Permit #2022070151
Permit Details
Status: COED
| Parcel Id: 07-11-31-7028-00320-0480 |
| GARAGE: 396 sqft |
| CONDITIONED SPACE: 1215 sqft |
| Total Square Footage: 1611 sqft |
| Block: 00320 |
| Subdivision: 2199 - SECTION 28-WYNNFIELD |
| Job Phone: 470-817-1259 |
| Location Address: 11 POSTMAN LN |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 08/25/2022 |
| NOC: RECORDED |
| Applicant name: WADE GILMER JURNEY JR |
| Owner: NATIONAL HOME CORPORATION |
|
Address 4850 TAMIAMI TRAIL NORTH NAPLES, FL 34103 |
| Lot: 0480 |
| Contracted Stated Job Value: ¤198,291.00 |
| Job Description: Single Family Residence |
| Type: CN |
Contractor
NATIONAL HOME CORPORATION
| Status | Location Address | Mailing Address | State License Number | Phone |
| INACTIVE |
1080 HOLCOMB BRIDGE ROAD , |
BLDG 100 - 330 ROSWELL , GA 30076 |
CBC1257700 (Exp: 08/31/2026) | 471-817-1259 |
Sub Contractors
JASON PATRICK RIBOCK
| Status | Location Address | State License Number | Phone |
| INACTIVE |
620 E PINE ST , 0 |
ES12001313 (Exp: 08/31/2026) | 407-625-0257 |
DUSTIN L ESTEP
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
2041 N HIAWASSEE RD APOPKA, FL 32703 |
CCC1330971 (Exp: 08/31/2026) | 407-702-0206 | 352-988-6629 |
RUSSELL J CARTER
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
PO BOX 302 DELAND, FL 32721 |
CFC1425938 (Exp: 08/31/2026) | 386-736-4220 | 386-736-4219 |
RANDALL SCOTT ROSENFELD
| Status | Location Address | State License Number | Phone |
| ACTIVE |
234 N WHITNEY ST PALM COAST, FL 32084 |
CAC1816641 (Exp: 08/31/2026) | 904-599-0082 |
Inspection History
| Type | Request Date | Result | Inspector |
| BLD - BUILDING FINAL | 09/13/2023 | FINAL APPROVED | KSANDOE |
| Note: 9/12/2023 - PREVIOUS INSPECTION NOTES PEP breakers in external panel off. When energized, alarm sounds. 9/8/2023 - PREVIOUS INSPECTION NOTES 9/8/23- Please repair weatherstripping at front door causing standing water at front entry interior. Please seal both tubs at floor line. Please seal power wall penetrations at AHU, and water heater. Please submit specifications on power mast flashiing boot that meets Florida product aproval code. | |||
| BLD - BUILDING FINAL | 09/12/2023 | Disapproved - NO FEE | KSANDOE |
| Note: PEP breakers in external panel off. When energized, alarm sounds. 9/8/2023 - PREVIOUS INSPECTION NOTES 9/8/23- Please repair weatherstripping at front door causing standing water at front entry interior. Please seal both tubs at floor line. Please seal power wall penetrations at AHU, and water heater. Please submit specifications on power mast flashiing boot that meets Florida product aproval code. | |||
| U -UTILITY RESIDENTIAL FINAL | 09/12/2023 | FINAL APPROVED | DHANEY |
| Note: per Larry -approved as noted to avoid builder having to lose loan for client-still need pep bore/tap and pumps-Ivan aware and will inform when all is completed so i can do final check-noone is going to occupy residence for a while 9/5/2023 - PREVIOUS INSPECTION NOTES provide pep tank circuit breaker/no pumps in pep tank-utility informed | |||
| BLD - BUILDING FINAL | 09/08/2023 | Disapproved - NO FEE | JSTEWART |
| Note: 9/8/23- Please repair weatherstripping at front door causing standing water at front entry interior. Please seal both tubs at floor line. Please seal power wall penetrations at AHU, and water heater. Please submit specifications on power mast flashiing boot that meets Florida product aproval code. | |||
| ROW - FINAL APRON (AFTER POUR) | 09/06/2023 | APPROVED | FSLADISH |
