I want to search for...

Permit #2022110385

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7028-00070-0010
Block: 00070
Subdivision: 2199 - SECTION 28-WYNNFIELD
Job Phone: 321-247-6073
Location Address: 101 PHEASANT DR
Type: SLRE - SOLAR ELECTRIC - PHOTOVOLTAIC
Issue Date: 11/18/2022
NOC: RECORDED
Applicant name: CAMERON CHRISTENSEN
Owner: LIPKA ANTHONY W & HOPE A H&W

Address

101 PHEASANT DRIVE

PALM COAST, FL 32164

Lot: 0010
Contracted Stated Job Value: ¤58,746.00
Job Description: ROOF MOUNTED PV SOLAR PANELS & DERATE 200A METER MAN WITH NEW 175A METER MAIN BREAKER
Type: CN

Contractor

MOMENTUM SOLAR,LLC
Status Location Address Mailing Address State License Number Phone
INACTIVE

8248 PARKLINE BOULEVARD

ORLANDO, FL 32809

STE 100

ORLANDO, FL 32809

CVC57036 (Exp: 08/31/2026) 321-247-6073

Inspection History

Type Request Date Result Inspector
SOLAR ELECTRIC FINAL 03/07/2023 FINAL APPROVED KSANDOE

Review History

Department Status Date In Date Out
ELEC COMPLETE 11/17/2022 11/17/2022
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ELEC HOLD 11/14/2022 11/15/2022
Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code PLAN REVIEW COMMENTS: 1. Submitted electrical calculations show the proposed load as 176 amps. Proposed 175 amp breaker can not be used. NEC 2017 220.
BLD COMPLETE 11/08/2022 11/08/2022
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ELEC HOLD 11/08/2022 11/08/2022
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM If putting in a smaller main breaker you need to submit electric load calcs proving you can do it. NEC 2017 220
ZON COMPLETE 11/08/2022 11/08/2022
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 50% (¤128.63) 11/18/2022
ADMINISTRATIVE RESIDENTIAL ¤30.00 11/18/2022
INSPECTION - RESIDENTIAL ¤162.25 11/18/2022
SOLAR PLAN REVIEW ¤65.00 11/18/2022
SURCHARGE FS 533.721 ¤2.00 11/18/2022
SURCHARGE - FS 468.631 ¤2.00 11/18/2022
Fees Total Due: ¤0.00 Total Paid: ¤132.62