Permit #2022081367
Permit Details
Status: CANCEL
| Parcel Id: 19-11-31-0330-00000-00B0 |
| Total Square Footage: 1050 sqft |
| Block: 00000 |
| Subdivision: 2298 - AMERICAN VILLAGE |
| Job Phone: 386-931-6577 |
| Location Address: 67 GREEN CIR |
| Type: BC - BUILDING COMMERCIAL |
| Issue Date: 08/24/2022 |
| NOC: Unknown |
| Applicant name: LUIS JORGE MEDEIROS |
| Owner: HAMMOCK REAL ESTATE DEVELOPMENT LLC |
|
Address 200 OCEAN CREST DRIVE #1111 PALM COAST, FL 32137 |
| Lot: 00B0 |
| Contracted Stated Job Value: ¤50,000.00 |
| Job Description: POOL PAVILION - AMENITY BUILDING |
| Type: CN |
| Original Permit #: 2021030883 |
Contractor
A PLUS HOME IMPROVEMENTS LLC
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
306 S RAILROAD ST BUNNELL, FL 32110 |
CGC1519145 (Exp: 08/31/2026) | 386-931-6577 | 386-263-3331 |
Sub Contractors
HEATH EDWARD SANFORD
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
1351 HAZELNUT ST BUNNELL, FL 32110 |
CFC1427527 (Exp: 08/31/2026) | 386-445-2532 | 386-445-5575 |
STEPHEN COURTEAUX
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
85 North Yonge Street Ormond Beach, FL 32174 |
EC13001748 (Exp: 08/31/2026) | (386) 672-4900 | 386-676-7472 |
JOSE E ORTIZ JR
| Status | Location Address | Mailing Address | State License Number | Phone |
| CANCEL |
4601 E MOODY BLVD BUNNELL, FL 32110 |
SUITE B7 BUNNELL, FL 32110 |
RC29027619 (Exp: 08/31/2023) | 386-503-6922 |
HEATH EDWARD SANFORD
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
1351 HAZELNUT ST BUNNELL, FL 32110 |
CFC1427527 (Exp: 08/31/2026) | 386-445-2532 | 386-445-5575 |
STEPHEN COURTEAUX
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
85 North Yonge Street Ormond Beach, FL 32174 |
EC13001748 (Exp: 08/31/2026) | (386) 672-4900 | 386-676-7472 |
JOSE E ORTIZ JR
| Status | Location Address | Mailing Address | State License Number | Phone |
| CANCEL |
4601 E MOODY BLVD BUNNELL, FL 32110 |
SUITE B7 BUNNELL, FL 32110 |
RC29027619 (Exp: 08/31/2023) | 386-503-6922 |
Inspection History
| Type | Request Date | Result | Inspector |
| EXTERIOR STRAP/CLIP | 02/16/2023 | APPROVED - AS NOTED | JWALKER |
| Note: The strapping holding 2x rafter to the LVL beam are approved. The anchors holding the LVL to the block columns still need to be detailed and submitted to the building department by the engineer. More notes can be found on the 2/15/23 roof braced inspection. | |||
| ROOF SHEATHING / BRACE / TIE DOWN | 02/15/2023 | Disapproved - NO FEE | JWALKER |
| Note: 2/15/23 1. Please have engineer specifi if P.T. rafter and collar ties are to be used. Or if the existing non P.T. grade #2 rafters and collars ties can remain. 2. Anchor detail for LVLs to block colums has not been provided. Please provide nail patter for fastening the two LVLs together. 3. Gable end framing and anchoring detail has not been provided. Submitt changes and revisions to the building department. 2/13/2023 - PREVIOUS INSPECTION NOTES THIS IS A REINSPECTION Conventional framing details shows 2 x 12 rafter at 16" o.c. and 2 x 10 Pt collar ties. Contractor use 2x8s for rafters and 2x6 for collar ties. Only 2 of the rafters installed are of the Pressure treated type. Please provdide details of how the Versa Lam 16" beam are to be fastened to the block wall. And the connections to the 4 Block columns. The print is also lacking a detail for the gable end and how it is to be connected to the Versa Lam beam please provide details. 2 of the 2x8 rafters in the back area of the building are missing the hold down straps. Right side of building. Please submitt above listed detail and revisons of materials to the building department. | |||
| ROOF SHEATHING / BRACE / TIE DOWN | 02/13/2023 | CANCELLED BY APPLICANT | JWALKER |