| Note: 09/06/23 PIPE IS GOOD. CUTS MADE. HOT PATCH COMPLETE. CULVERT CLEAR. At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. _______________________________________________________________________________________________________________________ 9/5/2023 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9465 09/01/23 APPROVING THIS FIELD SURVEY AS NOTED. THE PROPERTY INCLUDING THE SWALE NEEDS TO BE MOWED BEFORE ROW PASSAGE. IT IS HARD TO DETERMINE IF DRAINAGE WILL WORK. This is how the code defines it…..Excessive growth of grass, weeds, or brush and other overgrowth means grass or weeds or brush, or bushes, or shrubs, or trees, or vines, or flowering plants and other living plant life that is allowed to grow in a wild and unkempt manner not in keeping with the neighborhood. 15-108 (d) is the code ______________________________________________________________________________________________________________________ 8/24/2023 - PREVIOUS INSPECTION NOTES 8/24/23 NEED TO READ PREVIOUS INSPECTORS NOTES. NO CORRECTIONS MADE ON THR RIGHT SIDE SWALE. 08/22/23= The high spot (hump) on the right- side swale causes stormwater to back up. The swale on the right side should be lowered to match the existing grade.Water flow from the left to the right side. NEEDS TO BE MOWED ONCE CORRECTED ALSO TO HELP DETERMINE IF GRADE IS MATCHED AND POSITIVE DRAINAGE FLOW ATTAINED. This is how the code defines it…..Excessive growth of grass, weeds, or brush and other overgrowth means grass or weeds or brush, or bushes, or shrubs, or trees, or vines, or flowering plants and other living plant life that is allowed to grow in a wild and unkempt manner not in keeping with the neighborhood. 15-108 (d) is the code ------------------------------------------------------------------------------------------------------------------------------- 8/22/2023 - PREVIOUS INSPECTION NOTES 08/22/23= The high spot (hump) on the right- side swale causes stormwater to back up. The swale on the right side should be lowered to match the existing grade.Water flow from the left to the right side. | |||
| ROW - STORMWATER FINAL | 09/06/2023 | APPROVED | FSLADISH |
| Note: 09/06/23 At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. _______________________________________________________________________________________________________________________ 9/5/2023 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9465 09/01/23 APPROVING THIS FIELD SURVEY AS NOTED. THE PROPERTY INCLUDING THE SWALE NEEDS TO BE MOWED BEFORE ROW PASSAGE. IT IS HARD TO DETERMINE IF DRAINAGE WILL WORK. This is how the code defines it…..Excessive growth of grass, weeds, or brush and other overgrowth means grass or weeds or brush, or bushes, or shrubs, or trees, or vines, or flowering plants and other living plant life that is allowed to grow in a wild and unkempt manner not in keeping with the neighborhood. 15-108 (d) is the code ______________________________________________________________________________________________________________________ 8/24/2023 - PREVIOUS INSPECTION NOTES 8/24/23 NEED TO READ PREVIOUS INSPECTORS NOTES. NO CORRECTIONS MADE ON THR RIGHT SIDE SWALE. 08/22/23= The high spot (hump) on the right- side swale causes stormwater to back up. The swale on the right side should be lowered to match the existing grade.Water flow from the left to the right side. NEEDS TO BE MOWED ONCE CORRECTED ALSO TO HELP DETERMINE IF GRADE IS MATCHED AND POSITIVE DRAINAGE FLOW ATTAINED. This is how the code defines it…..Excessive growth of grass, weeds, or brush and other overgrowth means grass or weeds or brush, or bushes, or shrubs, or trees, or vines, or flowering plants and other living plant life that is allowed to grow in a wild and unkempt manner not in keeping with the neighborhood. 