Permit #2022070496

Permit Details

Status: COED

Parcel Id: 07-11-31-7031-00350-0090
CONDITIONED SPACE: 1517 sqft
GARAGE: 394 sqft
Total Square Footage: 1911 sqft
Block: 00350
Subdivision: 2166 - SECTION 31-ROYAL PALMS
Job Phone: 470-817-1259
Location Address: 9 RICHARD PL
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 08/01/2022
NOC: RECORDED
Applicant name: WADE GILMER JURNEY JR
Owner: NATIONAL HOME CORPORATION

Address

4850 TAMIAMI TRAIL N

NAPLES, FL 34103

Lot: 0090
Contracted Stated Job Value: ¤209,353.00
Job Description: Single Family Residence
Type: CN

Contractor

NATIONAL HOME CORPORATION
Status Location Address Mailing Address State License Number Phone
INACTIVE

1080 HOLCOMB BRIDGE ROAD

,

BLDG 100 - 330

ROSWELL , GA 30076

CBC1257700 (Exp: 08/31/2026) 471-817-1259

Sub Contractors

DUSTIN L ESTEP
Status Location Address State License Number Phone Fax
ACTIVE

2041 N HIAWASSEE RD

APOPKA, FL 32703

CCC1330971 (Exp: 08/31/2026) 407-702-0206 352-988-6629
JASON PATRICK RIBOCK
Status Location Address State License Number Phone
INACTIVE

620 E PINE ST

, 0

ES12001313 (Exp: 08/31/2026) 407-625-0257
RUSSELL J CARTER
Status Location Address State License Number Phone Fax
ACTIVE

PO BOX 302

DELAND, FL 32721

CFC1425938 (Exp: 08/31/2026) 386-736-4220 386-736-4219
RANDALL SCOTT ROSENFELD
Status Location Address State License Number Phone
ACTIVE

