I want to search for...
Permit #2022081615
Permit Details
Status: CANCEL
| Parcel Id: 07-11-31-7027-00450-0130 |
| Block: 00450 |
| Subdivision: 2128 - SECTION 27-WYNNFIELD |
| Job Phone: 386-574-2909 |
| Location Address: 9 WOOD CREST LN |
| Type: GEN - GENERATOR |
| NOC: RECORDED |
| Applicant name: BRIAN THOMAS HANEY |
| Owner: PERKINS DAVID & LYNN H&W |
|
Address 9 WOOD CREST LN PALM COAST, FL 32164 |
| Lot: 0130 |
| Contracted Stated Job Value: ¤7,500.00 |
| Job Description: GENERAC Generator installation |
| Type: CN |
Contractor
DELTRON ELECTRIC FL
| Status | Location Address | Mailing Address | State License Number | Phone |
| CANCEL |
1308 E NORMANDY BLVD DELTONA, FL 32725 |
STE E DELTONA, FL 32725 |
EC13009060 (Exp: 08/31/2022) | 386-574-2909 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 09/22/2022 | 09/22/2022 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ELEC | HOLD | 09/15/2022 | 09/19/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM #2 is not rated for the 100 amp breaker in the generator. NEC 2017 310.15(b)(16) | |||
| ELEC | HOLD | 09/08/2022 | 09/14/2022 |
| Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code PLAN REVIEW COMMENTS: 1. Provide size of the proposed wire to be installed. Revised plan calls-out 4 - AWG XHHW and 1 – AWG XHHW. | |||
| ELEC | HOLD | 08/31/2022 | 08/31/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM #2 is not rated for the 100 amp breaker in the generator. NEC 2017 310.15(b)(16) | |||
| ELEC | HOLD | 08/31/2022 | 09/06/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM #2 is not rated for the 100 amp breaker in the generator. NEC 2017 310.15(b)(16) | |||
| ELEC | HOLD | 08/29/2022 | 08/30/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM #4 is not rated for the 100 amp breaker in the generator. NEC 2017 310.15(b)(16) | |||
| ZON | COMPLETE | 08/29/2022 | 08/31/2022 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 50% | (¤61.25) | |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | |
| INSPECTION - RESIDENTIAL | ¤60.00 | |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | |
| SURCHARGE FS 533.721 | ¤2.00 | |
| SURCHARGE - FS 468.631 | ¤2.00 | |
| SITE PLAN 15 | ¤15.00 | |
| Fees | Total Due: ¤80.25 | Total Paid: ¤0.00 |