15-108 (d) is the code ------------------------------------------------------------------------------------------------------------------------------- 8/22/2023 - PREVIOUS INSPECTION NOTES 08/22/23= The high spot (hump) on the right- side swale causes stormwater to back up. The swale on the right side should be lowered to match the existing grade.Water flow from the left to the right side. | |||
| U -UTILITY RESIDENTIAL FINAL | 09/05/2023 | Disapproved -FEE REQUIRED | LFITZGERALD |
| Note: provide pep tank circuit breaker/no pumps in pep tank-utility informed | |||
| ROW - STORMWATER FINAL | 09/05/2023 | CANCELLED BY APPLICANT | FSLADISH |
| Note: Inspector Notes from Inspection 9465 09/01/23 APPROVING THIS FIELD SURVEY AS NOTED. THE PROPERTY INCLUDING THE SWALE NEEDS TO BE MOWED BEFORE ROW PASSAGE. IT IS HARD TO DETERMINE IF DRAINAGE WILL WORK. This is how the code defines it…..Excessive growth of grass, weeds, or brush and other overgrowth means grass or weeds or brush, or bushes, or shrubs, or trees, or vines, or flowering plants and other living plant life that is allowed to grow in a wild and unkempt manner not in keeping with the neighborhood. 15-108 (d) is the code ______________________________________________________________________________________________________________________ 8/24/2023 - PREVIOUS INSPECTION NOTES 8/24/23 NEED TO READ PREVIOUS INSPECTORS NOTES. NO CORRECTIONS MADE ON THR RIGHT SIDE SWALE. 08/22/23= The high spot (hump) on the right- side swale causes stormwater to back up. The swale on the right side should be lowered to match the existing grade.Water flow from the left to the right side. NEEDS TO BE MOWED ONCE CORRECTED ALSO TO HELP DETERMINE IF GRADE IS MATCHED AND POSITIVE DRAINAGE FLOW ATTAINED. This is how the code defines it…..Excessive growth of grass, weeds, or brush and other overgrowth means grass or weeds or brush, or bushes, or shrubs, or trees, or vines, or flowering plants and other living plant life that is allowed to grow in a wild and unkempt manner not in keeping with the neighborhood. 15-108 (d) is the code ------------------------------------------------------------------------------------------------------------------------------- 8/22/2023 - PREVIOUS INSPECTION NOTES 08/22/23= The high spot (hump) on the right- side swale causes stormwater to back up. The swale on the right side should be lowered to match the existing grade.Water flow from the left to the right side. | |||
| ROW - FINAL APRON (AFTER POUR) | 09/05/2023 | CANCELLED BY APPLICANT | FSLADISH |
| Note: Inspector Notes from Inspection 9465 09/01/23 APPROVING THIS FIELD SURVEY AS NOTED. THE PROPERTY INCLUDING THE SWALE NEEDS TO BE MOWED BEFORE ROW PASSAGE. IT IS HARD TO DETERMINE IF DRAINAGE WILL WORK. This is how the code defines it…..Excessive growth of grass, weeds, or brush and other overgrowth means grass or weeds or brush, or bushes, or shrubs, or trees, or vines, or flowering plants and other living plant life that is allowed to grow in a wild and unkempt manner not in keeping with the neighborhood. 15-108 (d) is the code ______________________________________________________________________________________________________________________ 8/24/2023 - PREVIOUS INSPECTION NOTES 8/24/23 NEED TO READ PREVIOUS INSPECTORS NOTES. NO CORRECTIONS MADE ON THR RIGHT SIDE SWALE. 