Permit Details
Status: COED
| Parcel Id: 07-11-31-5112-00000-0050 |
| Total Square Footage: 0 sqft |
| Block: 00000 |
| Subdivision: 1164 - PINE LAKES INDUSTRIAL PARK |
| Job Phone: 386-238-1570 |
| Location Address: 11 COMMERCE BLVD |
| Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION |
| Issue Date: 03/14/2023 |
| NOC: RECORDED |
| Applicant name: GARY LYNN ROBERTS |
| Owner: 11 COMMERCE EQUITIES LLC 11 COMMERCE ROBLES LLC &1 |
|
Address 24 CHURCH STREET MONTCLAIR, NJ 07042 |
|
Address ATTN: SCOTT GLAUBERG MONTCLAIR, NJ 07042 |
| Lot: 0050 |
| Contracted Stated Job Value: ¤240,000.00 |
| Job Description: Unit 6, 7 ,8 Interior Remodel Palm Coast Data |
| Type: CN |
Contractor
COMMERCIAL CONSTRUCTION INC.
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
7 SUNSHINE BLVD ORMOND BEACH, FL 32174 |
CGC059441 (Exp: 08/31/2026) | 386-238-1570 | 386-238-1571 |
Sub Contractors
MICHAEL WAYNE LYNCH
| Status | Location Address | Mailing Address | State License Number | Phone |
| INACTIVE |
512 FENTRESS BLVD DAYTONA BEACH, FL 32114 |
STE I DAYTONA BEACH, FL 32114 |
ER13015626 (Exp: 08/31/2023) | 386-313-1719 |
FREDERICK JOSEPH PREVOST
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
887 BRENTWOOD DRIVE DAYTONA BEACH, FL 0 |
CMC1250152 (Exp: 08/31/2026) | 386-252-7047 | 386-257-7819 |
ISAAC WALTER JOHNSTON
| Status | Location Address | State License Number | Phone |
| ACTIVE |
887 BRENTWOOD DRIVE Daytona Beach, FL 32117 |
CFC023634 (Exp: 08/31/2026) | (386) 252-7047 |
Inspection History
| Type | Request Date | Result | Inspector |
| BUILDING FINAL | 02/15/2024 | FINAL APPROVED | FWILLIS |
| FIRE FINAL | 02/14/2024 | APPROVED | RMARTIN |
| Note: 2/9/2024 - PREVIOUS INSPECTION NOTES EXIT IN HALL BETWEEN 7/8 NOT WORKING AND NEED TO VERIFY EXIT IN SMALL HALL UNIT 8 | |||
| HVAC FINAL | 02/13/2024 | FINAL APPROVED | CPISCITELLI |
| FIREWALL FINAL | 02/12/2024 | APPROVED | FWILLIS |
| MONOLITHIC SLAB | 02/09/2024 | APPROVED | FWILLIS |
| FIRE FINAL | 02/09/2024 | Disapproved -FEE REQUIRED | RMARTIN |
| Note: EXIT IN HALL BETWEEN 7/8 NOT WORKING AND NEED TO VERIFY EXIT IN SMALL HALL UNIT 8 | |||
| INSULATION | 02/09/2024 | APPROVED | FWILLIS |
| ELECTRIC FINAL | 02/08/2024 | APPROVED - AS NOTED | RMARTIN |
| Note: check em light in hall between 7/8 not working and exit light in small hall marked on plan check on fire final | |||
| ABOVE CEILING | 02/07/2024 | APPROVED | RMARTIN |
| Note: 2/5/2024 3:45:54 PM- PREVIOUS INSPECTION NOTES | |||
| ABOVE CEILING | 02/06/2024 | CANCELLED BY APPLICANT | CPISCITELLI |
| FIREWALL PENETRATIONS | 02/05/2024 | APPROVED | FWILLIS |
| HVAC ROUGH | 02/02/2024 | CANCELLED BY INSPECTOR | CPISCITELLI |
| Note: 1/10/2024 - PREVIOUS INSPECTION NOTES Inspected metal duct to wrap and flex duct and trunk line | |||
| BUILDING OTHER | 01/25/2024 | APPROVED | FWILLIS |
| FIREWALL PENETRATIONS | 01/25/2024 | APPROVED | FWILLIS |
| FIREWALL PENETRATIONS | 01/24/2024 | APPROVED | FWILLIS |
| BUILDING OTHER | 01/24/2024 | CANCELLED BY INSPECTOR | FWILLIS |
| HVAC OTHER | 01/23/2024 | APPROVED | CPISCITELLI |
| Note: Inspected fire dampers in fire riser room | |||
| FIREWALL NAILING | 01/19/2024 | APPROVED | FWILLIS |
| FIREWALL PENETRATIONS | 01/17/2024 | APPROVED | FWILLIS |
| FIREWALL NAILING | 01/16/2024 | APPROVED | FWILLIS |
| Note: 7/10/2023 - PREVIOUS INSPECTION NOTES WAITING FOR DAMPERS FOR FINAL INSPECTION. | |||
| HVAC ROUGH | 01/10/2024 | PARTIALLY APPROVED | CPISCITELLI |
| Note: Inspected metal duct to wrap and flex duct and trunk line | |||
| ELECTRIC 2ND ROUGH | 01/05/2024 | PARTIALLY APPROVED | RMARTIN |
| Note: walls in front room/riser room | |||
| FIREWALL FRAMING | 01/05/2024 | APPROVED | FWILLIS |
| Note: PENDING ELECTRICAL INSPECTION. | |||
