Permit Details
Status: FINAL
| Parcel Id: 09-11-30-0000-01020-0021 |
| Block: 01020 |
| Subdivision: - |
| Job Phone: 305-799-4886 |
| Location Address: 24 HARGROVE GRADE |
| Type: CSD - COMMERCIAL SITE DEVELOPMENT |
| Issue Date: 09/15/2022 |
| NOC: Unknown |
| Applicant name: JOHN EDWARD JAMES |
| Owner: REAL ESTATE DEVELOPMENT OF FLORIDA LLC |
|
Address 32 HARGROVE GRADE PALM COAST, FL 32164 |
| Lot: 0021 |
| Job Description: SITE WORK; PHASE 1 OFFICE WAREHOUSE |
| Type: CN |
Contractor
JAMES COMMERCIAL DEVELOPMENT INC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
9950 KIRCHHERR WEST PALM BEACH, FL 33411 |
CGC1514256 (Exp: 08/31/2026) | 305-799-4886 |
Inspection History
| Type | Request Date | Result | Inspector |
| MAINT BOND ACCEPTANCE (OFFICE) | 05/19/2025 | APPROVED | DRAMIREZ |
| LDSC- LANDSCAPE FINAL | 05/16/2025 | APPROVED - AS NOTED | LFITZGERALD |
| Note: 5/12/2025 5:00:13 PM- PREVIOUS INSPECTION NOTES 5/12/2025 4:56:51 PM- PREVIOUS INSPECTION NOTES Magnolias omitted per city/shrubs-vibernum now screening both backflow units REPEAT COMMENTS NOT ADDRESSED Irrigation system must be modified to inclued: 1. 4 magnolia trees 2. screen plantings for lsrge blue pipe /backflow preventer. 3. Revise irrigation plan after thos plants have been installed | |||
| U - UTILITY COMMERCIAL FINAL | 05/16/2025 | FINAL APPROVED | LFITZGERALD |
| ROW - FINAL INSPECTION | 05/16/2025 | APPROVED | LFITZGERALD |
| LDSC-IRRIGATION FINAL | 05/12/2025 | CANCELLED BY INSPECTOR | RPICATAGI |
| Note: 5/9/2025 2:46:25 PM- PREVIOUS INSPECTION NOTES IRRIGATION SYSTEM IS INCOMPLETE BECUSE LANDSCAPE IS INCOMPLETE. 1. PER EMAIL 4/8/25 - (4) FOUR MAGNOLIAS, 3.5" CAL. ARE REQUIRED ALONG SIDEWAL NEAR WET POND AT ENTRANCE ROAD CONRTACTOR MUST PROVIDE THESE TREEW, THEN MODIFY IRRIATION TO WATER THESE TREES WITH BUBBLERS (2 PER TREE) 2. LARGE BLUE PIPE/BACKFLOW PREVENTER, MUST BE SCREENED WITH 30" HT SHRUBS PER ldc 11.03.01-H. IRRIGATION SYSTEM MUST BE MODIFIED TO ADDRESS THESE PLANTINGS | |||
| LDSC- LANDSCAPE FINAL | 05/12/2025 | Disapproved -FEE REQUIRED | RPICATAGI |
| Note: Irrigation system must be modified to inclued: 1. 4 magnolia trees 2. screen plantings for lsrge blue pipe /backflow preventer. 3. Revise irrigation plan after thos plants have been installed | |||
| LDSC- LANDSCAPE FINAL | 05/09/2025 | Disapproved -FEE REQUIRED | RPICATAGI |
| Note: 5/12/2025 4:56:51 PM- PREVIOUS INSPECTION NOTES REPEAT COMMENTS NOT ADDRESSED Irrigation system must be modified to inclued: 1. 4 magnolia trees 2. screen plantings for lsrge blue pipe /backflow preventer. 3. Revise irrigation plan after thos plants have been installed | |||
| LDSC-IRRIGATION FINAL | 05/09/2025 | APPROVED | RPICATAGI |
| Note: IRRIGATION SYSTEM IS INCOMPLETE BECUSE LANDSCAPE IS INCOMPLETE. 1. PER EMAIL 4/8/25 - (4) FOUR MAGNOLIAS, 3.5" CAL. ARE REQUIRED ALONG SIDEWAL NEAR WET POND AT ENTRANCE ROAD CONRTACTOR MUST PROVIDE THESE TREEW, THEN MODIFY IRRIATION TO WATER THESE TREES WITH BUBBLERS (2 PER TREE) 2. LARGE BLUE PIPE/BACKFLOW PREVENTER, MUST BE SCREENED WITH 30" HT SHRUBS PER ldc 11.03.01-H. IRRIGATION SYSTEM MUST BE MODIFIED TO ADDRESS THESE PLANTINGS | |||
| PLANNING - OFFICE USE - FINAL AS-BUILT SURVEY | 05/09/2025 | APPROVED | DRAMIREZ |
| UC-FINAL SITE INSPECTION | 05/09/2025 | APPROVED - AS NOTED | LFITZGERALD |
| Note: Inspector Notes from Inspection 9114 waiti ng on valve brass ID tabs-told they were ordered all pipe now cleaned out 3/26/2024 - PREVIOUS INSPECTION NOTES all storm pipe now installed-ned to vac out several strctures/pipes associated with-exessive soil build up | |||