08/22/23= The high spot (hump) on the right- side swale causes stormwater to back up. The swale on the right side should be lowered to match the existing grade.Water flow from the left to the right side. NEEDS TO BE MOWED ONCE CORRECTED ALSO TO HELP DETERMINE IF GRADE IS MATCHED AND POSITIVE DRAINAGE FLOW ATTAINED. This is how the code defines it…..Excessive growth of grass, weeds, or brush and other overgrowth means grass or weeds or brush, or bushes, or shrubs, or trees, or vines, or flowering plants and other living plant life that is allowed to grow in a wild and unkempt manner not in keeping with the neighborhood. 15-108 (d) is the code ------------------------------------------------------------------------------------------------------------------------------- 8/22/2023 - PREVIOUS INSPECTION NOTES 08/22/23= The high spot (hump) on the right- side swale causes stormwater to back up. The swale on the right side should be lowered to match the existing grade.Water flow from the left to the right side. | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 09/01/2023 | APPROVED - AS NOTED | FSLADISH |
| Note: 09/01/23 APPROVING THIS FIELD SURVEY AS NOTED. THE PROPERTY INCLUDING THE SWALE NEEDS TO BE MOWED BEFORE ROW PASSAGE. IT IS HARD TO DETERMINE IF DRAINAGE WILL WORK. This is how the code defines it…..Excessive growth of grass, weeds, or brush and other overgrowth means grass or weeds or brush, or bushes, or shrubs, or trees, or vines, or flowering plants and other living plant life that is allowed to grow in a wild and unkempt manner not in keeping with the neighborhood. 15-108 (d) is the code ______________________________________________________________________________________________________________________ 8/24/2023 - PREVIOUS INSPECTION NOTES 8/24/23 NEED TO READ PREVIOUS INSPECTORS NOTES. NO CORRECTIONS MADE ON THR RIGHT SIDE SWALE. 08/22/23= The high spot (hump) on the right- side swale causes stormwater to back up. The swale on the right side should be lowered to match the existing grade.Water flow from the left to the right side. NEEDS TO BE MOWED ONCE CORRECTED ALSO TO HELP DETERMINE IF GRADE IS MATCHED AND POSITIVE DRAINAGE FLOW ATTAINED. This is how the code defines it…..Excessive growth of grass, weeds, or brush and other overgrowth means grass or weeds or brush, or bushes, or shrubs, or trees, or vines, or flowering plants and other living plant life that is allowed to grow in a wild and unkempt manner not in keeping with the neighborhood. 15-108 (d) is the code ------------------------------------------------------------------------------------------------------------------------------- 8/22/2023 - PREVIOUS INSPECTION NOTES 08/22/23= The high spot (hump) on the right- side swale causes stormwater to back up. The swale on the right side should be lowered to match the existing grade.Water flow from the left to the right side. | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 08/24/2023 | Disapproved -FEE REQUIRED | FSLADISH |
| Note: 8/24/23 NEED TO READ PREVIOUS INSPECTORS NOTES. NO CORRECTIONS MADE ON THR RIGHT SIDE SWALE. 08/22/23= The high spot (hump) on the right- side swale causes stormwater to back up. The swale on the right side should be lowered to match the existing grade.Water flow from the left to the right side. NEEDS TO BE MOWED ONCE CORRECTED ALSO TO HELP DETERMINE IF GRADE IS MATCHED AND POSITIVE DRAINAGE FLOW ATTAINED. This is how the code defines it…..Excessive growth of grass, weeds, or brush and other overgrowth means grass or weeds or brush, or bushes, or shrubs, or trees, or vines, or flowering plants and other living plant life that is allowed to grow in a wild and unkempt manner not in keeping with the neighborhood. 