Permit #2022080781
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7013-00090-0190 |
| Total Square Footage: 2000 sqft |
| Block: 00090 |
| Subdivision: 2192 - SECTION 13-BELLE TERRE |
| Job Phone: 904-200-1339 |
| Location Address: 97 BRESSLER LN |
| Type: FS - FIRE SPRINKLER WET COMMERCIAL |
| Issue Date: 11/02/2022 |
| NOC: RECORDED |
| Applicant name: JOHN CHEEK |
| Owner: NEJAME JAMAL |
|
Address 97 BRESSLER LANE PALM COAST, FL 32137 |
| Lot: 0190 |
| Contracted Stated Job Value: ¤9,000.00 |
| Job Description: FIRE SPRINKLER |
| Type: CN |
Contractor
PYE-BARKER FIRE & SAFETY LLC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
8936 WESTERN WAY, SUITE 5 JACKSONVILLE, FL 32256 |
FPC16-000111 (Exp: 06/30/2026) | 904-634-7100 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE SPRINKLER FINAL | 11/16/2022 | FINAL APPROVED | LMILLER |
| Note: 11/15/2022 - PREVIOUS INSPECTION NOTES Record of completion documents are needed to final approve the permit. The documents provided are for yearly testing Please provide the documentation for Record of Completion for the Final inspection per NFPA 1, 13.7.2.2.1 (12) 11-16-22 Record of completion was received and added to the system. Result is Final Approved | |||
| FIRE SPRINKLER FINAL | 11/15/2022 | Disapproved - NO FEE | LMILLER |
| Note: Record of completion documents are needed to final approve the permit. The documents provided are for yearly testing Please provide the documentation for Record of Completion for the Final inspection per NFPA 1, 13.7.2.2.1 (12) | |||
| FIRE SPRINKLER 1ST ROUGH | 11/15/2022 | APPROVED | LMILLER |
| Note: 11/14/2022 - PREVIOUS INSPECTION NOTES 11/9/2022 - PREVIOUS INSPECTION NOTES Need approved plans on site for inspection 107.3 11-14-22 1. Note on plans calls for outside hose connection and there is no FDC for hose connection. 2. First room checked for First rough Sprinkler pipe and sprinkler locations does not match the approved plans (the Master Bedroom calls for 2 sprinklers and only one is insalled. Please revise the plans and have the approved revision on site for inspection. 11-15-22 Approved | |||
| FIRE SPRINKLER 1ST ROUGH | 11/14/2022 | Disapproved -FEE REQUIRED | LMILLER |
| Note: 11/9/2022 - PREVIOUS INSPECTION NOTES Need approved plans on site for inspection 107.3 11-14-22 1. Note on plans calls for outside hose connection and there is no FDC for hose connection. 2. First room checked for First rough Sprinkler pipe and sprinkler locations does not match the approved plans (the Master Bedroom calls for 2 sprinklers and only one is insalled. Please revise the plans and have the approved revision on site for inspection. | |||
| FIRE SPRINKLER 1ST ROUGH | 11/09/2022 | Disapproved -FEE REQUIRED | LMILLER |
| Note: Need approved plans on site for inspection 107.3 | |||
| FIRE SPRINKLER 2ND RGH HYDROSTATIC PRESS TEST | 11/09/2022 | APPROVED | LMILLER |
| Note: Hydro only |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 11/16/2022 | 11/16/2022 |
| Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM | |||
| FI1 | COMPLETE | 10/17/2022 | 10/17/2022 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM A review of FS 633.102 (2) (b) revealked that a Contractor II is able to install piping serving a fire sprinkler system from the "point of service". This being the only remaining review comment, the permit is now approved for issuance. | |||
| FI1 | HOLD | 09/14/2022 | 09/19/2022 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM A separate permit is required for all fire underground work to be performed by a Type V Fire Contractor (Fire underground must be approved prior to approval of the Sprinkler System). | |||
| FI1 | HOLD | 09/13/2022 | 09/13/2022 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM All comments below per the 2020 Florida Fire Prevention Code. And or 2020 FBC Please provide a written response to each comment below in a response letter and provide clouded response changes on plan sheets and add page locations for each response. 1. Floor plan needs to indicate total number of square feet of home. 2. FDC will need to be at the Fire Back Flow Preventer Per AHJ (the riser detail shows a wall mounted FDC, this is not allowed per AHJ). 3. Please submit Material cut sheets for pipe to be used. 4. A separate permit is required for fire underground. (Fire underground must be approved prior to approval of the Sprinkler System). | |||
| FI1 | HOLD | 08/12/2022 | 08/24/2022 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM 1. You are proposing a 13-D Sprinkler System. The system required for this location is a 13-R. Please revise documents for review. 2. Floor plan needs to indicate total number of square feet of home. 3. FDC will need to be at the Fire Back Flow Preventer Per AHJ (the riser detail shows a wall mounted FDC). 4. Please submit Material cut sheets for pipe to be used. 5. A separate permit is required for fire underground. (Fire underground must be approved prior to approval of the Sprinkler System). | |||
| UD1 | COMPLETE | 08/12/2022 | 08/15/2022 |
| Note: Released By: CHRIS JOHNSON - (386)986-2384 - CJOHNSON@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION - COMMERCIAL | ¤60.00 | 11/14/2022 |
| REINSPECTION - COMMERCIAL | ¤60.00 | 11/11/2022 |
| SURCHARGE FS 533.721 | ¤2.00 | 11/02/2022 |
| SURCHARGE - FS 468.631 | ¤2.00 | 11/02/2022 |
| SW ENG - INSPECTION 20 | ¤20.00 | 11/02/2022 |
| ADJUSTMENT 50% | (¤121.95) | 11/02/2022 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 11/02/2022 |
| INSPECTION - FIRE COMMERCIAL | ¤65.40 | 11/02/2022 |
| PLAN REVIEW - COMMERCIAL | ¤103.50 | 11/02/2022 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤265.95 |