Status: COED

Parcel Id: 07-11-31-7002-00030-0130
Block: 00030
Subdivision: 2218 - SECTION 2-FLORIDA PARK
Job Phone: 386-313-6922
Location Address: 3 FLORIDA PARK DR
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 05/01/2023
NOC: RECORDED
Applicant name: FRANK JOSEPH WHALEN
Owner: JETS DAY CARE INC

Address

P.O. BOX 1255

BUNNELL, FL 32110

Lot: 0130
Contracted Stated Job Value: ¤35,000.00
Job Description: UNIT D - INTERIOR ALTERATION (JETS DAY CARE INC.)
Type: CN

Contractor

EAST COAST BUILDING CORP
Status Location Address State License Number Phone Fax
ACTIVE

321 BRIARWOOD DRIVE

BUNNELL, FL 32110

CGC057860 (Exp: 08/31/2026) 386-313-6922 386-313-6922

Sub Contractors

MICHAEL C PASTERNAK
Status Location Address State License Number Phone Fax
ACTIVE

748 N RIDGEWOOD AVE

ORMOND BEACH, FL 32174

EC13005663 (Exp: 08/31/2026) 386-671-7474 386-671-7670
RICHARD GARY WILSON JR
Status Location Address Mailing Address State License Number Phone
ACTIVE

1504 OLD MOODY BLVD

BUNNELL, FL 32110

UNIT 6

BUNNELL, FL 32110

CAC1817645 (Exp: 08/31/2026) 386-586-6290
SCOTT PATRICK RAYMOND
Status Location Address State License Number
ACTIVE

61 FRENEAU LN

PALM COAST, FL 32137

RF11067787 (Exp: 08/31/2027)

Inspection History

Type Request Date Result Inspector
INSULATION 08/07/2023 APPROVED FWILLIS
BUILDING FINAL 08/07/2023 FINAL APPROVED FWILLIS
FIRE FINAL 08/03/2023 APPROVED RMARTIN
U - UTILITY COMMERCIAL FINAL 08/03/2023 FINAL APPROVED DHANEY
HVAC FINAL 08/01/2023 Disapproved -FEE REQUIRED CPISCITELLI
Note: 1. Breakers in panel need to be labeled. There are 2 AHU and no ODU. 2. AHU heater not marked. Could not verify breaker
HVAC FINAL 08/01/2023 FINAL APPROVED CPISCITELLI
Note: Facetime inspection
PLUMBING FINAL 07/31/2023 APPROVED MGIBSON
Note: 7/24/2023 - PREVIOUS INSPECTION NOTES 1. No hot water. 2. Washing machine stand pipe Install washing maching or cap the standpipe. 3. Kitchen sink drain tee / p-trap cannot be of the flexible type. 7/10/2023 - PREVIOUS INSPECTION NOTES
PLUMBING FINAL 07/24/2023 Disapproved - NO FEE JWALKER
Note: 1. No hot water. 2. Washing machine stand pipe Install washing maching or cap the standpipe. 3. Kitchen sink drain tee / p-trap cannot be of the flexible type. 7/10/2023 - PREVIOUS INSPECTION NOTES
ELECTRIC FINAL 07/24/2023 APPROVED - AS NOTED RMARTIN
Note: check quad outlets in main area on fire final for tamper 7/12/2023 - PREVIOUS INSPECTION NOTES need to frame out above electrical panel, need gfci in attic for ahu, need emergency light in left room
HVAC FINAL 07/12/2023 Disapproved - NO FEE CPISCITELLI
Note: 1. Need to move location of attic access. High votage line runs through center of existing location. 2. Need plywood in front of AHU. 3. Need service oulet 4. Need to soffit cap for bathfan. 5. Need to reseal bottom of several duct connections and bathroom line is kinked 6. Need to install lineset cover over lineset on wall. 7. Need to label breaker panel for AC unit 8. Need to shift ODU toward electrical closet for access and serviceability thru fence.
ELECTRIC 2ND ROUGH 07/12/2023 APPROVED - AS NOTED RMARTIN
Note: need to frame out above electrical panel, need gfci in attic for ahu, need emergency light in left room
ELECTRIC FINAL 07/12/2023 CANCELLED BY APPLICANT RMARTIN
Note: need to frame out above electrical panel, need gfci in attic for ahu, need emergency light in left room
PLUMBING FINAL 07/10/2023 CANCELLED BY APPLICANT MGIBSON
PLUMBING FINAL 07/06/2023 CANCELLED BY APPLICANT WEB
HVAC FINAL 07/06/2023 CANCELLED BY APPLICANT WEB
Note: Inspector Notes from Inspection 3140 1. Need to move location of attic access. High votage line runs through center of existing location. 2. Need to have metal on bottom of return box in ceiling. 3. Need plywood in front of AHU. 4. Need service oulet and light in attic near AHU. 5. Need to vent bathfan. 6. Need to reseal bottom of several duct connections and bathroom line is kinked
HVAC ROUGH 06/16/2023 APPROVED - AS NOTED CPISCITELLI
Note: 1. Need to move location of attic access. High votage line runs through center of existing location. 2. Need to have metal on bottom of return box in ceiling. 3. Need plywood in front of AHU. 4. Need service oulet and light in attic near AHU. 5. Need to vent bathfan. 6. Need to reseal bottom of several duct connections and bathroom line is kinked
MONOLITHIC SLAB 06/16/2023 APPROVED FWILLIS
FRAMING 06/16/2023 APPROVED FWILLIS
PLUMBING 1ST ROUGH 06/07/2023 APPROVED MGIBSON