| Note: THIS IS A REINSPECTION Conventional framing details shows 2 x 12 rafter at 16" o.c. and 2 x 10 Pt collar ties. Contractor use 2x8s for rafters and 2x6 for collar ties. Only 2 of the rafters installed are of the Pressure treated type. Please provdide details of how the Versa Lam 16" beam are to be fastened to the block wall. And the connections to the 4 Block columns. The print is also lacking a detail for the gable end and how it is to be connected to the Versa Lam beam please provide details. 2 of the 2x8 rafters in the back area of the building are missing the hold down straps. Right side of building. Please submitt above listed detail and revisons of materials to the building department. | |||
| WATER METER INSTALLATION REQUEST | 06/17/2022 | CANCELLED BY INSPECTOR | LFITZGERALD |
| Note: to be inspected on the site permit | |||
| WATER SERVICE | 06/16/2022 | CANCELLED BY INSPECTOR | MGIBSON |
| Note: WRONG INSPECTION CALLED, CONTRACTOR WAS LOOKING FOR A METER TO BE SET, SPOKE TO CONTRACTOR AND EXPLAINED TO HIM THAT REQUIRED A RPZ BACKFLOW DEVICE AND THAT PLUMBER NEEDS TO GO TO THE UTILITY DEPARTMENT | |||
| ELECTRIC OTHER | 05/11/2022 | CANCELLED BY INSPECTOR | JMUNSON |
| Note: Dont do TUGs on commercial buildings must set temp pole or wait till early power. | |||
| ROOF SHEATHING / BRACE / TIE DOWN | 04/28/2022 | Disapproved - NO FEE | JWALKER |
| Note: Conventional framing details shows 2 x 12 rafter at 16" o.c. and 2 x 10 Pt collar ties. Contractor use 2x8s for rafters and 2x6 for collar ties. Only 2 of the rafters installed are of the Pressure treated type. Please provdide details of how the Versa Lam 16" beam are to be fastened to the block wall. And the connections to the 4 Block columns. The print is also lacking a detail for the gable end and how it is to be connected to the Versa Lam beam please provide details. 2 of the 2x8 rafters in the back area of the building are missing the hold down straps. Right side of building. Please submitt above listed detail and revisons of materials to the building department. | |||
| LATH/BRICK/WATER BARRIER | 12/29/2021 | APPROVED | FWILLIS |
| MONOLITHIC SLAB | 06/30/2021 | APPROVED | MMESSER |
| PLUMBING 1ST ROUGH | 06/18/2021 | APPROVED | JGIBSON |
| Note: THIS IS A REINSPECTION NOT READY NO TEST ON WATER OR SANITARY | |||
| PLUMBING 1ST ROUGH | 06/11/2021 | Disapproved -FEE REQUIRED | JGIBSON |
| Note: NOT READY NO TEST ON WATER OR SANITARY | |||
| FOUNDATION SURVEY - OFFICE USE ONLY | |||
| ELECTRIC FINAL | |||
| FRAMING | |||
| PLUMBING 2ND ROUGH | |||
| GRAVITY SEWER | |||
| BLD - SEWER TIE IN | |||
| PLUMBING FINAL | |||
| HVAC ROUGH | |||
| HVAC FINAL | |||
| ELECTRIC 1ST ROUGH | |||
| ELECTRIC 2ND ROUGH | |||
| ELECTRIC - EARLY POWER | |||
| U - UTILITY COMMERCIAL FINAL | |||
| ROOF SHEATHING / BRACE / TIE DOWN | |||
| Note: 2/15/2023 - PREVIOUS INSPECTION NOTES 2/15/23 1. Please have engineer specifi if P.T. rafter and collar ties are to be used. Or if the existing non P.T. grade #2 rafters and collars ties can remain. 2. Anchor detail for LVLs to block colums has not been provided. Please provide nail patter for fastening the two LVLs together. 3. Gable end framing and anchoring detail has not been provided. Submitt changes and revisions to the building department. 2/13/2023 - PREVIOUS INSPECTION NOTES THIS IS A REINSPECTION Conventional framing details shows 2 x 12 rafter at 16" o.c. and 2 x 10 Pt collar ties. Contractor use 2x8s for rafters and 2x6 for collar ties. Only 2 of the rafters installed are of the Pressure treated type. Please provdide details of how the Versa Lam 16" beam are to be fastened to the block wall. And the connections to the 4 Block columns. The print is also lacking a detail for the gable end and how it is to be connected to the Versa Lam beam please provide details. 2 of the 2x8 rafters in the back area of the building are missing the hold down straps. Right side of building. Please submitt above listed detail and revisons of materials to the building department. | |||