| UC-DRAINAGE PIPE PLACEMENT/LAMPING | 05/08/2025 | APPROVED - AS NOTED | LFITZGERALD |
| Note: all pipe now cleaned out 3/26/2024 - PREVIOUS INSPECTION NOTES all storm pipe now installed-ned to vac out several strctures/pipes associated with-exessive soil build up | |||
| CLOSE OUT DOCUMENTS | 05/07/2025 | APPROVED | DRAMIREZ |
| LDSC-PRE-PLANTING TREE QUALITY | 01/14/2025 | APPROVED - AS NOTED | LFITZGERALD |
| Note: *** NOTES ADDED BY LFITZGERALD 1/14/2025 10:08:29 AM *** inspection never scheduled at time when required andrichard never took care of | |||
| LDSC-IRRIGATION FINAL | 01/14/2025 | Disapproved - NO FEE | LFITZGERALD |
| Note: *** NOTES ADDED BY LFITZGERALD 1/14/2025 3:52:51 PM *** as builts not recieved by the city | |||
| LDSC- LANDSCAPE / IRRIGATION AS-BUILT | 01/14/2025 | APPROVED - AS NOTED | LFITZGERALD |
| Note: *** NOTES ADDED BY LFITZGERALD 1/14/2025 10:07:17 AM *** recieved | |||
| U-WATER MAIN INSTALLATION/TESTING/BACKFLOW PREVENTOR | 12/03/2024 | APPROVED | LFITZGERALD |
| Note: 5/3/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY LFITZGERALD 5/3/2024 12:49:33 PM *** wire tone completed (Tony with Gemstone) Inspector Notes from Inspection 9111 Inspector Notes from Inspection 9020 M&S now paving parking lot-bldg.1/2 Inspector Notes from Inspection 9015 all 9 meters now connected and functional Letter of approval recieved from Arch regarding 4in sewer pipe from building 1 to LS 12/1/2023 - PREVIOUS INSPECTION NOTES 4in. sch 40 now installed from front front bldg connection(bldg 1)-(plans call for 6in -John to provide letter from ARCH to allow/approve this change. ) to Y connection at proposed LS/6in now installed vfrom bldg 2(rear)to Y CONNECTION WITH 4IN AT lIFT StATION(LS) 4/10/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9113 Unable to hold pressure(Tomoka Cstr-on site performing testing)-2inch poly pond concete spread weir now installed 10/25/2023 - PREVIOUS INSPECTION NOTES westnside-MES TO STR 1 TO STR 2 HEADING NORTH-57 STONE PLACED UNDERNEATH STRUCTURES 2/23/2024 - PREVIOUS INSPECTION NOTES 2 wet taps now done-8infire(16x8 sleeve with gate valve and 2in saddle with gate valve for potable) and potable now tied in to the 2in BF/METER assembly NOTE -no meters at building to be released until certification by FDEP for water permit 1/6/2024 - PREVIOUS INSPECTION NOTES 3in water main now revised to 2in poly-John to provide documentation(Letter from ARCH.) approving this change-2in installed from Master Backflow Assembly at ROW to Bldg 1 tie in area and to Bldg 2 te in area | |||
| UROW - FINAL DRAINAGE | 12/03/2024 | APPROVED | LFITZGERALD |
| UROW-RETENT/DETENT STABILI | 11/22/2024 | FINAL APPROVED | LFITZGERALD |
| Note: 3/26/2024 - PREVIOUS INSPECTION NOTES all pond slopes sodded except where outfall pipe is installed | |||
| UROW -FINAL GRADE PRIOR SOD | 11/22/2024 | FINAL APPROVED | LFITZGERALD |
| ROW - EROSION CONTROL / INLET PROTE/SILT FENCE | 11/22/2024 | APPROVED | LFITZGERALD |
| Note: 9/20/2023 1:43:32 PM- PREVIOUS INSPECTION NOTES | |||
| UROW - FORM BOARD/CONCRETE (NON STRUCTURAL) | 11/22/2024 | APPROVED | LFITZGERALD |
| Note: 9/22/2023 - PREVIOUS INSPECTION NOTES North/South sidewalks poured 9/21/2023 - PREVIOUS INSPECTION NOTES NORTH/SOUTH THICKEN sidewalk per revised detail ready for concrete placement-2-5bars in thickened footing to be wet set/inspected during pour tomorrow | |||
| U-SEWER FORCE MAIN INSTALL/TESTING | 11/22/2024 | APPROVED | LFITZGERALD |
