Permit #2022120995
Permit Details
Status: COED
| Parcel Id: 07-11-31-7030-00730-0120 |
| CONDITIONED SPACE: 1215 sqft |
| GARAGE: 396 sqft |
| Total Square Footage: 1611 sqft |
| Block: 00730 |
| Subdivision: 2154 - SECTION 30-ROYAL PALMS |
| Job Phone: 407-432-2344 |
| Location Address: 32 RAMBLING LN |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 01/23/2023 |
| NOC: RECORDED |
| Applicant name: WADE GILMER JURNEY JR |
| Owner: NATIONAL HOME CORP |
|
Address 1080 HOLCOMB BRIDGE 100-330 ROSWELL , GA 30076 |
| Lot: 0120 |
| Contracted Stated Job Value: ¤198,291.00 |
| Job Description: Single Family Residence |
| Type: CN |
Contractor
NATIONAL HOME CORPORATION
| Status | Location Address | Mailing Address | State License Number | Phone |
| INACTIVE |
1080 HOLCOMB BRIDGE ROAD , |
BLDG 100 - 330 ROSWELL , GA 30076 |
CBC1257700 (Exp: 08/31/2026) | 471-817-1259 |
Sub Contractors
RANDALL SCOTT ROSENFELD
| Status | Location Address | State License Number | Phone |
| ACTIVE |
234 N WHITNEY ST PALM COAST, FL 32084 |
CAC1816641 (Exp: 08/31/2026) | 904-599-0082 |
DUSTIN L ESTEP
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
2041 N HIAWASSEE RD APOPKA, FL 32703 |
CCC1330971 (Exp: 08/31/2026) | 407-702-0206 | 352-988-6629 |
JASON PATRICK RIBOCK
| Status | Location Address | State License Number | Phone |
| INACTIVE |
620 E PINE ST , 0 |
ES12001313 (Exp: 08/31/2026) | 407-625-0257 |
PAUL ERIC FORSTER
| Status | Location Address | State License Number | Phone |
| ACTIVE |
6114 GOODMAN RD JACKSONVILLE, FL 32244 |
CFC1429261 (Exp: 08/31/2026) | 904-647-1820 |
Inspection History
| Type | Request Date | Result | Inspector |
| GRAVITY SEWER TEST | 11/30/2023 | APPROVED | MGIBSON |
| Note: Inspector Notes from Inspection 2060 3/17/2023 - PREVIOUS INSPECTION NOTES Please have a full set of approved prints onsite for inspection. The prints in the job box are not an approved set and are prints from 5 zollinger ln. REMOVE ALL COQUINA STONE FROM SLAB BEFORE BACKFILLING | |||
| U-CROSS CONNECTION | 11/30/2023 | APPROVED - AS NOTED | JHARDING |
| Note: No irrigation,no cross connections. | |||
| U - SEWER TIE IN | 11/30/2023 | APPROVED | MGIBSON |
| Note: Inspector Notes from Inspection 2060 3/17/2023 - PREVIOUS INSPECTION NOTES Please have a full set of approved prints onsite for inspection. The prints in the job box are not an approved set and are prints from 5 zollinger ln. REMOVE ALL COQUINA STONE FROM SLAB BEFORE BACKFILLING | |||
| BLD - BUILDING FINAL | 11/29/2023 | Disapproved -FEE REQUIRED | JWALKER |
| Note: 11/29/23 Items listed below have not been corrected. 11/28/2023 - PREVIOUS INSPECTION NOTES 11/28/23 1. Right side roof has a boot flashing installed where the old electrical mast was installed. Boot will need to be removed and shingles installed. 2. The vent soffit above the meter can has been torn out. 3. Termite cert not posted. 11/27/2023 - PREVIOUS INSPECTION NOTES 1. The exterior outlet under the meter can needs to be of the weather resistant type. 2. Missing termite cert. 3. Heat appliance label not affixed to the AHU. Check for correct circuit breaker size. 4. Seal the garage wall and ceiling above the electical panel. 5. Hot water not working possibly due to breaker not being on. | |||
| BLD - BUILDING FINAL | 11/29/2023 | FINAL APPROVED | JWALKER |