Review History

Department Status Date In Date Out
MECH COMPLETE 04/18/2023 04/19/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
FI1 COMPLETE 03/24/2023 03/30/2023
Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM
MECH HOLD 03/24/2023 03/27/2023
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 2. Provide Ventilation calculation per Table 403.3.1.1 FBC Mechanical 2020 7Th edition (Second Request) Show calculation formula from Table 403.3.1. Update duct layout and CFM requirements to correspond to formula
BLD COMPLETE 03/24/2023 04/10/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ELEC COMPLETE 03/24/2023 04/03/2023
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
PLUM COMPLETE 03/24/2023 04/10/2023
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM
ELEC HOLD 03/21/2023 03/21/2023
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Corrections to this permit need to be in person as origionally applied for.
MECH HOLD 03/21/2023 03/21/2023
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Corrections to this permit need to be in person as origionally applied for.
FI1 HOLD 03/21/2023 03/21/2023
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM All comments remain unresolved the revised plans were not uploaded. (the energy calcs were uploaded twice with no new plans uploaded. All comments below per the 2020 Florida Fire Prevention Code, 2020 FBC, and or 2020 Existing Building Code Please provide a written response to each comment below in a response letter and provide clouded response changes on plan sheets and add page locations for each response. 1. Please include a Code Analysis utilizing the FBC Existing Building Code 7th edition chapter 7, 8, for the alteration. 2. Please include FFPC 7th edition in the code analysis 3. Please include FBC 7th edition in the code analysis 4. Please include FBC Existing Building Code 7th edition in the code analysis 5. Please note the space will be required to have a fire sprinkler system or exit doors leading directly to a public way from each classroom per FBC 903.2.6 Exception (2). Be advised classroom 2 will be treated as a separate classroom and will drive the need for Sprinklers or an exit door must be added. 6. Please advise if there will be access provided through the current firewall or if access will be through separate exit doors. The Current plan provided shows no access between the two I-4 occupancies. If access will be opened through the Firewall the Details for the opening will need to be uploaded. 7. If the space will have an access from the adjacent occupancy through the firewall, please provide the square footage for the entire building. If no access will be provided thought the firewall please show the square footage for the unit under change of occupancy. 8. Please include a clearly defined description of the work to be performed, the work area, and any existing areas that will not be affected by the changes including fire sprinklers (if any) and or alarm system. 9. Please place a note on the plan indicating separate permits are required for Fire Alarms, also if fire sprinklers will be added, place a similar note for fire sprinklers. 10. Please provide travel distance from the most remote location to the exit 11. Please provide travel distance from the most remote location to the required fire extinguishers per FFPC 1, 13.6.3.2.1.2.2 12. Additional comments are likely after resubmittal.
BLD HOLD 03/21/2023 03/21/2023
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Corrections to this permit need to be in person as origionally applied for.
PLUM HOLD 03/21/2023 03/21/2023
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Corrections to this permit need to be in person as origionally applied for.
BLD HOLD 11/23/2022 12/07/2022
Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code PLAN REVIEW COMMENTS: 1. Provide compliance with Chapter 10 2020 7th Edition Florida Building Existing. Existing unit occupancy is Business and the proposed is Institutional Group I-4. 2. Provide if this will be two separate Day Care Centers or will adjoined. 3. Provide direct Exit from Classroom #2 or provide a fire sprinkler system. 4. Provide how the bathroom complies with Section 806 for accessibility.
DSD COMPLETE 11/23/2022 11/28/2022
Note: Released By: JACQUELINE GONZALEZ - (386)986-3751 - JGONZALEZ@PALMCOASTGOV.COM
ELEC HOLD 11/23/2022 12/05/2022
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. All outlet must be tamper resistant. NEC 2017 406.12 2. Outlets specified in NEC 2017 210.8 (B) need to be GFCI protected. 3 Provide existing electrical layout.
FI1 HOLD 11/23/2022 12/07/2022
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM All comments below per the 2020 Florida Fire Prevention Code, 2020 FBC, and or 2020 Existing Building Code Please provide a written response to each comment below in a response letter and provide clouded response changes on plan sheets and add page locations for each response. 1. Please include a Code Analysis utilizing the FBC Existing Building Code 7th edition chapter 7, 8, for the alteration. 2. Please include FFPC 7th edition in the code analysis 3. Please include FBC 7th edition in the code analysis 4. Please include FBC Existing Building Code 7th edition in the code analysis 5. Please note the space will be required to have a fire sprinkler system or exit doors leading directly to a public way from each classroom per FBC 903.2.6 Exception (2). Be advised classroom 2 will be treated as a separate classroom and will drive the need for Sprinklers or an exit door must be added. 6. Please advise if there will be access provided through the current firewall or if access will be through separate exit doors. The Current plan provided shows no access between the two I-4 occupancies. If access will be opened through the Firewall the Details for the opening will need to be uploaded. 7. If the space will have an access from the adjacent occupancy through the firewall, please provide the square footage for the entire building. If no access will be provided thought the firewall please show the square footage for the unit under change of occupancy. 8. Please include a clearly defined description of the work to be performed, the work area, and any existing areas that will not be affected by the changes including fire sprinklers (if any) and or alarm system. 9. Please place a note on the plan indicating separate permits are required for Fire Alarms, also if fire sprinklers will be added, place a similar note for fire sprinklers. 10. Please provide travel distance from the most remote location to the exit 11. Please provide travel distance from the most remote location to the required fire extinguishers per FFPC 1, 13.6.3.2.1.2.2 12. Additional comments are likely after resubmittal.
MECH HOLD 11/23/2022 12/06/2022
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide Heatload Calculation per C403.2.1 FBC Energy Conservation 2020 7Th edition 2. Provide Ventilation calculation per Table 403.3.1.1 FBC Mechanical 2020 7Th edition 3. Provide existing duct layout showing supply, return, fresh air, exhaust and equipment model numbers. Complete review was not completed. Additional comments may be generated after resubmittal
PLUM HOLD 11/23/2022 12/07/2022
Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code – Plumbing PLAN REVIEW COMMENTS: 1. Per Table 403.1, a shower is required.
UD1 COMPLETE 11/23/2022 11/28/2022
Note: Released By: CHRIS JOHNSON - (386)986-2384 - CJOHNSON@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
CONTRACTOR CHANGE ¤20.00 07/10/2023
CONTRACTOR CHANGE ¤20.00 06/19/2023
CONTRACTOR CHANGE ¤20.00 06/19/2023
SURCHARGE FS 533.721 ¤2.00 05/01/2023
SURCHARGE - FS 468.631 ¤2.01 05/01/2023
SITE PLAN 30 ¤30.00 05/01/2023
ADJUSTMENT 50% (¤100.00) 05/01/2023
ADMINISTRATIVE - COMMERCIAL ¤75.00 05/01/2023
INSPECTION COMMERCIAL ¤60.00 05/01/2023
PLAN REVIEW - COMMERCIAL ¤65.00 05/01/2023
Fees Total Due: ¤0.00 Total Paid: ¤194.01