| Note: Inspector Notes from Inspection 9602 *** NOTES ADDED BY LFITZGERALD 5/6/2024 4:25:05 PM *** ADA mats(Truncated Domes) not yet installed at acsh entrance cross walk/landing-told they are ordered and will be installed ASAP- i will note this if not done before substantial walk, on the punch list, for site close-out 5/3/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY LFITZGERALD 5/3/2024 12:50:12 PM *** wire tone completed(Tony Gemstone) Inspector Notes from Inspection 9111 Inspector Notes from Inspection 9020 M&S now paving parking lot-bldg.1/2 Inspector Notes from Inspection 9015 all 9 meters now connected and functional Letter of approval recieved from Arch regarding 4in sewer pipe from building 1 to LS 12/1/2023 - PREVIOUS INSPECTION NOTES 4in. sch 40 now installed from front front bldg connection(bldg 1)-(plans call for 6in -John to provide letter from ARCH to allow/approve this change. ) to Y connection at proposed LS/6in now installed vfrom bldg 2(rear)to Y CONNECTION WITH 4IN AT lIFT StATION(LS) 3/28/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9050 FM sweep now installed so effluent flows directly-without splashing- into 10inch gravity main Inspector Notes from Inspection 9105 2 day samples all passed 9/20/2023 1:40:12 PM- PREVIOUS INSPECTION NOTES now base installed 3/13/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9040 DAY 1 and Day 2 samples taken sunday night/monday afternoon by owner-Artie-waiting on results Inspector Notes from Inspection 9070 2in. poly-flush only since pipe comes wrapped and pretty much clean and install is usually a clean job Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom Inspector Notes from Inspection 9050 Inspector Notes from Inspection 9105 2 day samples all passed 9/20/2023 1:40:12 PM- PREVIOUS INSPECTION NOTES now base installed 3/13/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9040 DAY 1 and Day 2 samples taken sunday night/monday afternoon by owner-Artie-waiting on results Inspector Notes from Inspection 9070 2in. poly-flush only since pipe comes wrapped and pretty much clean and install is usually a clean job Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom 3/18/2024 - PREVIOUS INSPECTION NOTES jim w/CTL drilled into existing mahhole with 2in green poly(never told anyone), pictures were taken looks ok BUT still need to fit a 45 fittting on end so it lays on the concrete bench which will prevent splasing of effluent, then manhole required to be coated with spectra-shield 3/14/2024 - PREVIOUS INSPECTION NOTES still cant make site visit-tied up on another project 3/13/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9070 not able to make site -resch.tomorrow Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom 1/6/2024 - PREVIOUS INSPECTION NOTES 2in poly instaled from LS to MH tie in area in ROW -next is to core MH and install remaining pipe | |||
| U-WATER METER INSTALLATION/VERIFICATION | 05/13/2024 | APPROVED - AS NOTED | LFITZGERALD |
| Note: *** NOTES ADDED BY LFITZGERALD 5/13/2024 9:49:47 AM *** utility rep noah verified all meters working and to correct units 5/3/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY LFITZGERALD 5/3/2024 9:29:18 AM *** meters missing front curb stop valve and rear union that allows for meter maintanence and/or removal | |||
| BLD - ADA RAMPS/SIDEWALKS/CROSSWALKS | 05/09/2024 | FINAL APPROVED | FWILLIS |
| BLD- ADA PARKING | 05/09/2024 | FINAL APPROVED | FWILLIS |
| Note: 5/6/2024 - PREVIOUS INSPECTION NOTES 5/6/24 - INSTALLING TRUNCATED DOMES THIS AFTERNOON. Inspector Notes from Inspection 1510 direct buried poles | |||
| BLD- ADA SIGNAGECONTROL | 05/06/2024 | APPROVED | FWILLIS |
| Note: Inspector Notes from Inspection 1510 direct buried poles | |||