| FRAMING | 10/09/2023 | APPROVED | FWILLIS |
| U - UTILITY COMMERCIAL FINAL | 10/06/2023 | FINAL APPROVED | DHANEY |
| BUILDING FINAL | 10/06/2023 | APPROVED | FWILLIS |
| Note: UNIT #5 ONLY | |||
| FIRE FINAL | 10/06/2023 | CANCELLED BY APPLICANT | CPISCITELLI |
| ABOVE CEILING | 09/21/2023 | APPROVED | RMARTIN |
| Note: 6/15/2023 - PREVIOUS INSPECTION NOTES 6/15/23 call back when grid is installed 6/13/2023 - PREVIOUS INSPECTION NOTES | |||
| FIREWALL FINAL | 09/08/2023 | APPROVED | FWILLIS |
| FIREWALL NAILING | 09/06/2023 | APPROVED | FWILLIS |
| Note: 6/30/2023 - PREVIOUS INSPECTION NOTES PARTIAL 2ND LAYER AT AREA 1. 9/6/23 - 2ND LAYER IN HALLWAYS, RISER ROOM AND ENTRY. | |||
| FIREWALL NAILING | 09/01/2023 | APPROVED | FWILLIS |
| FIREWALL FRAMING | 08/31/2023 | APPROVED | FWILLIS |
| HVAC ROUGH | 08/25/2023 | APPROVED | CPISCITELLI |
| Note: 8/24/2023 - PREVIOUS INSPECTION NOTES Inspected partially fire dampers 6/2/2023 - PREVIOUS INSPECTION NOTES Inspected above hall for duct only. Did not inspect dampers and drops. Also need to inspect AHU when running and finished | |||
| HVAC ROUGH | 08/24/2023 | PARTIALLY APPROVED | CPISCITELLI |
| Note: Inspected partially fire dampers 6/2/2023 - PREVIOUS INSPECTION NOTES Inspected above hall for duct only. Did not inspect dampers and drops. Also need to inspect AHU when running and finished | |||
| FLOOR/WALL PENETRATION | 07/12/2023 | PARTIALLY APPROVED | LMILLER |
| Note: Partial for corridoors 6, 7, and 8 tops of walls last 1 foot only, Common loading room for 6,7, and 8 roof deck area only, Unit 6 top of north and west walls only' need to seal open wall penitrations by hvac final on room 6 nrth wall | |||
| FIREWALL NAILING | 07/10/2023 | PARTIALLY APPROVED | FWILLIS |
| Note: WAITING FOR DAMPERS FOR FINAL INSPECTION. | |||
| FIREWALL NAILING | 06/30/2023 | PARTIALLY APPROVED | FWILLIS |
| Note: PARTIAL 2ND LAYER AT AREA 1. | |||
| FIREWALL NAILING | 06/20/2023 | APPROVED | FWILLIS |
| Note: 6/9/2023 - PREVIOUS INSPECTION NOTES PARTIAL SCREW EXTERIOR WALL, HIGHLIGHTED ON APPROVED PLANS. (6,7,8) 6/20/23 - PARTIAL INTERIOR FIREWALL SCREW. | |||
| ELECTRIC 2ND ROUGH | 06/15/2023 | APPROVED | RMARTIN |
| ABOVE CEILING | 06/15/2023 | CANCELLED BY APPLICANT | RMARTIN |
| Note: 6/15/23 call back when grid is installed 6/13/2023 - PREVIOUS INSPECTION NOTES | |||
| ABOVE CEILING | 06/13/2023 | CANCELLED BY APPLICANT | RMARTIN |
| FIREWALL NAILING | 06/09/2023 | PARTIALLY APPROVED | FWILLIS |
| Note: PARTIAL SCREW EXTERIOR WALL, HIGHLIGHTED ON APPROVED PLANS. (6,7,8) | |||
| HVAC ROUGH | 06/02/2023 | PARTIALLY APPROVED | CPISCITELLI |
| Note: Inspected above hall for duct only. Did not inspect dampers and drops. Also need to inspect AHU when running and finished | |||
| FRAMING | 06/01/2023 | APPROVED | FWILLIS |
| Note: Corridors and doorways. Two doors are pending revision for being moved. Marked on plans. suggested that he contact Chris for all HVAC questions before closing the ceiling. |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 11/22/2023 | 11/22/2023 |
| Note: Released By: JACQUELINE GONZALEZ - (386)986-3751 - JGONZALEZ@PALMCOASTGOV.COM | |||
| DSD | COMPLETE | 11/22/2023 | 11/22/2023 |
| Note: Released By: JACQUELINE GONZALEZ - (386)986-3751 - JGONZALEZ@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 11/22/2023 | 11/30/2023 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| FI1 | COMPLETE | 11/22/2023 | 12/04/2023 |
| Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 11/22/2023 | 11/30/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| PLUM | COMPLETE | 11/22/2023 | 12/08/2023 |
| Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM | |||
| UD1 | COMPLETE | 11/22/2023 | 12/06/2023 |
