I want to search for...

Permit #2022081615

Permit Details

Status: CANCEL

Parcel Id: 07-11-31-7027-00450-0130
Block: 00450
Subdivision: 2128 - SECTION 27-WYNNFIELD
Job Phone: 386-574-2909
Location Address: 9 WOOD CREST LN
Type: GEN - GENERATOR
NOC: RECORDED
Applicant name: BRIAN THOMAS HANEY
Owner: PERKINS DAVID & LYNN H&W

Address

9 WOOD CREST LN

PALM COAST, FL 32164

Lot: 0130
Contracted Stated Job Value: ¤7,500.00
Job Description: GENERAC Generator installation
Type: CN

Contractor

DELTRON ELECTRIC FL
Status Location Address Mailing Address State License Number Phone
CANCEL

1308 E NORMANDY BLVD

DELTONA, FL 32725

STE E

DELTONA, FL 32725

EC13009060 (Exp: 08/31/2022) 386-574-2909

Inspection History

Type Request Date Result Inspector
ELECTRIC FINAL

Review History

Department Status Date In Date Out
ELEC COMPLETE 09/22/2022 09/22/2022
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ELEC HOLD 09/15/2022 09/19/2022
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM #2 is not rated for the 100 amp breaker in the generator. NEC 2017 310.15(b)(16)
ELEC HOLD 09/08/2022 09/14/2022
Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code PLAN REVIEW COMMENTS: 1. Provide size of the proposed wire to be installed. Revised plan calls-out 4 - AWG XHHW and 1 – AWG XHHW.
ELEC HOLD 08/31/2022 08/31/2022
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM #2 is not rated for the 100 amp breaker in the generator. NEC 2017 310.15(b)(16)
ELEC HOLD 08/31/2022 09/06/2022
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM #2 is not rated for the 100 amp breaker in the generator. NEC 2017 310.15(b)(16)
ELEC HOLD 08/29/2022 08/30/2022
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM #4 is not rated for the 100 amp breaker in the generator. NEC 2017 310.15(b)(16)
ZON COMPLETE 08/29/2022 08/31/2022
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 50% (¤61.25)
ADMINISTRATIVE RESIDENTIAL ¤30.00
INSPECTION - RESIDENTIAL ¤60.00
PLAN REVIEW - MISC 32.50 ¤32.50
SURCHARGE FS 533.721 ¤2.00
SURCHARGE - FS 468.631 ¤2.00
SITE PLAN 15 ¤15.00
Fees Total Due: ¤80.25 Total Paid: ¤0.00