| BLD- ADA PARKING | 05/06/2024 | CANCELLED BY APPLICANT | FWILLIS |
| Note: 5/6/24 - INSTALLING TRUNCATED DOMES THIS AFTERNOON. Inspector Notes from Inspection 1510 direct buried poles | |||
| UC-TRAF - FINAL (SIGN/PAVEMENT MARKING) | 05/06/2024 | APPROVED - AS NOTED | LFITZGERALD |
| Note: *** NOTES ADDED BY LFITZGERALD 5/6/2024 4:25:05 PM *** ADA mats(Truncated Domes) not yet installed at acsh entrance cross walk/landing-told they are ordered and will be installed ASAP- i will note this if not done before substantial walk, on the punch list, for site close-out | |||
| U-WATER METER INSTALLATION/VERIFICATION | 05/03/2024 | Disapproved - NO FEE | LFITZGERALD |
| Note: *** NOTES ADDED BY LFITZGERALD 5/3/2024 9:29:18 AM *** meters missing front curb stop valve and rear union that allows for meter maintanence and/or removal | |||
| U-SEWER FORCE MAIN INSTALL/TESTING | 05/03/2024 | PARTIALLY APPROVED | LFITZGERALD |
| Note: *** NOTES ADDED BY LFITZGERALD 5/3/2024 12:50:12 PM *** wire tone completed(Tony Gemstone) Inspector Notes from Inspection 9111 Inspector Notes from Inspection 9020 M&S now paving parking lot-bldg.1/2 Inspector Notes from Inspection 9015 all 9 meters now connected and functional Letter of approval recieved from Arch regarding 4in sewer pipe from building 1 to LS 12/1/2023 - PREVIOUS INSPECTION NOTES 4in. sch 40 now installed from front front bldg connection(bldg 1)-(plans call for 6in -John to provide letter from ARCH to allow/approve this change. ) to Y connection at proposed LS/6in now installed vfrom bldg 2(rear)to Y CONNECTION WITH 4IN AT lIFT StATION(LS) 3/28/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9050 FM sweep now installed so effluent flows directly-without splashing- into 10inch gravity main Inspector Notes from Inspection 9105 2 day samples all passed 9/20/2023 1:40:12 PM- PREVIOUS INSPECTION NOTES now base installed 3/13/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9040 DAY 1 and Day 2 samples taken sunday night/monday afternoon by owner-Artie-waiting on results Inspector Notes from Inspection 9070 2in. poly-flush only since pipe comes wrapped and pretty much clean and install is usually a clean job Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom Inspector Notes from Inspection 9050 Inspector Notes from Inspection 9105 2 day samples all passed 9/20/2023 1:40:12 PM- PREVIOUS INSPECTION NOTES now base installed 3/13/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9040 DAY 1 and Day 2 samples taken sunday night/monday afternoon by owner-Artie-waiting on results Inspector Notes from Inspection 9070 2in. poly-flush only since pipe comes wrapped and pretty much clean and install is usually a clean job Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom 3/18/2024 - PREVIOUS INSPECTION NOTES jim w/CTL drilled into existing mahhole with 2in green poly(never told anyone), pictures were taken looks ok BUT still need to fit a 45 fittting on end so it lays on the concrete bench which will prevent splasing of effluent, then manhole required to be coated with spectra-shield 3/14/2024 - PREVIOUS INSPECTION NOTES still cant make site visit-tied up on another project 3/13/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9070 not able to make site -resch.tomorrow Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom 1/6/2024 - PREVIOUS INSPECTION NOTES 2in poly instaled from LS to MH tie in area in ROW -next is to core MH and install remaining pipe | |||
| U-WATER MAIN INSTALLATION/TESTING/BACKFLOW PREVENTOR | 05/03/2024 | PARTIALLY APPROVED | LFITZGERALD |