234 N WHITNEY ST

PALM COAST, FL 32084

CAC1816641 (Exp: 08/31/2026) 904-599-0082

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 12/12/2023 FINAL APPROVED JWALKER
ROW - STORMWATER FINAL 12/12/2023 APPROVED PFLANAGAN
Note: At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. ---------------------------------------------------------------------- 11/30/2023 - PREVIOUS INSPECTION NOTES 1) ALL BARE AREAS THAT WAS ON THE RIGHT SIDE OF YOUR LOT NEED TO BE SOD 2) NOT ALLOWED TO HAVE SEED AND STRAW IN THE RIGHT OF WAY NEEDS SOD Sec 300.03 F4 Bare earth and damage to any City roadside swales, drainage ditches, canals or other drainage conveyances must be sodded to match grade and prevent soil erosion.
U -UTILITY RESIDENTIAL FINAL 12/12/2023 APPROVED - AS NOTED LFITZGERALD
Note: please dont invert square nut type cap -try to use flush mount caps 11/30/2023 - PREVIOUS INSPECTION NOTES lower sewer C/Ocap-try to use a flush not square nut type
U -UTILITY RESIDENTIAL FINAL 11/30/2023 Disapproved -FEE REQUIRED LFITZGERALD
Note: lower sewer C/Ocap-try to use a flush not square nut type
ROW - STORMWATER FINAL 11/30/2023 Disapproved -FEE REQUIRED PFLANAGAN
Note: 1) ALL BARE AREAS THAT WAS ON THE RIGHT SIDE OF YOUR LOT NEED TO BE SOD 2) NOT ALLOWED TO HAVE SEED AND STRAW IN THE RIGHT OF WAY NEEDS SOD Sec 300.03 F4 Bare earth and damage to any City roadside swales, drainage ditches, canals or other drainage conveyances must be sodded to match grade and prevent soil erosion.
ROW - FINAL APRON (AFTER POUR) 11/30/2023 APPROVED PFLANAGAN
Note: At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved.
ROW- FINAL SURVEY/GRADING CERTIFICATION 11/28/2023 APPROVED PFLANAGAN
Note: At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. -------------------------------------------------------------------------------------- 11/21/2023 - PREVIOUS INSPECTION NOTES 1) CULVERT PIPE HAS TO MUCH PITCH NEED TO REVERIFY THAT THE PIPE IS CORRECT Sec 300.01c3 The driveway culvert(s) must be set within the range established by the Swale Plan.The culvert cannot sloped more than 0.10 feet in the direction of the drainage flow. 2) NEED TO HAVE AN ELEVATION IN THE MIDDLE AGAINST THE BACK OF HOUSE ELEVATIONS SHOW THE 10' OFF STRUCTURE IS HIGHER SO WATER WILL IMPACT THE STRUCTURE 3) NEED TO HAVE .10 OF FALL EVERY 20' Sec.300.01 (4,5,6) Positive fall is considered to be 0.10 feet in 20 feet.
ROW FIELD SURVEY /GRADING CERTIFICATION 11/28/2023 APPROVED PFLANAGAN
Note: At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved.
ROW - DRAINAGE 11/28/2023 APPROVED PFLANAGAN
Note: 11/6/2023 - PREVIOUS INSPECTION NOTES 11/06/23 PLEASE READ PREVIOUS INSPECTORS NOTES. YOU NEED TO MOVE THE PORTA POTTY OUT OF THE CITY STREE AND ONTO YOUR SITE. THIS IS A SAFETY HAZARD AND NEEDS TO BE CORRECTED IMMEDIATELY. INSPECTOR WILL BE BVACK FOR COMPLIANCE REINSPECTION TOMORROW 11/7/23. IF IT IS NOT REMOVED A STOP WORK ORDER MAY BE ISSUED. SEE PHOTO. ________________________________________________________________________________________________________________________ 11/1/2023 - PREVIOUS INSPECTION NOTES 11/1/23= IT IS NECESSARY TO REMOVE THE PORTA POTTY FROM THE CITY ROAD AND PLACE IT ON YOUR PROPERTY. iNSPECTOR BE BACK 11/6/23. PICTURE ATTACHED.
ROW- FINAL SURVEY/GRADING CERTIFICATION 11/21/2023 Disapproved - NO FEE PFLANAGAN
Note: 1) CULVERT PIPE HAS TO MUCH PITCH NEED TO REVERIFY THAT THE PIPE IS CORRECT Sec 300.01c3 The driveway culvert(s) must be set within the range established by the Swale Plan.The culvert cannot sloped more than 0.10 feet in the direction of the drainage flow. 2) NEED TO HAVE AN ELEVATION IN THE MIDDLE AGAINST THE BACK OF HOUSE ELEVATIONS SHOW THE 10' OFF STRUCTURE IS HIGHER SO WATER WILL IMPACT THE STRUCTURE 3) NEED TO HAVE .10 OF FALL EVERY 20' Sec.300.01 (4,5,6) Positive fall is considered to be 0.10 feet in 20 feet.