15-108 (d) is the code ------------------------------------------------------------------------------------------------------------------------------- 8/22/2023 - PREVIOUS INSPECTION NOTES 08/22/23= The high spot (hump) on the right- side swale causes stormwater to back up. The swale on the right side should be lowered to match the existing grade.Water flow from the left to the right side. | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 08/22/2023 | APPROVED | GBERTOLA |
| Note: 08/22/23= At the time of the inspection, all minimum city requirements were met. It is the builder's responsibility to ensure that nothing changes after this Inspection is approved. | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 08/22/2023 | Disapproved - NO FEE | GBERTOLA |
| Note: 08/22/23= The high spot (hump) on the right- side swale causes stormwater to back up. The swale on the right side should be lowered to match the existing grade.Water flow from the left to the right side. | |||
| U-CROSS CONNECTION | 08/21/2023 | APPROVED - AS NOTED | LFITZGERALD |
| Note: no irrigation-no cross connection | |||
| GRAVITY SEWER TEST | 06/26/2023 | APPROVED | MGIBSON |
| Note: 12/20/2022 - PREVIOUS INSPECTION NOTES SEWER NOT RAN YET | |||
| U - SEWER TIE IN | 06/23/2023 | APPROVED - AS NOTED | MGIBSON |
| Note: C/M TO SHEDULE GRAVITY SEWER INSPECTION FOR6/26/23 | |||
| ROW- PRE-APRON (PRE-POUR) | 06/01/2023 | APPROVED | GBERTOLA |
| Note: 6/1/23= AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS BEFORE POURING. MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL +++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 5/22/2023 - PREVIOUS INSPECTION NOTES 05/22/23 SEE PREVIOUS NOTES. NEED TO REMOVE ASPHALT/CONCRETE CHUNKS FROM APRON POUR AREA. NEED TO REDIG CULVERT FOOTERS TO 6" X 6", THEY HAVE WASHED IN. PIPE IS GOOD AT TIME OF INSPECTION. ________________________________________________________________________________________________________________________ 5/16/2023 - PREVIOUS INSPECTION NOTES 1) THE FOOTER ON LEFT SIDE AT END OF CULVERT NEEDS TO BE 6"X6" 2) THERE IS TO MUCH CHIPS OF ASPHALT IN POURING AREA 3) NEED TO HAVE DIRT ON OUT SIDE OF THE FORMS SO CONCRETE STAYS IN POURING AREA | |||
| ROW- PRE-APRON (PRE-POUR) | 05/22/2023 | Disapproved -FEE REQUIRED | FSLADISH |
| Note: 05/22/23 SEE PREVIOUS NOTES. NEED TO REMOVE ASPHALT/CONCRETE CHUNKS FROM APRON POUR AREA. NEED TO REDIG CULVERT FOOTERS TO 6" X 6", THEY HAVE WASHED IN. PIPE IS GOOD AT TIME OF INSPECTION. ________________________________________________________________________________________________________________________ 5/16/2023 - PREVIOUS INSPECTION NOTES 1) THE FOOTER ON LEFT SIDE AT END OF CULVERT NEEDS TO BE 6"X6" 2) THERE IS TO MUCH CHIPS OF ASPHALT IN POURING AREA 3) NEED TO HAVE DIRT ON OUT SIDE OF THE FORMS SO CONCRETE STAYS IN POURING AREA | |||
| ELECTRIC - EARLY POWER | 05/18/2023 | APPROVED - AS NOTED | KSANDOE |
| Note: Emailed FPL @ 1134. Release Power 5/12/2023 - PREVIOUS INSPECTION NOTES Overhead service wire needs to be sunlight resistant | |||
| ROW- PRE-APRON (PRE-POUR) | 05/16/2023 | Disapproved -FEE REQUIRED | PFLANAGAN |
| Note: 1) THE FOOTER ON LEFT SIDE AT END OF CULVERT NEEDS TO BE 6"X6" 2) THERE IS TO MUCH CHIPS OF ASPHALT IN POURING AREA 3) NEED TO HAVE DIRT ON OUT SIDE OF THE FORMS SO CONCRETE STAYS IN POURING AREA | |||
| ELECTRIC - EARLY POWER | 05/12/2023 | Disapproved -FEE REQUIRED | KSANDOE |