| Note: *** NOTES ADDED BY LFITZGERALD 5/3/2024 12:49:33 PM *** wire tone completed (Tony with Gemstone) Inspector Notes from Inspection 9111 Inspector Notes from Inspection 9020 M&S now paving parking lot-bldg.1/2 Inspector Notes from Inspection 9015 all 9 meters now connected and functional Letter of approval recieved from Arch regarding 4in sewer pipe from building 1 to LS 12/1/2023 - PREVIOUS INSPECTION NOTES 4in. sch 40 now installed from front front bldg connection(bldg 1)-(plans call for 6in -John to provide letter from ARCH to allow/approve this change. ) to Y connection at proposed LS/6in now installed vfrom bldg 2(rear)to Y CONNECTION WITH 4IN AT lIFT StATION(LS) 4/10/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9113 Unable to hold pressure(Tomoka Cstr-on site performing testing)-2inch poly pond concete spread weir now installed 10/25/2023 - PREVIOUS INSPECTION NOTES westnside-MES TO STR 1 TO STR 2 HEADING NORTH-57 STONE PLACED UNDERNEATH STRUCTURES 2/23/2024 - PREVIOUS INSPECTION NOTES 2 wet taps now done-8infire(16x8 sleeve with gate valve and 2in saddle with gate valve for potable) and potable now tied in to the 2in BF/METER assembly NOTE -no meters at building to be released until certification by FDEP for water permit 1/6/2024 - PREVIOUS INSPECTION NOTES 3in water main now revised to 2in poly-John to provide documentation(Letter from ARCH.) approving this change-2in installed from Master Backflow Assembly at ROW to Bldg 1 tie in area and to Bldg 2 te in area | |||
| UC-ASPHALT PRE PLACEMENT | 04/30/2024 | APPROVED - AS NOTED | LFITZGERALD |
| Note: Inspector Notes from Inspection 9020 M&S now paving parking lot-bldg.1/2 Inspector Notes from Inspection 9015 all 9 meters now connected and functional Letter of approval recieved from Arch regarding 4in sewer pipe from building 1 to LS 12/1/2023 - PREVIOUS INSPECTION NOTES 4in. sch 40 now installed from front front bldg connection(bldg 1)-(plans call for 6in -John to provide letter from ARCH to allow/approve this change. ) to Y connection at proposed LS/6in now installed vfrom bldg 2(rear)to Y CONNECTION WITH 4IN AT lIFT StATION(LS) | |||
| U-WATER SERVICE INSTALLATION | 04/29/2024 | APPROVED - AS NOTED | LFITZGERALD |
| Note: all 9 meters now connected and functional | |||
| U-GRAVITY SEWER INSTALL/TESTING | 04/29/2024 | APPROVED - AS NOTED | LFITZGERALD |
| Note: Inspector Notes from Inspection 9015 all 9 meters now connected and functional Letter of approval recieved from Arch regarding 4in sewer pipe from building 1 to LS 12/1/2023 - PREVIOUS INSPECTION NOTES 4in. sch 40 now installed from front front bldg connection(bldg 1)-(plans call for 6in -John to provide letter from ARCH to allow/approve this change. ) to Y connection at proposed LS/6in now installed vfrom bldg 2(rear)to Y CONNECTION WITH 4IN AT lIFT StATION(LS) | |||
| UROW- CURBING & GUTTER | 04/29/2024 | APPROVED - AS NOTED | LFITZGERALD |
| Note: Inspector Notes from Inspection 9020 all curbing now installed Inspector Notes from Inspection 9015 all 9 meters now connected and functional Letter of approval recieved from Arch regarding 4in sewer pipe from building 1 to LS 12/1/2023 - PREVIOUS INSPECTION NOTES 4in. sch 40 now installed from front front bldg connection(bldg 1)-(plans call for 6in -John to provide letter from ARCH to allow/approve this change. ) to Y connection at proposed LS/6in now installed vfrom bldg 2(rear)to Y CONNECTION WITH 4IN AT lIFT StATION(LS) 3/25/2024 - PREVIOUS INSPECTION NOTES now starting Fcurb install in parking lot | |||
| FIRE ACCESS ROAD | 04/24/2024 | APPROVED | LMILLER |
| BLD - UNDERGROUND SITE LIGHTING CONDUITS | 04/24/2024 | APPROVED | RMARTIN |