ROW - DRAINAGE 11/06/2023 Disapproved -FEE REQUIRED FSLADISH
Note: 11/06/23 PLEASE READ PREVIOUS INSPECTORS NOTES. YOU NEED TO MOVE THE PORTA POTTY OUT OF THE CITY STREE AND ONTO YOUR SITE. THIS IS A SAFETY HAZARD AND NEEDS TO BE CORRECTED IMMEDIATELY. INSPECTOR WILL BE BVACK FOR COMPLIANCE REINSPECTION TOMORROW 11/7/23. IF IT IS NOT REMOVED A STOP WORK ORDER MAY BE ISSUED. SEE PHOTO. ________________________________________________________________________________________________________________________ 11/1/2023 - PREVIOUS INSPECTION NOTES 11/1/23= IT IS NECESSARY TO REMOVE THE PORTA POTTY FROM THE CITY ROAD AND PLACE IT ON YOUR PROPERTY. iNSPECTOR BE BACK 11/6/23. PICTURE ATTACHED.
ROW - DRAINAGE 11/01/2023 Disapproved - NO FEE GBERTOLA
Note: 11/1/23= IT IS NECESSARY TO REMOVE THE PORTA POTTY FROM THE CITY ROAD AND PLACE IT ON YOUR PROPERTY. iNSPECTOR BE BACK 11/6/23. PICTURE ATTACHED.
ROW- PRE-APRON (PRE-POUR) 11/01/2023 APPROVED GBERTOLA
Note: 11/1/23=AT THE TIME OF THE INSPECTION, THE CULVERT PIPE IS GOOD AND READY TO POUR; THE BUILDER SHOULD DOUBLE-CHECK THE CULVERT ELEVATIONS BEFORE POURING. MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300E RESIDENTIAL CULVERT DETAIL ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 9/26/2023 - PREVIOUS INSPECTION NOTES 9/26/23= FOOTERS HAVE WASHED IN AND NEED TO BE DUG OUT A MINIMUM OF TWO INCHES OF CONCRETE IS REQUIRED OVER THE EXPOSED EDGE OF THE MITERED END SECTION OF THE PIPE.300 E RESIDENTIAL CULVERT DETAIL ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 9/22/2023 - PREVIOUS INSPECTION NOTES 09/22/23 DUE TO INTERNET OUTAGE I WAS NOT ABLE TO COMPLETE THIS INSPECTION. NO FEE. I AM RESCHEDULING FOR MONDAY SEPTEMBER 25TH. IT DOES NOT APPEAR THAT ANYTHING WAS DONE AS FAR AS CORRECTION THAT THE PREVIOUS INSPECTOR NOTED. NOTE TO INSPECTOR THE CULVERT NEEDS TO BE CUT SO THE MITER END IS NOT SO LONG HOME OWNER TO THE RIGHT CALL CODE ABOUT THE MITER END IS OVER THE PROPERTY LINE RIGHT SIDE ONLY NEED TO BE 8" FROM THE DRIVEWAY TO THE MITER OF THE CULVERT. PER ROBERT ------------------------------------------------------------------------------------ 9/14/2023 - PREVIOUS INSPECTION NOTES 9/13/2023 - PREVIOUS INSPECTION NOTES 09/13/23 need to have 5" minimum concrete coverage over culvert pipe. Need to turn down your band bolts out of the pour area. Dirt and silt has washed onto the culvert pipe, should only be 1/2 way covered. Culvert ends and mitered ends full of water. Need to have a 6" x 6" footer at the mitered end.
ROW- PRE-APRON (PRE-POUR) 09/26/2023 Disapproved -FEE REQUIRED GBERTOLA
Note: 9/26/23=at the time of the inspection culvert pipe is good FOOTERS HAVE WASHED IN AND NEED TO BE DUG OUT A MINIMUM OF TWO INCHES OF CONCRETE IS REQUIRED OVER THE EXPOSED EDGE OF THE MITERED END SECTION OF THE PIPE.300 E RESIDENTIAL CULVERT DETAIL ++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++++ 9/22/2023 - PREVIOUS INSPECTION NOTES 09/22/23 DUE TO INTERNET OUTAGE I WAS NOT ABLE TO COMPLETE THIS INSPECTION. NO FEE. I AM RESCHEDULING FOR MONDAY SEPTEMBER 25TH. IT DOES NOT APPEAR THAT ANYTHING WAS DONE AS FAR AS CORRECTION THAT THE PREVIOUS INSPECTOR NOTED. NOTE TO INSPECTOR THE CULVERT NEEDS TO BE CUT SO THE MITER END IS NOT SO LONG HOME OWNER TO THE RIGHT CALL CODE ABOUT THE MITER END IS OVER THE PROPERTY LINE RIGHT SIDE ONLY NEED TO BE 8" FROM THE DRIVEWAY TO THE MITER OF THE CULVERT. PER ROBERT ------------------------------------------------------------------------------------ 9/14/2023 - PREVIOUS INSPECTION NOTES 9/13/2023 - PREVIOUS INSPECTION NOTES 09/13/23 need to have 5" minimum concrete coverage over culvert pipe. Need to turn down your band bolts out of the pour area. Dirt and silt has washed onto the culvert pipe, should only be 1/2 way covered. Culvert ends and mitered ends full of water. Need to have a 6" x 6" footer at the mitered end.