| Note: 11/29/2023 - PREVIOUS INSPECTION NOTES 11/29/23 Items listed below have not been corrected. 11/28/2023 - PREVIOUS INSPECTION NOTES 11/28/23 1. Right side roof has a boot flashing installed where the old electrical mast was installed. Boot will need to be removed and shingles installed. 2. The vent soffit above the meter can has been torn out. 3. Termite cert not posted. 11/27/2023 - PREVIOUS INSPECTION NOTES 1. The exterior outlet under the meter can needs to be of the weather resistant type. 2. Missing termite cert. 3. Heat appliance label not affixed to the AHU. Check for correct circuit breaker size. 4. Seal the garage wall and ceiling above the electical panel. 5. Hot water not working possibly due to breaker not being on. | |||
| BLD - BUILDING FINAL | 11/28/2023 | Disapproved - NO FEE | JWALKER |
| Note: 11/28/23 1. Right side roof has a boot flashing installed where the old electrical mast was installed. Boot will need to be removed and shingles installed. 2. The vent soffit above the meter can has been torn out. 3. Termite cert not posted. Added not the boot flashing at the newly installed electrical mast is not installed properly. 11/27/2023 - PREVIOUS INSPECTION NOTES 1. The exterior outlet under the meter can needs to be of the weather resistant type. 2. Missing termite cert. 3. Heat appliance label not affixed to the AHU. Check for correct circuit breaker size. 4. Seal the garage wall and ceiling above the electical panel. 5. Hot water not working possibly due to breaker not being on. | |||
| BLD - BUILDING FINAL | 11/27/2023 | Disapproved - NO FEE | JWALKER |
| Note: 1. The exterior outlet under the meter can needs to be of the weather resistant type. 2. Missing termite cert. 3. Heat appliance label not affixed to the AHU. Check for correct circuit breaker size. 4. Seal the garage wall and ceiling above the electical panel. 5. Hot water not working possibly due to breaker not being on. | |||
| ROW - FINAL APRON (AFTER POUR) | 11/22/2023 | APPROVED | PFLANAGAN |
| Note: At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. ---------------------------------------------------------------- 11/15/2023 - PREVIOUS INSPECTION NOTES 1) NEED TO HAVE ROAD REPAIR DONE WITH HOT PATCH. 2) NEED TO HAVE SAW CUTS IN THE DRIVEWAY . -------------------------------------------------------------------------- Inspector Notes from Inspection 9465 11/14/23 DRAINAGE WILL WORK AS INDICATED IN SURVEY. At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. 11/13/2023 - PREVIOUS INSPECTION NOTES THIS INSPECTION IS DONE AFTER THE FINAL SURVEY IS PASSED | |||
| U -UTILITY RESIDENTIAL FINAL | 11/22/2023 | FINAL APPROVED | DHANEY |
| Note: 11/17/2023 - PREVIOUS INSPECTION NOTES sewer C/Opipes still need lowering-no change 11/15/2023 - PREVIOUS INSPECTION NOTES sewer clean out pipes need lowering as well 11/15/2023 - PREVIOUS INSPECTION NOTES pep tank missing pumps-utility informed | |||
| U -UTILITY RESIDENTIAL FINAL | 11/17/2023 | Disapproved -FEE REQUIRED | LFITZGERALD |
| Note: sewer C/Opipes still need lowering-no change 11/15/2023 - PREVIOUS INSPECTION NOTES sewer clean out pipes need lowering as well 11/15/2023 - PREVIOUS INSPECTION NOTES pep tank missing pumps-utility informed | |||
| ROW - STORMWATER FINAL | 11/17/2023 | APPROVED | PFLANAGAN |