| Note: Inspector Notes from Inspection 2190 Emailed FPL @ 1134. Release Power 5/12/2023 - PREVIOUS INSPECTION NOTES Overhead service wire needs to be sunlight resistant | |||
| ELECTRIC TEMP POLE | 04/28/2023 | CANCELLED BY APPLICANT | KSANDOE |
| INSULATION | 03/06/2023 | APPROVED | TSCHWEERS |
| Note: 3/2/2023 - PREVIOUS INSPECTION NOTES DRYER DUCT NAIL PLATE M1502.5 FOR PROTECTION OF EXHAUST VENTS SHALL EXTEND 2 inches ABOVE SOLE PLATES AND BELOW TOP PLATES | |||
| INSULATION | 03/02/2023 | Disapproved - NO FEE | KSANDOE |
| Note: DRYER DUCT NAIL PLATE M1502.5 FOR PROTECTION OF EXHAUST VENTS SHALL EXTEND 2 inches ABOVE SOLE PLATES AND BELOW TOP PLATES | |||
| PEP TANK INSTALLATION REQUEST | 03/02/2023 | APPROVED | CBOWERMASTER |
| LATH/BRICK/ WATER BARRIER | 02/16/2023 | APPROVED | KSANDOE |
| Note: Inspector Notes from Inspection 2420 Dryer vent needs nail plate at top plate | |||
| ALL ROUGH | 02/15/2023 | APPROVED - AS NOTED | KSANDOE |
| Note: Dryer vent needs nail plate at top plate | |||
| ROOF VALLEY & METAL | 01/25/2023 | APPROVED | KSANDOE |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 01/20/2023 | APPROVED | KSANDOE |
| Note: 1/12/2023 - PREVIOUS INSPECTION NOTES 1. Roof sheating has not been nailed as per details on page S 4.0 edges are to be nailed 4" o.c. field nailing is to be 6" o.c. Multiple missed rows and nails sunk too deep. Nail properly and leave roof uncoved for reinspection. 2. Missing hold down heta 16's at truss EJ11, T1, T9 and T-6 3. Blocking used for roof bracing is to be SYP. Detail Page D-2. remove NSPR. 4. Roof engineering packet was not onsite unable to check truss engineering. 5. Install missing bottom chord lateral bracing on trusses 10' o.c. max spacing missing near the walls on both sides of the building. Detail page. D2 TBO5. Inspection stopped. | |||
| WALL SHEATHING | 01/12/2023 | APPROVED | JWALKER |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 01/12/2023 | Disapproved -FEE REQUIRED | JWALKER |
| Note: 1. Roof sheating has not been nailed as per details on page S 4.0 edges are to be nailed 4" o.c. field nailing is to be 6" o.c. Multiple missed rows and nails sunk too deep. Nail properly and leave roof uncoved for reinspection. 2. Missing hold down heta 16's at truss EJ11, T1, T9 and T-6 3. Blocking used for roof bracing is to be SYP. Detail Page D-2. remove NSPR. 4. Roof engineering packet was not onsite unable to check truss engineering. 5. Install missing bottom chord lateral bracing on trusses 10' o.c. max spacing missing near the walls on both sides of the building. Detail page. D2 TBO5. Inspection stopped. | |||
| TIE BEAM / LINTEL | 01/05/2023 | APPROVED | KSANDOE |
| FOUND SURVEY APPROVED (OFFICE) | 12/29/2022 | APPROVED | TBAKER |
| MONOLITHIC SLAB | 12/28/2022 | APPROVED | KSANDOE |
| Note: 12/27/2022 - PREVIOUS INSPECTION NOTES Minimum slab depth not met throughout | |||
| MONOLITHIC SLAB | 12/27/2022 | Disapproved - NO FEE | KSANDOE |
| Note: Minimum slab depth not met throughout | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 12/20/2022 | APPROVED | MGIBSON |
| GRAVITY SEWER TEST | 12/20/2022 | Disapproved - NO FEE | MGIBSON |
| Note: SEWER NOT RAN YET | |||
| WATER METER INSTALLATION REQUEST | 11/21/2022 | APPROVED | CSTONE |
Review History
| Department | Status | Date In | Date Out |
| BADMIN | INFORMATION | 08/18/2023 | 08/18/2023 |
| Note: Marked INFORMATION By: LIBBY MUSGROVE - - LMUSGROVE@PALMCOASTGOV.COM cannot result the final survey until the lower open inspection is resulted | |||
| BADMIN | INFORMATION | 08/18/2023 | 08/18/2023 |