ROW- PRE-APRON (PRE-POUR) 09/22/2023 Disapproved - NO FEE FSLADISH
Note: 09/22/23 DUE TO INTERNET OUTAGE I WAS NOT ABLE TO COMPLETE THIS INSPECTION. NO FEE. I AM RESCHEDULING FOR MONDAY SEPTEMBER 25TH. IT DOES NOT APPEAR THAT ANYTHING WAS DONE AS FAR AS CORRECTION THAT THE PREVIOUS INSPECTOR NOTED. NOTE TO INSPECTOR THE CULVERT NEEDS TO BE CUT SO THE MITER END IS NOT SO LONG HOME OWNER TO THE RIGHT CALL CODE ABOUT THE MITER END IS OVER THE PROPERTY LINE RIGHT SIDE ONLY NEED TO BE 8" FROM THE DRIVEWAY TO THE MITER OF THE CULVERT. PER ROBERT ------------------------------------------------------------------------------------ 9/14/2023 - PREVIOUS INSPECTION NOTES 9/13/2023 - PREVIOUS INSPECTION NOTES 09/13/23 need to have 5" minimum concrete coverage over culvert pipe. Need to turn down your band bolts out of the pour area. Dirt and silt has washed onto the culvert pipe, should only be 1/2 way covered. Culvert ends and mitered ends full of water. Need to have a 6" x 6" footer at the mitered end.
ROW - DRAINAGE 09/19/2023 APPROVED PFLANAGAN
Note: THE FLAIR ON THE MITER ENDS NEED TO BE CUT SO THERE IS ONLY 8" FROM CUT OF THE MITER AND DRIVEWAY --------------------------------------------------------------------------- rjg. Caller and code enforcement said the neighbor is reporting that the new construction builder is "pouring driveway 3 feet over the property line. I see the Pre pour failed for other reasons, please check that the flare does not cross the property line. Code officer is Dan. His City Cell is 986-286-2013.
U-CROSS CONNECTION 09/14/2023 APPROVED - AS NOTED LFITZGERALD
Note: no irrigation-no cross connectin
ROW- PRE-APRON (PRE-POUR) 09/14/2023 CANCELLED BY APPLICANT FSLADISH
Note: 9/13/2023 - PREVIOUS INSPECTION NOTES 09/13/23 need to have 5" minimum concrete coverage over culvert pipe. Need to turn down your band bolts out of the pour area. Dirt and silt has washed onto the culvert pipe, should only be 1/2 way covered. Culvert ends and mitered ends full of water. Need to have a 6" x 6" footer at the mitered end.
ROW- PRE-APRON (PRE-POUR) 09/13/2023 Disapproved -FEE REQUIRED FSLADISH
Note: 09/13/23 need to have 5" minimum concrete coverage over culvert pipe. Need to turn down your band bolts out of the pour area. Dirt and silt has washed onto the culvert pipe, should only be 1/2 way covered. Culvert ends and mitered ends full of water. Need to have a 6" x 6" footer at the mitered end. See photos for reference.
ELECTRIC - EARLY POWER 06/14/2023 APPROVED JWALKER
U - SEWER TIE IN 06/08/2023 APPROVED - AS NOTED MGIBSON
Note: THIS WAS A VIRTUAL INSPECTION
INSULATION 05/17/2023 APPROVED FWILLIS
Note: 5/16/2023 - PREVIOUS INSPECTION NOTES 5-15-23 1. Fire foam needs to be in every hole through the top plate.
INSULATION 05/16/2023 Disapproved - NO FEE BTAYLOR
Note: 5-15-23 1. Fire foam needs to be in every hole through the top plate.
PEP TANK INSTALLATION REQUEST 05/16/2023 APPROVED CSTONE
ALL ROUGH 05/10/2023 APPROVED JWALKER
Note: 4/26/2023 - PREVIOUS INSPECTION NOTES 4/26/23 Below listed correction has not been made. 4/10/2023 - PREVIOUS INSPECTION NOTES 4-10-23 still missing nail plates as described below. Nail plates at the exterior walls need to be installed before the inspection can pass. The insulation will concealed the areas needed to be nail plated. 3/22/2023 - PREVIOUS INSPECTION NOTES 3/22/23 1. Nail plates at the exterior walls need to be installed before the inspection can pass. The insulation will concealed the areas needed to be nail plated. 