| Note: At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. ------------------------------------------------------------------------------------------- 11/15/2023 - PREVIOUS INSPECTION NOTES 1) NEED TO CLEAN ALL DIRT AND OVER POURED CONCRETE OUT OF THE CULVERT PIPE 2) NEED TO REMOVE ALL PALLETS FROM THE LOT AND THE VACANT ACCROSSED THE STREET 3) NEED TO REMOVE ALL LEFT OVER SOD FROM VACANT LOT ACCROSSED THE STREET 4) NEED TO PICK UP ALL TRASH AND CONSTRUCTION DEBRIS FROM VACANTS ACCROSSED THE STREET | |||
| U -UTILITY RESIDENTIAL FINAL | 11/15/2023 | Disapproved - NO FEE | LFITZGERALD |
| Note: pep tank missing pumps-utility informed | |||
| U -UTILITY RESIDENTIAL FINAL | 11/15/2023 | Disapproved -FEE REQUIRED | LFITZGERALD |
| Note: sewer clean out pipes need lowering as well 11/15/2023 - PREVIOUS INSPECTION NOTES pep tank missing pumps-utility informed | |||
| ROW - FINAL APRON (AFTER POUR) | 11/15/2023 | Disapproved -FEE REQUIRED | PFLANAGAN |
| Note: 1) NEED TO HAVE ROAD REPAIR DONE WITH HOT PATCH. 2) NEED TO HAVE SAW CUTS IN THE DRIVEWAY . -------------------------------------------------------------------------- Inspector Notes from Inspection 9465 11/14/23 DRAINAGE WILL WORK AS INDICATED IN SURVEY. At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. 11/13/2023 - PREVIOUS INSPECTION NOTES THIS INSPECTION IS DONE AFTER THE FINAL SURVEY IS PASSED | |||
| ROW - STORMWATER FINAL | 11/15/2023 | Disapproved -FEE REQUIRED | PFLANAGAN |
| Note: 1) NEED TO CLEAN ALL DIRT AND OVER POURED CONCRETE OUT OF THE CULVERT PIPE 2) NEED TO REMOVE ALL PALLETS FROM THE LOT AND THE VACANT ACCROSSED THE STREET 3) NEED TO REMOVE ALL LEFT OVER SOD FROM VACANT LOT ACCROSSED THE STREET 4) NEED TO PICK UP ALL TRASH AND CONSTRUCTION DEBRIS FROM VACANTS ACCROSSED THE STREET | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 11/14/2023 | APPROVED - AS NOTED | FSLADISH |
| Note: 11/14/23 DRAINAGE WILL WORK AS INDICATED IN SURVEY. At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. 11/13/2023 - PREVIOUS INSPECTION NOTES THIS INSPECTION IS DONE AFTER THE FINAL SURVEY IS PASSED | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 11/14/2023 | APPROVED | FSLADISH |
| ROW FIELD SURVEY /GRADING CERTIFICATION | 11/13/2023 | Disapproved - NO FEE | PFLANAGAN |
| Note: THIS INSPECTION IS DONE AFTER THE FINAL SURVEY IS PASSED | |||
| ROW- PRE-APRON (PRE-POUR) | 09/01/2023 | APPROVED | FSLADISH |
| Note: 09/01/23 PIPE IS GOOD. READY TO POUR AT THE TIME OF THIS INSPECTION. At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. This includes but is not limited to, the Culvert Pipe Elevation from the time of the inspection approval to the concrete pour. AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS BEFORE POURING. MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL 8/31/2023 - PREIOUS INSPECTION NOTES 8/31/23DUE TO HURRICANE IDALIA, ALL STORMWATER INSPECTIONS IN THE CITY OF PALM COAST ARE CANCELLED UNTIL FRIDAY, SEPTEMBER 1, 2023. BUILDERS SHOULD RESCHEDULE THE INSPECTIONS FOR NORMAL OPERATIONS ON FRIDAY SEPTEMBER 1, 2023. THANK YOU. | |||
| PEP TANK INSTALLATION REQUEST | 08/31/2023 | APPROVED | CBOWERMASTER |
| ROW- PRE-APRON (PRE-POUR) | 08/31/2023 | Disapproved - NO FEE | GBERTOLA |
| Note: 8/31/23DUE TO HURRICANE IDALIA, ALL STORMWATER INSPECTIONS IN THE CITY OF PALM COAST ARE CANCELLED UNTIL FRIDAY, SEPTEMBER 1, 2023. BUILDERS SHOULD RESCHEDULE THE INSPECTIONS FOR NORMAL OPERATIONS ON FRIDAY SEPTEMBER 1, 2023. THANK YOU. | |||
| ELECTRIC - EARLY POWER | 08/21/2023 | APPROVED | JWALKER |
| INSULATION | 07/05/2023 | APPROVED | RSIMS |