| BLD - SITE LIGHTING-PLACEMENT/FOUNDATION | 04/24/2024 | APPROVED - AS NOTED | RMARTIN |
| Note: direct buried poles | |||
| BLD - SITE LIGHTING-POLE SET/FIXTURE | 04/24/2024 | APPROVED | RMARTIN |
| U-WATER MAIN INSTALLATION/TESTING/BACKFLOW PREVENTOR | 04/10/2024 | PARTIALLY APPROVED | LFITZGERALD |
| Note: Inspector Notes from Inspection 9113 Unable to hold pressure(Tomoka Cstr-on site performing testing)-2inch poly pond concete spread weir now installed 10/25/2023 - PREVIOUS INSPECTION NOTES westnside-MES TO STR 1 TO STR 2 HEADING NORTH-57 STONE PLACED UNDERNEATH STRUCTURES 2/23/2024 - PREVIOUS INSPECTION NOTES 2 wet taps now done-8infire(16x8 sleeve with gate valve and 2in saddle with gate valve for potable) and potable now tied in to the 2in BF/METER assembly NOTE -no meters at building to be released until certification by FDEP for water permit 1/6/2024 - PREVIOUS INSPECTION NOTES 3in water main now revised to 2in poly-John to provide documentation(Letter from ARCH.) approving this change-2in installed from Master Backflow Assembly at ROW to Bldg 1 tie in area and to Bldg 2 te in area | |||
| UC-DRAINAGE STRUCT PLACMNT | 04/08/2024 | APPROVED - AS NOTED | LFITZGERALD |
| Note: pond concete spread weir now installed 10/25/2023 - PREVIOUS INSPECTION NOTES westnside-MES TO STR 1 TO STR 2 HEADING NORTH-57 STONE PLACED UNDERNEATH STRUCTURES | |||
| U-SEWER FORCE MAIN INSTALL/TESTING | 03/28/2024 | PARTIALLY APPROVED | LFITZGERALD |
| Note: Inspector Notes from Inspection 9050 FM sweep now installed so effluent flows directly-without splashing- into 10inch gravity main Inspector Notes from Inspection 9105 2 day samples all passed 9/20/2023 1:40:12 PM- PREVIOUS INSPECTION NOTES now base installed 3/13/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9040 DAY 1 and Day 2 samples taken sunday night/monday afternoon by owner-Artie-waiting on results Inspector Notes from Inspection 9070 2in. poly-flush only since pipe comes wrapped and pretty much clean and install is usually a clean job Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom Inspector Notes from Inspection 9050 Inspector Notes from Inspection 9105 2 day samples all passed 9/20/2023 1:40:12 PM- PREVIOUS INSPECTION NOTES now base installed 3/13/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9040 DAY 1 and Day 2 samples taken sunday night/monday afternoon by owner-Artie-waiting on results Inspector Notes from Inspection 9070 2in. poly-flush only since pipe comes wrapped and pretty much clean and install is usually a clean job Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom 3/18/2024 - PREVIOUS INSPECTION NOTES jim w/CTL drilled into existing mahhole with 2in green poly(never told anyone), pictures were taken looks ok BUT still need to fit a 45 fittting on end so it lays on the concrete bench which will prevent splasing of effluent, then manhole required to be coated with spectra-shield 3/14/2024 - PREVIOUS INSPECTION NOTES still cant make site visit-tied up on another project 3/13/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9070 not able to make site -resch.tomorrow Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom 1/6/2024 - PREVIOUS INSPECTION NOTES 2in poly instaled from LS to MH tie in area in ROW -next is to core MH and install remaining pipe | |||
| BLD - SEWER TIE IN | 03/27/2024 | APPROVED | MGIBSON |
| Note: this inspection was done with same inspection type on building permit-just needs signing off | |||
| UC-DRAINAGE PIPE PLACEMENT/LAMPING | 03/26/2024 | PARTIALLY APPROVED | LFITZGERALD |
| Note: all storm pipe now installed-ned to vac out several strctures/pipes associated with-exessive soil build up | |||