2. Item 4 listed below. The plumbing inspector Mark Gibson state the P-trap was installed at plumbing 1st rough.. 3/10/2023 - PREVIOUS INSPECTION NOTES 3/10/23 Below listed violations have not been corrected. 3/8/2023 - PREVIOUS INSPECTION NOTES 1. Ground wire to the Ufer is to be protected running down the exterior wall. 2. Nm wire is to be secured with in 12" minmum of entering the electrcial panel and 12" min where it enters the top plate. 3. Wire not phased out in the electrical panel. 4. Unable to see the washing machine p-trap. 5. No returns installed at the front bedrooms. 6. Install nail plates at the bottom of the furring strips at the exterior walls where the wiring passes through or under 7. Water distribution lines are to be under pressure test.
ALL ROUGH 04/26/2023 Disapproved -FEE REQUIRED JWALKER
Note: 4/26/23 Below listed correction has not been made. 4/10/2023 - PREVIOUS INSPECTION NOTES 4-10-23 still missing nail plates as described below. Nail plates at the exterior walls need to be installed before the inspection can pass. The insulation will concealed the areas needed to be nail plated. 3/22/2023 - PREVIOUS INSPECTION NOTES 3/22/23 1. Nail plates at the exterior walls need to be installed before the inspection can pass. The insulation will concealed the areas needed to be nail plated. 2. Item 4 listed below. The plumbing inspector Mark Gibson state the P-trap was installed at plumbing 1st rough.. 3/10/2023 - PREVIOUS INSPECTION NOTES 3/10/23 Below listed violations have not been corrected. 3/8/2023 - PREVIOUS INSPECTION NOTES 1. Ground wire to the Ufer is to be protected running down the exterior wall. 2. Nm wire is to be secured with in 12" minmum of entering the electrcial panel and 12" min where it enters the top plate. 3. Wire not phased out in the electrical panel. 4. Unable to see the washing machine p-trap. 5. No returns installed at the front bedrooms. 6. Install nail plates at the bottom of the furring strips at the exterior walls where the wiring passes through or under 7. Water distribution lines are to be under pressure test.
ALL ROUGH 04/10/2023 Disapproved -FEE REQUIRED LMILLER
Note: 4-10-23 still missing nail as described below. Nail plates at the exterior walls need to be installed before the inspection can pass. The insulation will concealed the areas needed to be nail plated. 3/22/2023 - PREVIOUS INSPECTION NOTES 3/22/23 1. Nail plates at the exterior walls need to be installed before the inspection can pass. The insulation will concealed the areas needed to be nail plated. 2. Item 4 listed below. The plumbing inspector Mark Gibson state the P-trap was installed at plumbing 1st rough.. 3/10/2023 - PREVIOUS INSPECTION NOTES 3/10/23 Below listed violations have not been corrected. 3/8/2023 - PREVIOUS INSPECTION NOTES 1. Ground wire to the Ufer is to be protected running down the exterior wall. 2. Nm wire is to be secured with in 12" minmum of entering the electrcial panel and 12" min where it enters the top plate. 3. Wire not phased out in the electrical panel. 4. Unable to see the washing machine p-trap. 5. No returns installed at the front bedrooms. 6. Install nail plates at the bottom of the furring strips at the exterior walls where the wiring passes through or under 7. Water distribution lines are to be under pressure test.
ALL ROUGH 03/22/2023 Disapproved - NO FEE JWALKER