| INSULATION | |||
| BUILDING FINAL | |||
| FIRE FINAL | |||
| EXTERIOR ARCHITECTURAL FEATURES |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 11/29/2022 | 12/05/2022 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM | |||
| ARCHR | COMPLETE | 08/24/2022 | 08/25/2022 |
| Note: Released By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM | |||
| BLD | HOLD | 08/24/2022 | 08/29/2022 |
| Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code REVIEW COMMENTS: 1. Revised Cross Section Detail calls-out #2 Grade Lumber. Provide Grade of Lumber to be installed. | |||
| DSD | COMPLETE | 08/24/2022 | 08/25/2022 |
| Note: Released By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 08/24/2022 | 08/25/2022 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| FI1 | CANCEL | 08/24/2022 | 08/25/2022 |
| Note: not needed | |||
| MECH | CANCEL | 08/24/2022 | 08/25/2022 |
| Note: not needed | |||
| PLLA | COMPLETE | 08/24/2022 | 08/25/2022 |
| Note: Released By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM | |||
| PLUM | COMPLETE | 08/24/2022 | 08/30/2022 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM | |||
| UD1 | COMPLETE | 08/24/2022 | 08/25/2022 |
| Note: Released By: CHRIS JOHNSON - (386)986-2384 - CJOHNSON@PALMCOASTGOV.COM | |||
| ARCHR | COMPLETE | 05/04/2021 | 05/06/2021 |
| Note: Released By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM | |||
| UD1 | COMPLETE | 04/22/2021 | 04/22/2021 |
| Note: Released By: CHRIS JOHNSON - - CJOHNSON@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 04/22/2021 | 05/06/2021 |
| Note: Released By: FRED REODICA - (386)986-4734 - FREODICA@PALMCOASTGOV.COM | |||
| ARCHR | HOLD | 04/22/2021 | 04/23/2021 |
| Note: Held By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM Architectural plan is missing the color chart. Please provide colors to be used for the building and roof. | |||
| PLLA | COMPLETE | 03/17/2021 | 03/31/2021 |
| Note: Released By: DAMARIS RAMIREZ - (386)986-3750 - dramirez@ci.palm-coast.fl.us Landscaping for this site will be part of the site permit. | |||
| ARCHR | HOLD | 03/12/2021 | 03/31/2021 |
| Note: Held By: DAMARIS RAMIREZ - (386)986-3750 - dramirez@ci.palm-coast.fl.us Provide DO approved architectural plans. | |||
| BLD | HOLD | 03/12/2021 | 03/26/2021 |
| Note: Held By: FRED REODICA - (386)986-4734 - FReodica@ci.palm-coast.fl.us 1. Clarify footer detail as to the number of # 5 rebar and depth as there are (2) different details per FBC 7th Ed. Sec. 107.2.1. 2. Provide truss layout per FBCR 7th Ed. Sec. R802.10.2. | |||
| DSD | COMPLETE | 03/12/2021 | 03/18/2021 |
| Note: Released By: JACQUELINE GONZALEZ - - JGONZALEZ@CI.PALM-COAST.FL.US | |||
| ELEC | COMPLETE | 03/12/2021 | 03/17/2021 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| FI1 | COMPLETE | 03/12/2021 | 03/23/2021 |
| Note: Released By: WILLIAM MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 03/12/2021 | 03/18/2021 |
| Note: Released By: CHRIS PISCITELLI - - CPISCITELLI@PALMCOASTGOV.COM | |||
| PLUM | COMPLETE | 03/12/2021 | 03/26/2021 |
| Note: Released By: FRED REODICA - (386)986-4734 - FReodica@ci.palm-coast.fl.us | |||
| UD1 | HOLD | 03/12/2021 | 03/16/2021 |
| Note: Held By: CHRIS JOHNSON - - cjohnson@ci.palm-coast.fl.us Utility fees, agreements and FDEP permits or Design Engineers letter of determination must be completed before a building permit will be issued. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 50% | (¤212.50) | 08/24/2022 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 08/24/2022 |
| INSPECTION COMMERCIAL | ¤350.00 | 08/24/2022 |
| CONTRACTOR CHANGE | ¤40.00 | 08/24/2022 |
| REINSPECTION FEE | ¤40.00 | 08/24/2022 |
| SURCHARGE FS 533.721 | ¤2.49 | 08/24/2022 |
| SURCHARGE - FS 468.631 | ¤3.73 | 08/24/2022 |
| SITE PLAN 30 | ¤30.00 | 08/24/2022 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤328.72 |