| UC-CONSTRUCTION ENTRANCE | 03/26/2024 | APPROVED - AS NOTED | LFITZGERALD |
| Note: 9/20/2023 1:40:12 PM- PREVIOUS INSPECTION NOTES now base installed | |||
| U-WATER MAIN DISINFECTION SAMPLING | 03/26/2024 | APPROVED - AS NOTED | LFITZGERALD |
| Note: Inspector Notes from Inspection 9105 2 day samples all passed 9/20/2023 1:40:12 PM- PREVIOUS INSPECTION NOTES now base installed 3/13/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9040 DAY 1 and Day 2 samples taken sunday night/monday afternoon by owner-Artie-waiting on results Inspector Notes from Inspection 9070 2in. poly-flush only since pipe comes wrapped and pretty much clean and install is usually a clean job Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom | |||
| UROW-RETENT/DETENT STABILI | 03/26/2024 | PARTIALLY APPROVED | LFITZGERALD |
| Note: all pond slopes sodded except where outfall pipe is installed | |||
| UROW- CURBING & GUTTER | 03/25/2024 | PARTIALLY APPROVED | LFITZGERALD |
| Note: now starting Fcurb install in parking lot | |||
| U-SEWER FORCE MAIN INSTALL/TESTING | 03/18/2024 | PARTIALLY APPROVED | LFITZGERALD |
| Note: jim w/CTL drilled into existing mahhole with 2in green poly(never told anyone), pictures were taken looks ok BUT still need to fit a 45 fittting on end so it lays on the concrete bench which will prevent splasing of effluent, then manhole required to be coated with spectra-shield 3/14/2024 - PREVIOUS INSPECTION NOTES still cant make site visit-tied up on another project 3/13/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9070 not able to make site -resch.tomorrow Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom 1/6/2024 - PREVIOUS INSPECTION NOTES 2in poly instaled from LS to MH tie in area in ROW -next is to core MH and install remaining pipe | |||
| U-SEWER FORCE MAIN INSTALL/TESTING | 03/14/2024 | CANCELLED BY APPLICANT | LFITZGERALD |
| Note: still cant make site visit-tied up on another project 3/13/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9070 not able to make site -resch.tomorrow Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom 1/6/2024 - PREVIOUS INSPECTION NOTES 2in poly instaled from LS to MH tie in area in ROW -next is to core MH and install remaining pipe | |||
| U-SEWER FORCE MAIN INSTALL/TESTING | 03/13/2024 | CANCELLED BY APPLICANT | LFITZGERALD |
| Note: Inspector Notes from Inspection 9070 not able to make site -resch.tomorrow Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom 1/6/2024 - PREVIOUS INSPECTION NOTES 2in poly instaled from LS to MH tie in area in ROW -next is to core MH and install remaining pipe | |||
| U-WATER MAIN DISINFECTION | 03/13/2024 | APPROVED - AS NOTED | LFITZGERALD |
| Note: Inspector Notes from Inspection 9070 2in. poly-flush only since pipe comes wrapped and pretty much clean and install is usually a clean job Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom | |||
| U-WATER MAIN DISINFECTION SAMPLING | 03/13/2024 | PARTIALLY APPROVED | LFITZGERALD |
| Note: Inspector Notes from Inspection 9040 DAY 1 and Day 2 samples taken sunday night/monday afternoon by owner-Artie-waiting on results Inspector Notes from Inspection 9070 2in. poly-flush only since pipe comes wrapped and pretty much clean and install is usually a clean job Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom | |||
| U-PUMP STATION PRE-INSTALLATION | 03/06/2024 | APPROVED - AS NOTED | LFITZGERALD |
| Note: LS set on rock and cocrete poured around bottom | |||
| U-PUMP STATION START-UP | 03/06/2024 | APPROVED - AS NOTED | LFITZGERALD |