| Note: Released By: ALEXANDER BLAKE - - ABLAKE@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 11/22/2023 | 12/08/2023 |
| Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 02/27/2023 | 03/13/2023 |
| Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 02/27/2023 | 02/27/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| FI1 | COMPLETE | 02/16/2023 | 02/22/2023 |
| Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM | |||
| MECH | HOLD | 02/16/2023 | 02/23/2023 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Page M101 is cut off at the top. Upload new M101 | |||
| BLD | HOLD | 02/16/2023 | 02/16/2023 |
| Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code REVIEW COMMENTS: 1. A revision to sheet X2 and X3 is required. Revise to show the bathroom renovations. 2. Various sheets reference a future UL rated wall. Will be constructed under this application? If not, remove the reference to the proposed wall and separate application will be required when the wall is to be constructed. | |||
| ELEC | COMPLETE | 02/16/2023 | 02/24/2023 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 12/22/2022 | 12/22/2022 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| BLD | HOLD | 12/12/2022 | 12/27/2022 |
| Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code REVIEW COMMENTS: 1. A revision to sheet X2 and X3 is required. Revise to show the bathroom renovations. 2. Various sheets reference a future UL rated wall. Will be constructed under this application? If not, remove the reference to the proposed wall and separate application will be required when the wall is to be constructed. | |||
| DSD | COMPLETE | 12/12/2022 | 12/21/2022 |
| Note: Released By: JACQUELINE GONZALEZ - (386)986-3751 - JGONZALEZ@PALMCOASTGOV.COM multitenant use is permit per deputy chief community development officer. | |||
| ELEC | HOLD | 12/12/2022 | 12/21/2022 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Automatic lighting controls are not permitted where electrical equipment is placed. NEC 2017 110.26 (D) 2. Need emergency lighting where electrical equipment is located. NEC 2017 110.26(D) | |||
| FI1 | HOLD | 12/12/2022 | 12/16/2022 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Need to show Fire extinguishers per Sheet A2 (Life Safety Plans - unit 8) Per FBC 2017 Section 906, and FFPC 1, section 13.6, and Table 13.6.1.2 | |||
| MECH | HOLD | 12/12/2022 | 12/22/2022 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Mechanical plans need to be digitally signed, sealed and verifable. F.S.471.025 2. Provide Ventilation calculation for each area 6,7, and 8 per Table 403.3.1.1 FBC Mechanical 2020 7Th edition 3. Provide Heatload Calculation for each area 6,7, and 8 per C403.2.1 FBC Energy Conservation 2020 7Th edition 4. Provide details on existing equipment for all areas on schedule and what is new. Provide condensing equpment details also. 5. Provide duct layout for all areas showing supply, return, fresh air and exhaust. 6. Provide thermostat location for each area. | |||
| PLUM | COMPLETE | 12/12/2022 | 12/27/2022 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM | |||
| UD1 | COMPLETE | 12/12/2022 | 12/12/2022 |
| Note: Released By: CHRIS JOHNSON - (386)986-2384 - CJOHNSON@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION - COMMERCIAL | ¤60.00 | 02/14/2024 |
| SURCHARGE FS 533.721 | ¤10.72 | 03/14/2023 |
| SURCHARGE - FS 468.631 | ¤16.09 | 03/14/2023 |
| SITE PLAN 30 | ¤30.00 | 03/14/2023 |
| ADJUSTMENT 50% | (¤1,015.50) | 03/14/2023 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 03/14/2023 |
| INSPECTION COMMERCIAL | ¤1,680.00 | 03/14/2023 |
| PLAN REVIEW - COMMERCIAL | ¤276.00 | 03/14/2023 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤1,132.31 |