - EARLY POWER 03/23/2023 Disapproved - NO FEE MKRASKI
Note: 1. Over head service wires, Just red and white, do not appear and are not marked that they are sun light resistant NEC 310.10(d)
ROW- PRE-APRON (PRE-POUR) 03/09/2023 APPROVED GBERTOLA
Note: AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS BEFORE POURING. MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL
U - SEWER TIE IN 02/27/2023 APPROVED - AS NOTED MGIBSON
Note: THIS WAS A VIRTUAL INSPECTION
PEP TANK INSTALLATION REQUEST 01/12/2023 APPROVED CSTONE
INSULATION 01/03/2023 APPROVED - AS NOTED LMILLER
Note: Inspector Notes from Inspection 2420 12/22/22: Check at insulation inspection. 1). Back sliding door - window/door tape is falling off at header. 2). 2nd left bedroom has a broken upper window sash. 3). dryer gooseneck not installed. (roof is shingled). 12/21/2022 - PREVIOUS INSPECTION NOTES 1-3-23 notes 1 and 3 above resolved note 2 is not resolved (broken upper window at 2nd bedroom upper sash, need to resolve by final and (need to weatherproof opening now to prevent water damage)
LATH/BRICK/ WATER BARRIER 01/03/2023 APPROVED - AS NOTED LMILLER
Note: Inspector Notes from Inspection 2420 12/22/22: Check at insulation inspection. 1). Back sliding door - window/door tape is falling off at header. 2). 2nd left bedroom has a broken upper window sash. 3). dryer gooseneck not installed. (roof is shingled). 12/21/2022 - PREVIOUS INSPECTION NOTES 1-3-23 notes 1 and 3 above resolved note 2 is not resolved (broken upper window at 2nd bedroom upper sash, need to resolve by final and (need to weatherproof opening now to prevent water damage)
ALL ROUGH 12/22/2022 APPROVED - AS NOTED RSIMS
Note: 12/22/22: Check at insulation inspection. 1). Back sliding door - window/door tape is falling off at header. 2). 2nd left bedroom has a broken upper window sash. 3). dryer gooseneck not installed. (roof is shingled). 12/21/2022 - PREVIOUS INSPECTION NOTES
ALL ROUGH 12/21/2022 CANCELLED BY APPLICANT MKRASKI
ROOF SHEATHING / BRACES/TIES/DOWN CELL 11/17/2022 APPROVED MKRASKI
ROOF SHEATHING / BRACES/TIES/DOWN CELL 11/03/2022 Disapproved - NO FEE MKRASKI
Note: 1. Srtraps missing on truss's HJ01 (2) , HJ03 (2) marked on plans 2. Missing straps on hand framed rafter on lani marked on plans 3. Gable end truss's not strapped 4. Bracing for gable end not per plans
ROOF VALLEY & METAL 10/24/2022 APPROVED KSANDOE
ROOF SHEATHING 10/19/2022 APPROVED MKRASKI
WALL SHEATHING 10/19/2022 APPROVED MKRASKI
FOUND SURVEY APPROVED (OFFICE) 10/18/2022 APPROVED TBAKER
TIE BEAM / LINTEL 10/04/2022 APPROVED MKRASKI
MONOLITHIC SLAB 09/15/2022 APPROVED MKRASKI
MONOLITHIC SLAB 09/14/2022 CANCELLED BY APPLICANT MKRASKI
Note: THIS IS A REINSPECTION Not ready
MONOLITHIC SLAB 09/13/2022 Disapproved - NO FEE MKRASKI
Note: Not ready
PLUMBING 1ST ROUGH UNDERGROUND 09/12/2022 APPROVED MGIBSON
GRAVITY SEWER TEST 09/12/2022 APPROVED MGIBSON
WATER METER INSTALLATION REQUEST 09/01/2022 APPROVED CSTONE
WATER METER INSTALLATION REQUEST 08/17/2022 APPROVED CSTONE

Review History

Department Status Date In Date Out
BADMIN INFORMATION 03/22/2023 03/22/2023
Note: Marked INFORMATION By: MICHELLE RAMOS - - MRAMOS@PALMCOASTGOV.COM NOC expired.
ENGIN1 COMPLETE 10/18/2022 10/18/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON COMPLETE 10/18/2022 10/18/2022
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
SW1 COMPLETE 06/29/2022 07/07/2022
Note: Released By: ROBERT GROSS - (386)986-4769 - RGROSS@PALMCOASTGOV.COM
BLD COMPLETE 06/14/2022 06/17/2022
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
CUSVC COMPLETE 06/14/2022 06/16/2022
Note: Released By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM
ELEC COMPLETE 06/14/2022 06/15/2022
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ENGIN1 COMPLETE 06/14/2022 06/14/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
LOCATE COMPLETE 06/14/2022 06/21/2022
Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM
MECH COMPLETE 06/14/2022 06/14/2022
Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM
SW1 HOLD 06/14/2022 06/21/2022
Note: Held By: PARREN FLANAGAN - (386)986-2392 - PFLANAGAN@PALMCOASTGOV.COM NEED TO MAKE THE LEFT SIDE SWALE ALONG PROPERTY LINE A COMMON SWALE DO TO THE VACANT
ZON COMPLETE 06/14/2022 06/15/2022
Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM
SWALE COMPLETE 06/14/2022 09/13/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
WATER- TURN ON ¤25.00 07/28/2022
ADMINISTRATIVE RESIDENTIAL ¤30.00 07/28/2022
INSPECTION - RESIDENTIAL ¤651.75 07/28/2022
PLAN REVIEW - RESIDENTIAL ¤184.86 07/28/2022
CONNECTION FEES ¤1,077.88 07/28/2022
3% FIRE IMPACT FEE CREDIT (¤11.66) 07/28/2022
IMPACT FEE FIRE ¤388.65 07/28/2022
IMPACT FEE PARKS ¤1,455.13 07/28/2022
IMPACT FEE SCHOOL ¤3,600.00 07/28/2022
IMPACT FEE TRANSPORTATION ¤1,764.00 07/28/2022
WATER -IRRIGATION INSPECTION ¤25.00 07/28/2022
3% PARKS IMPACT FEE CREDIT (¤43.65) 07/28/2022
SURCHARGE FS 533.721 ¤7.30 07/28/2022
SURCHARGE - FS 468.631 ¤10.95 07/28/2022
SW ENG - FOUNDATION SURVEY ¤20.00 07/28/2022
SW ENG INSPECTION 80 ¤80.00 07/28/2022
SW ENG PRE APRON ¤30.00 07/28/2022
SW ENG - REVIEW 20 ¤20.00 07/28/2022
SW ENG RES REVIEW 200 ¤200.00 07/28/2022
3% TRANS IMPACT FEE CREDIT (¤52.92) 07/28/2022
SEWER CREDIT (¤1,146.97) 07/28/2022
SEWER INSPECTION ¤25.00 07/28/2022
SEWER CAPITAL FACILITY ¤4,939.76 07/28/2022
WATER CAPITAL FACILITY FEE ¤3,626.50 07/28/2022
SITE PLAN 30 ¤30.00 07/28/2022
SW ENG REINSPECTION 20 ¤20.00
Fees Total Due: ¤20.00 Total Paid: ¤16,936.58