| Note: 6/29/2023 - PREVIOUS INSPECTION NOTES 6/29/23 Below listed corretions have not been made. PLEASE do not call for reinspection without first checking the job site Inspector Notes from Inspection 2420 6/23/23 Water distribution still no pressure. Approved duct layout still not onsited. Please have above listed corrected at insulation inspection to avoid fees and delays. 5/25/2023 - PREVIOUS INSPECTION NOTES 5/25/23 1. The smoke detector outlet in the hall way is to be a minimum of 3' from the HVAC supply register. 2. Please have the approved energy calculations with the approved duct layout onsite 3. No pressure on the water distrubution pipes. 4. Flex duct is to be supported a minimum of 4' o.c.. 5. The spray foam used to seal the annualar spaces at the top plates is to be of the fire resitant type. Remove the yellow foam or provide the can with the UL listing. 6. Check for AAV at final build in the rear right side bath. 7. The two item listed below have not been corrected from the previous inspection. 5/9/23 1. X- bracing and lateral bracing shown of page D2. Detail TBO5 need to be installed. 2. Trusses V1,2, and 3 need to be anchored down at both ends. Rear of truss good. Front sides need anchors installed. Check for corrections at all rough. | |||
| INSULATION | 06/29/2023 | Disapproved -FEE REQUIRED | JWALKER |
| Note: 6/29/23 Below listed corretions have not been made. PLEASE do not call for reinspection without first checking the job site Inspector Notes from Inspection 2420 6/23/23 Water distribution still no pressure. Approved duct layout still not onsited. Please have above listed corrected at insulation inspection to avoid fees and delays. 5/25/2023 - PREVIOUS INSPECTION NOTES 5/25/23 1. The smoke detector outlet in the hall way is to be a minimum of 3' from the HVAC supply register. 2. Please have the approved energy calculations with the approved duct layout onsite 3. No pressure on the water distrubution pipes. 4. Flex duct is to be supported a minimum of 4' o.c.. 5. The spray foam used to seal the annualar spaces at the top plates is to be of the fire resitant type. Remove the yellow foam or provide the can with the UL listing. 6. Check for AAV at final build in the rear right side bath. 7. The two item listed below have not been corrected from the previous inspection. 5/9/23 1. X- bracing and lateral bracing shown of page D2. Detail TBO5 need to be installed. 2. Trusses V1,2, and 3 need to be anchored down at both ends. Rear of truss good. Front sides need anchors installed. Check for corrections at all rough. | |||
| ALL ROUGH | 06/23/2023 | APPROVED - AS NOTED | JWALKER |
| Note: 6/23/23 Water distribution still no pressure. Approved duct layout still not onsited. Please have above listed corrected at insulation inspection to avoid fees and delays. 5/25/2023 - PREVIOUS INSPECTION NOTES 5/25/23 1. The smoke detector outlet in the hall way is to be a minimum of 3' from the HVAC supply register. 2. Please have the approved energy calculations with the approved duct layout onsite 3. No pressure on the water distrubution pipes. 4. Flex duct is to be supported a minimum of 4' o.c.. 5. The spray foam used to seal the annualar spaces at the top plates is to be of the fire resitant type. Remove the yellow foam or provide the can with the UL listing. 6. Check for AAV at final build in the rear right side bath. 7. The two item listed below have not been corrected from the previous inspection. 5/9/23 1. X- bracing and lateral bracing shown of page D2. Detail TBO5 need to be installed. 2. Trusses V1,2, and 3 need to be anchored down at both ends. Rear of truss good. Front sides need anchors installed. Check for corrections at all rough. | |||
