I want to search for...

Permit #2022080782

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7013-00090-0190
Total Square Footage: 2000 sqft
Block: 00090
Subdivision: 2192 - SECTION 13-BELLE TERRE
Job Phone: 904-634-7100
Location Address: 97 BRESSLER LN
Type: FRA - FIRE RESIDENTIAL ALARM
Issue Date: 10/14/2022
NOC: RECORDED
Applicant name: SEAN THOMAS FATHERREE
Owner: NEJAME JAMAL

Address

97 BRESSLER LANE

PALM COAST, FL 32137

Lot: 0190
Contracted Stated Job Value: ¤4,800.00
Job Description: FIRE ALARM
Type: CN

Contractor

PYE-BARKER FIRE & SAFETY, LLC
Status Location Address State License Number Phone
INACTIVE

8936 WESTERN WAY, SUITE 5

JACKSONVILLE, FL 32256

EF20001661 (Exp: 08/31/2024) 904-634-7100

Inspection History

Type Request Date Result Inspector
FIRE ALARM FINAL 11/15/2022 Disapproved - NO FEE LMILLER
Note: 11/14/2022 - PREVIOUS INSPECTION NOTES The installation does not match the approved plans. Please revise the plans to be sure all device locations, end of line resistors etc. match the revised plans for final inspection 11-15-22 Record of completion documents are needed to final approve the permit. The documents provided are for yearly testing Please provide the documentation for Record of Completion for the Final inspection per NFPA 72, 7.2.1 (12)
FIRE ALARM FINAL 11/15/2022 FINAL APPROVED LMILLER
Note: 11/15/2022 - PREVIOUS INSPECTION NOTES 11/14/2022 - PREVIOUS INSPECTION NOTES The installation does not match the approved plans. Please revise the plans to be sure all device locations, end of line resistors etc. match the revised plans for final inspection 11-15-22 Record of completion documents are needed to final approve the permit. The documents provided are for yearly testing Please provide the documentation for Record of Completion for the Final inspection per NFPA 72, 7.2.1 (12) 11-15-22 Correction to the last entry the record of completion was received and the result is Final Approved
FIRE ALARM FINAL 11/14/2022 Disapproved -FEE REQUIRED LMILLER
Note: The installation does not match the approved plans. Please revise the plans to be sure all device locations, end of line resistors etc. match the revised plans for final inspection also Stobe devices are not in sinc

Review History

Department Status Date In Date Out
FI1 COMPLETE 11/15/2022 11/15/2022
Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM
FI1 COMPLETE 10/14/2022 10/14/2022
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
BADMIN INFORMATION 10/14/2022 10/14/2022
Note: Marked INFORMATION By: MARGA DEFREITAS - - MDEFREITAS@PALMCOASTGOV.COM PLEASE RENAME THE PLANS ACCORDING TO WHAT THEY ARE FA1,FA2
FI1 HOLD 09/09/2022 09/14/2022
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM All comments below per the 2020 Florida Fire Prevention Code. And or 2020 FBC Please provide a written response to each comment below in a response letter and provide clouded response changes on plan sheets and add page locations for each response. Please show locations of the EOL's and identify in the symbols
FI1 HOLD 08/12/2022 08/24/2022
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM 1. Provide end of line location on drawings per NFPA 72 -7.4.8 2. Please clean up the floor plan room names (it appears the Garage is shown as a Master Bedroom etc.).

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION - COMMERCIAL ¤60.00 11/14/2022
SURCHARGE FS 533.721 ¤2.00 10/14/2022
SURCHARGE - FS 468.631 ¤2.00 10/14/2022
ADJUSTMENT 50% (¤101.50) 10/14/2022
ADMINISTRATIVE - COMMERCIAL ¤75.00 10/14/2022
INSPECTION - FIRE COMMERCIAL ¤63.00 10/14/2022
PLAN REVIEW - COMMERCIAL ¤65.00 10/14/2022
Fees Total Due: ¤0.00 Total Paid: ¤165.50