| Note: Inspector Notes from Inspection 9060 LS start up rep performed all required checks-LS good to go-copy of report to Utility-Rebecca LS set on rock and cocrete poured around bottom | |||
| U-WATER MAIN INSTALLATION/TESTING/BACKFLOW PREVENTOR | 02/23/2024 | PARTIALLY APPROVED | LFITZGERALD |
| Note: 2 wet taps now done-8infire(16x8 sleeve with gate valve and 2in saddle with gate valve for potable) and potable now tied in to the 2in BF/METER assembly NOTE -no meters at building to be released until certification by FDEP for water permit 1/6/2024 - PREVIOUS INSPECTION NOTES 3in water main now revised to 2in poly-John to provide documentation(Letter from ARCH.) approving this change-2in installed from Master Backflow Assembly at ROW to Bldg 1 tie in area and to Bldg 2 te in area | |||
| MONOLITHIC SLAB | 02/14/2024 | APPROVED | FWILLIS |
| Note: Dumpster Pad | |||
| U-WATER MAIN INSTALLATION/TESTING/BACKFLOW PREVENTOR | 01/06/2024 | PARTIALLY APPROVED | LFITZGERALD |
| Note: 3in water main now revised to 2in poly-John to provide documentation approving this change-2in installed from Master Backflow Assembly at ROW to Bldg 1 tie in area and to Bldg 2 tie in area | |||
| U-SEWER FORCE MAIN INSTALL/TESTING | 01/06/2024 | PARTIALLY APPROVED | LFITZGERALD |
| Note: 2in poly instaled from LS to MH tie in area in ROW -next is to core MH and install remaining pipe | |||
| U-GRAVITY SEWER INSTALL/TESTING | 12/01/2023 | PARTIALLY APPROVED | LFITZGERALD |
| Note: 4in. sch 40 now installed for front bldg. from bldg.connection to Y connection at proposed LS | |||
| UC-DRAINAGE STRUCT PLACMNT | 10/25/2023 | PARTIALLY APPROVED | LFITZGERALD |
| Note: westnside-MES TO STR 1 TO STR 2 HEADING NORTH-57 STONE PLACED UNDERNEATH STRUCTURES | |||
| UROW - FORM BOARD/CONCRETE (NON STRUCTURAL) | 09/22/2023 | PARTIALLY APPROVED | LFITZGERALD |
| Note: North/South sidewalks poured 9/21/2023 - PREVIOUS INSPECTION NOTES NORTH/SOUTH THICKEN sidewalk per revised detail ready for concrete placement-2-5bars in thickened footing to be wet set/inspected during pour tomorrow | |||
| UROW - FORM BOARD/CONCRETE (NON STRUCTURAL) | 09/21/2023 | PARTIALLY APPROVED | LFITZGERALD |
| Note: NORTH/SOUTH THICKEN sidewalk per revised detail ready for concrete placement(also 4-6 inches paver base-3/8 rock installed in sidewalk pad)-2-5bars in thickened footing to be wet set/inspected during pour tomorrow | |||
| ROW - EROSION CONTROL / INLET PROTE/SILT FENCE | 09/21/2023 | PARTIALLY APPROVED | LFITZGERALD |
| UC-CONSTRUCTION ENTRANCE | 09/21/2023 | PARTIALLY APPROVED | LFITZGERALD |
| PRE-CON | 09/21/2023 | APPROVED | LFITZGERALD |
| PLAN - PRE-CON 386-986-3750 | 10/10/2022 | APPROVED | DHANEY |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 07/15/2022 | 07/18/2022 |
| Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 07/15/2022 | 07/18/2022 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| PLENG | COMPLETE | 07/15/2022 | 07/15/2022 |
| Note: Released By: DENNIS R. LEAP, P.E. - (386)986-2482 - DLEAP@PALMCOASTGOV.COM | |||
| PLLA | COMPLETE | 07/15/2022 | 07/15/2022 |
| Note: Released By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM | |||
| UD1 | COMPLETE | 07/15/2022 | 07/18/2022 |
| Note: Released By: CHRIS JOHNSON - (386)986-2384 - CJOHNSON@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION- SITE INSPECTOR | ¤40.00 | 05/12/2025 |
| REINSPECTION- SITE INSPECTOR | ¤40.00 | 05/12/2025 |
| SITE PLAN 30 | ¤30.00 | 09/15/2022 |
| ADMINISTRATIVE- SITE DEVELOP | ¤125.00 | 09/15/2022 |
| SITE INSPECTION | ¤1,080.00 | 09/15/2022 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤1,315.00 |