Note: 3/22/23 1. Nail plates at the exterior walls need to be installed before the inspection can pass. The insulation will concealed the areas needed to be nail plated. 2. Item 4 listed below. The plumbing inspector Mark Gibson state the P-trap was installed at plumbing 1st rough.. 3/10/2023 - PREVIOUS INSPECTION NOTES 3/10/23 Below listed violations have not been corrected. 3/8/2023 - PREVIOUS INSPECTION NOTES 1. Ground wire to the Ufer is to be protected running down the exterior wall. 2. Nm wire is to be secured with in 12" minmum of entering the electrcial panel and 12" min where it enters the top plate. 3. Wire not phased out in the electrical panel. 4. Unable to see the washing machine p-trap. 5. No returns installed at the front bedrooms. 6. Install nail plates at the bottom of the furring strips at the exterior walls where the wiring passes through or under 7. Water distribution lines are to be under pressure test.
ALL ROUGH 03/16/2023 CANCELLED BY APPLICANT WEB
Note: 3/10/2023 - PREVIOUS INSPECTION NOTES 3/10/23 Below listed violations have not been corrected. 3/8/2023 - PREVIOUS INSPECTION NOTES 1. Ground wire to the Ufer is to be protected running down the exterior wall. 2. Nm wire is to be secured with in 12" minmum of entering the electrcial panel and 12" min where it enters the top plate. 3. Wire not phased out in the electrical panel. 4. Unable to see the washing machine p-trap. 5. No returns installed at the front bedrooms. 6. Install nail plates at the bottom of the furring strips at the exterior walls where the wiring passes through or under 7. Water distribution lines are to be under pressure test.
LATH/BRICK/ WATER BARRIER 03/16/2023 APPROVED JWALKER
ALL ROUGH 03/10/2023 Disapproved -FEE REQUIRED JWALKER
Note: 3/10/23 Below listed violations have not been corrected. 3/8/2023 - PREVIOUS INSPECTION NOTES 1. Ground wire to the Ufer is to be protected running down the exterior wall. 2. Nm wire is to be secured with in 12" minmum of entering the electrcial panel and 12" min where it enters the top plate. 3. Wire not phased out in the electrical panel. 4. Unable to see the washing machine p-trap. 5. No returns installed at the front bedrooms. 6. Install nail plates at the bottom of the furring strips at the exterior walls where the wiring passes through or under 7. Water distribution lines are to be under pressure test.
ALL ROUGH 03/08/2023 Disapproved -FEE REQUIRED JWALKER
Note: 1. Ground wire to the Ufer is to be protected running down. 2. Nm wire is to be secured with in 12" minmum of entering the electrcial panel and 12" min where it enters the top plate. 3. Wire not phased out in the electrical panel. 4. Unable to see the washing machine p-trap. 5. No returns installed at the front bedrooms. 6. Install nail plates at the bottom of the furring strips at the exterior walls where the wiring passes through or under 7. Water distribution lines are to be under pressure test.
ROOF VALLEY & METAL 02/21/2023 APPROVED JWALKER
Note: Inspector Notes from Inspection 2460 Install missing blocking and bracing at gable end. Detail GE01 page D2. Blocking and cross bracing are to be 48" o.c.
WALL SHEATHING 02/13/2023 APPROVED JWALKER
ROOF SHEATHING / BRACES/TIES/DOWN CELL 02/13/2023 APPROVED - AS NOTED JWALKER
Note: Install missing blocking and bracing at gable end. Detail GE01 page D2. Blocking and cross bracing are to be 48" o.c.
FOUND SURVEY APPROVED (OFFICE) 02/09/2023 APPROVED TBAKER
TIE BEAM / LINTEL 02/06/2023 APPROVED JWALKER
MONOLITHIC SLAB 01/25/2023 APPROVED JWALKER
Note: 1/24/2023 - PREVIOUS INSPECTION NOTES Slab needs to be tamped. The rebar back side of garage area needs to be lifted to allow for 3" ground clearance. Remove collapsed soil into footing garage opening. Reseal the poly, center of slab area.
MONOLITHIC SLAB 01/24/2023 Disapproved - NO FEE JWALKER
Note: Slab needs to be tamped. The rebar back side of garage area needs to be lifted to allow for 3" ground clearance. Remove collapsed soil into footing garage opening. Reseal the poly, center of slab area.
PLUMBING 1ST ROUGH UNDERGROUND 01/17/2023 APPROVED MGIBSON
GRAVITY SEWER TEST 01/17/2023 APPROVED MGIBSON
WATER METER INSTALLATION REQUEST 12/28/2022 APPROVED CSTONE