| Note: Marked INFORMATION By: LIBBY MUSGROVE - - LMUSGROVE@PALMCOASTGOV.COM cannot result the final survey until the lower open inspection is resulted - pep install. | |||
| BADMIN | INFORMATION | 06/16/2023 | 06/16/2023 |
| Note: Marked INFORMATION By: SCOTT THOMAS - - STHOMAS@PALMCOASTGOV.COM NOC MISSING NOTARY AT BOTTOM | |||
| MECH | COMPLETE | 02/08/2023 | 02/08/2023 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM | |||
| MECH | HOLD | 02/02/2023 | 02/03/2023 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Duct layout needs to be signed by the AC contractor per 107.1 FBC Residential 2020 7th Edition | |||
| ENGIN1 | COMPLETE | 12/28/2022 | 12/29/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 12/28/2022 | 12/28/2022 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 07/13/2022 | 07/13/2022 |
| Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM | |||
| SWALE | COMPLETE | 07/07/2022 | 09/27/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 07/06/2022 | 07/12/2022 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM | |||
| CUSVC | COMPLETE | 07/06/2022 | 07/11/2022 |
| Note: Released By: LISA ASBILL - - lasbill@palmcoastgov.com | |||
| ELEC | COMPLETE | 07/06/2022 | 07/07/2022 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ENGIN1 | COMPLETE | 07/06/2022 | 07/07/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| LOCATE | COMPLETE | 07/06/2022 | 07/12/2022 |
| Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM | |||
| MECH | HOLD | 07/06/2022 | 07/07/2022 |
| Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM Energy Calcs need to be signed by the builder | |||
| SW1 | COMPLETE | 07/06/2022 | 07/12/2022 |
| Note: Released By: PARREN FLANAGAN - (386)986-2392 - PFLANAGAN@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 07/06/2022 | 07/08/2022 |
| Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION FEE | ¤40.00 | 12/22/2023 |
| SW ENG REINSPECTION 20 | ¤20.00 | 12/22/2023 |
| SW ENG REINSPECTION 30 | ¤30.00 | 12/22/2023 |
| SW ENG REINSPECTION 30 | ¤30.00 | 12/22/2023 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 12/22/2023 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 04/13/2023 |
| CONTRACTOR CHANGE | ¤20.00 | 01/04/2023 |
| 3% FIRE IMPACT FEE CREDIT | (¤11.66) | 08/25/2022 |
| IMPACT FEE FIRE | ¤388.65 | 08/25/2022 |
| IMPACT FEE PARKS | ¤1,455.13 | 08/25/2022 |
| IMPACT FEE SCHOOL | ¤3,600.00 | 08/25/2022 |
| IMPACT FEE TRANSPORTATION | ¤1,764.00 | 08/25/2022 |
| WATER -IRRIGATION INSPECTION | ¤25.00 | 08/25/2022 |
| 3% PARKS IMPACT FEE CREDIT | (¤43.65) | 08/25/2022 |
| SURCHARGE FS 533.721 | ¤2.47 | 08/25/2022 |
| SURCHARGE - FS 468.631 | ¤3.71 | 08/25/2022 |
| SW ENG - FOUNDATION SURVEY | ¤20.00 | 08/25/2022 |
| SW ENG INSPECTION 80 | ¤80.00 | 08/25/2022 |
| SW ENG PRE APRON | ¤30.00 | 08/25/2022 |
| WATER- TURN ON | ¤25.00 | 08/25/2022 |
| ADJUSTMENT 50% | (¤366.24) | 08/25/2022 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 08/25/2022 |
| INSPECTION - RESIDENTIAL | ¤547.25 | 08/25/2022 |
| PLAN REVIEW - RESIDENTIAL | ¤155.22 | 08/25/2022 |
| CONNECTION FEES | ¤1,077.88 | 08/25/2022 |
| CONTRACTOR CHANGE | ¤40.00 | 08/25/2022 |
| SW ENG - REVIEW 20 | ¤20.00 | 08/25/2022 |
| SW ENG RES REVIEW 200 | ¤200.00 | 08/25/2022 |
| 3% TRANS IMPACT FEE CREDIT | (¤52.92) | 08/25/2022 |
| SEWER CREDIT | (¤650.00) | 08/25/2022 |
| SEWER INSPECTION | ¤25.00 | 08/25/2022 |
| SEWER CAPITAL FACILITY | ¤4,939.76 | 08/25/2022 |
| WATER CAPITAL FACILITY FEE | ¤3,626.50 | 08/25/2022 |
| SITE PLAN 30 | ¤30.00 | 08/25/2022 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤17,181.10 |