I want to search for...
Permit #2022110126
Permit Details
Status: FINAL
| Parcel Id: 06-12-31-5815-00000-0010 |
| Block: 00000 |
| Subdivision: 2118 - TOWN CENTER PHASE I |
| Job Phone: 908-334-6117 |
| Location Address: 800 BELLE TERRE PKWY |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 02/20/2023 |
| NOC: Unknown |
| Applicant name: KIM EUGENE ADAMS |
| Owner: REAL SUB LLC |
|
Address PO BOX 32018 LAKELAND, FL 33802 |
| Lot: 0010 |
| Contracted Stated Job Value: ¤2,400.00 |
| Job Description: UNIT 112 - REMOVING 4 INTERIOR WALLS |
| Type: CN |
Contractor
JMD QUALITY CONSTRUCTION, LLC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
300 CANOPY WALK LANE APT 342 ZEPHYRHILLS, FL 33542 |
CGC1526854 (Exp: 08/31/2026) | 908-334-6117 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 02/24/2023 | FINAL APPROVED | CPISCITELLI |
| Note: 2/23/2023 - PREVIOUS INSPECTION NOTES Need to seal return ducts in hallway | |||
| FIRE FINAL | 02/24/2023 | FINAL APPROVED | CPISCITELLI |
| Note: 2/23/2023 - PREVIOUS INSPECTION NOTES 1. Fire extinguishers need to be certified and up to date. 2. Emergency light in right office needs to be working. | |||
| U - UTILITY COMMERCIAL FINAL | 02/23/2023 | FINAL APPROVED | JHARDING |
| FIRE FINAL | 02/23/2023 | Disapproved -FEE REQUIRED | CPISCITELLI |
| Note: 1. Fire extinguishers need to be certified and up to date. 2. Emergency light in right office needs to be working. | |||
| HVAC FINAL | 02/23/2023 | Disapproved -FEE REQUIRED | CPISCITELLI |
| Note: Need to seal return ducts in hallway | |||
| BUILDING FINAL | 02/23/2023 | FINAL APPROVED | FWILLIS |
| FIRE FINAL | 02/21/2023 | Disapproved - NO FEE | RMARTIN |
| Note: ALL EMERGENCY AND EXITS NEED TO BE WORKING, AND FIRE EXTINGUISHERS NEED TO BE CERTIFIED AND UP TO DATE | |||
| HVAC FINAL | 02/21/2023 | Disapproved - NO FEE | CPISCITELLI |
| Note: 1. Need return air in back office 2. Need metal sleeves in all transfer grills. 3. Need to strap supply line in back office. Laying on sprinkler pipe. 4. Need more return air transfer for large exam room. Main returns in room. 5. Need to cap off dryer vent | |||
| ELECTRIC 2ND ROUGH | 02/21/2023 | APPROVED | RMARTIN |
| ELECTRIC FINAL | 02/21/2023 | APPROVED | RMARTIN |
| ABOVE CEILING | 02/21/2023 | APPROVED | RMARTIN |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 01/09/2023 | 01/10/2023 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 01/09/2023 | 01/10/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| DSD | COMPLETE | 12/09/2022 | 12/09/2022 |
| Note: Released By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM | |||
| ELEC | HOLD | 12/09/2022 | 12/12/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. FBC 2020 Existing . This is a Level 2 alteration.FBC 2020 Existing 603 2. Submit a lighting plan 3. Any outlets within 6 feet of water need to be GFCI protected. NEC 2017 210.8 (B) | |||
| FI1 | COMPLETE | 12/09/2022 | 12/15/2022 |
| Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM | |||
| MECH | HOLD | 12/09/2022 | 12/12/2022 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide code analysis showing occupangy classification per chapter 3 FBC Building 2020 7Th edition and correct level of alteration per Chapter 6 FBC Existing Building 2020 7Th edition. (Nott a level 1) 2. Provide duct layout showing supply, return, fresh air and exhaust with existing and proposed changes per FBC mechanical 2020 7th edition (Second Request) Further comments could be required after initial comments are reviewed. | |||
| BLD | COMPLETE | 12/09/2022 | 12/15/2022 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM | |||
| BLD | HOLD | 11/02/2022 | 11/14/2022 |
| Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code PLAN REVIEW COMMENTS: 1. Provide a Code analysis per the 2020 7th Edition Florida Building Code Existing. | |||
| DSD | HOLD | 11/02/2022 | 11/03/2022 |
| Note: Held By: JACQUELINE GONZALEZ - (386)986-3751 - JGONZALEZ@PALMCOASTGOV.COM Provide information regarding the type of business occupying the space. | |||
| ELEC | HOLD | 11/02/2022 | 11/03/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Need to show what 4 walls are be removed. 2. Show what the business is and the occupancy because there are no ther permit assoictaed with this address. | |||
| FI1 | HOLD | 11/02/2022 | 11/03/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Need to show what 4 walls are be removed. 2. Show what the business is and the occupancy because there are no other permits assoictaed with this address. 3. Submit a life safety plan showing all fire extinguishers, exit sign locations, travel disatnces. | |||
| MECH | HOLD | 11/02/2022 | 11/04/2022 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide code analysis showing occupangy classification per chapter 3 FBC Building 2020 7Th edition and level of alteration per Chapter 6 FBC Existing Building 2020 7Th edition 2. Provide duct layout showing supply, return, fresh air and exhaust with existing and proposed changes per FBC mechanical 2020 7th edition Further comments could be required after initial comments are reviewed. | |||
| PLUM | COMPLETE | 11/02/2022 | 11/14/2022 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM | |||
| UD1 | COMPLETE | 11/02/2022 | 11/04/2022 |
| Note: Released By: CHRIS JOHNSON - (386)986-2384 - CJOHNSON@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION - COMMERCIAL | ¤60.00 | 02/23/2023 |
| REINSPECTION - COMMERCIAL | ¤60.00 | 02/23/2023 |
| SURCHARGE FS 533.721 | ¤2.00 | 02/20/2023 |
| SURCHARGE - FS 468.631 | ¤2.01 | 02/20/2023 |
| SITE PLAN 30 | ¤30.00 | 02/20/2023 |
| ADJUSTMENT 50% | (¤100.00) | 02/20/2023 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 02/20/2023 |
| INSPECTION COMMERCIAL | ¤60.00 | 02/20/2023 |
| PLAN REVIEW - COMMERCIAL | ¤65.00 | 02/20/2023 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤254.01 |