Review History

Department Status Date In Date Out
MECH COMPLETE 02/10/2023 02/10/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
BADMIN INFORMATION 02/09/2023 02/09/2023
Note: Marked INFORMATION By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM Rename your file correctly.
ENGIN1 COMPLETE 02/07/2023 02/09/2023
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON COMPLETE 02/07/2023 02/07/2023
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
MECH HOLD 02/03/2023 02/03/2023
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Duct layout needs to be signed by the AC contractor per 107.1 FBC Residential 2020 7th Edition
MECH COMPLETE 02/02/2023 02/03/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
MECH COMPLETE 07/25/2022 07/25/2022
Note: Released By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM
SWALE COMPLETE 07/13/2022 10/19/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
BLD COMPLETE 07/12/2022 07/15/2022
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
CUSVC COMPLETE 07/12/2022 07/14/2022
Note: Released By: LISA ASBILL - - lasbill@palmcoastgov.com
ELEC COMPLETE 07/12/2022 07/13/2022
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ENGIN1 COMPLETE 07/12/2022 07/13/2022
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
LOCATE COMPLETE 07/12/2022 07/14/2022
Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM
MECH HOLD 07/12/2022 07/13/2022
Note: Held By: CHRIS PISCITELLI - (386)986-3782 - CPISCITELLI@PALMCOASTGOV.COM Orientation of Energy Calcs does not match the site plan. Revise to match per R405.4.2.1 FBC Energy Conservation 2020 7Th Edition
SW1 COMPLETE 07/12/2022 07/18/2022
Note: Released By: PARREN FLANAGAN - (386)986-2392 - PFLANAGAN@PALMCOASTGOV.COM
ZON COMPLETE 07/12/2022 07/19/2022
Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION FEE ¤40.00 12/13/2023
SW ENG - INSPECTION 20 ¤20.00 12/13/2023
SW ENG - INSPECTION 20 ¤20.00 12/13/2023
SW ENG - INSPECTION 20 ¤20.00 12/13/2023
SW ENG - INSPECTION 20 ¤20.00 12/13/2023
SW ENG REINSPECTION 20 ¤20.00 12/13/2023
SW ENG REINSPECTION 30 ¤30.00 12/13/2023
SW ENG REINSPECTION 30 ¤30.00 12/13/2023
REINSPECTION RESIDENTIAL ¤40.00 12/13/2023
PLAN REVIEW - REVISION ¤32.50 04/13/2023
REINSPECTION RESIDENTIAL ¤40.00 04/13/2023
REINSPECTION RESIDENTIAL ¤40.00 04/13/2023
REINSPECTION RESIDENTIAL ¤40.00 04/13/2023
CONTRACTOR CHANGE ¤40.00 01/04/2023
CONTRACTOR CHANGE ¤20.00 01/04/2023
3% FIRE IMPACT FEE CREDIT (¤11.66) 08/01/2022
IMPACT FEE FIRE ¤388.65 08/01/2022
IMPACT FEE PARKS ¤1,455.13 08/01/2022
IMPACT FEE SCHOOL ¤3,600.00 08/01/2022
IMPACT FEE TRANSPORTATION ¤1,764.00 08/01/2022
WATER -IRRIGATION INSPECTION ¤25.00 08/01/2022
3% PARKS IMPACT FEE CREDIT (¤43.65) 08/01/2022
WATER- TURN ON ¤25.00 08/01/2022
ADMINISTRATIVE RESIDENTIAL ¤30.00 08/01/2022
INSPECTION - RESIDENTIAL ¤577.50 08/01/2022
PLAN REVIEW - RESIDENTIAL ¤163.80 08/01/2022
SW ENG - REVIEW 20 ¤20.00 08/01/2022
SW ENG RES REVIEW 200 ¤200.00 08/01/2022
3% TRANS IMPACT FEE CREDIT (¤52.92) 08/01/2022
SEWER CREDIT (¤1,342.00) 08/01/2022
SEWER INSPECTION ¤25.00 08/01/2022
SEWER CAPITAL FACILITY ¤4,939.76 08/01/2022
WATER CAPITAL FACILITY FEE ¤3,626.50 08/01/2022
SITE PLAN 30 ¤30.00 08/01/2022
SW ENG INSPECTION 80 ¤80.00 08/01/2022
SW ENG PRE APRON ¤30.00 08/01/2022
SURCHARGE FS 533.721 ¤6.54 08/01/2022
SURCHARGE - FS 468.631 ¤9.81 08/01/2022
SW ENG - FOUNDATION SURVEY ¤20.00 08/01/2022
CONNECTION FEES ¤1,077.88 08/01/2022
Fees Total Due: ¤0.00 Total Paid: ¤17,096.84