| LATH/BRICK/ WATER BARRIER | 06/05/2023 | APPROVED | JWALKER |
| ALL ROUGH | 05/25/2023 | Disapproved -FEE REQUIRED | JWALKER |
| Note: 5/25/23 1. The smoke detector outlet in the hall way is to be a minimum of 3' from the HVAC supply register. 2. Please have the approved energy calculations with the approved duct layout onsite 3. No pressure on the water distrubution pipes. 4. Flex duct is to be supported a minimum of 4' o.c.. 5. The spray foam used to seal the annualar spaces at the top plates is to be of the fire resitant type. Remove the yellow foam or provide the can with the UL listing. 6. Check for AAV at final build in the rear right side bath. 7. The two item listed below have not been corrected from the previous inspection. 5/9/23 1. X- bracing and lateral bracing shown of page D2. Detail TBO5 need to be installed. 2. Trusses V1,2, and 3 need to be anchored down at both ends. Rear of truss good. Front sides need anchors installed. Check for corrections at all rough. | |||
| ALL ROUGH | 05/23/2023 | CANCELLED BY APPLICANT | WEB |
| ROOF VALLEY & METAL | 05/11/2023 | APPROVED | JWALKER |
| Note: Inspector Notes from Inspection 2460 5/9/23 1. X- bracing and lateral bracing shown of page D2. Detail TBO5 need to be installed. 2. Trusses V1,2, and 3 need to be anchored down at both ends. Rear of truss good. Front sides need anchors installed. Check for corrections at all rough. 5/5/2023 - PREVIOUS INSPECTION NOTES 1. Please have a full set of approved plans onsite for all inspections. Prints in the job box are not the approved set. 2. Walked roof left side nails have been counter sunk too deep. Renail and leave underlayment off for reinspection. 3. Two down cells left side of the garage are not filled properly. | |||
| ROOF SHEATHING | 05/09/2023 | APPROVED | JWALKER |
| Note: 5/5/2023 - PREVIOUS INSPECTION NOTES Roof sheating at left side roof nails have been sunk too deep into sheating and needs to be renailed. Leave underlayment off the roof for reinspection. NOTE TO THE CONTRACTOR A SEPARATE ROOF SHEATING INSPECTION IS NOT NEEDED, ROOF SHEATING IS CHECKED AT ROOF BRACE INSPECTION. | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 05/09/2023 | APPROVED - AS NOTED | JWALKER |
| Note: 5/9/23 1. X- bracing and lateral bracing shown of page D2. Detail TBO5 need to be installed. 2. Trusses V1,2, and 3 need to be anchored down at both ends. Rear of truss good. Front sides need anchors installed. Check for corrections at all rough. 5/5/2023 - PREVIOUS INSPECTION NOTES 1. Please have a full set of approved plans onsite for all inspections. Prints in the job box are not the approved set. 2. Walked roof left side nails have been counter sunk too deep. Renail and leave underlayment off for reinspection. 3. Two down cells left side of the garage are not filled properly. | |||
| ROOF SHEATHING | 05/05/2023 | Disapproved - NO FEE | JWALKER |
| Note: Roof sheating at left side roof nails have been sunk too deep into sheating and needs to be renailed. Leave underlayment off the roof for reinspection. NOTE TO THE CONTRACTOR A SEPARATE ROOF SHEATING INSPECTION IS NOT NEEDED, ROOF SHEATING IS CHECKED AT ROOF BRACE INSPECTION. | |||
| WALL SHEATHING | 05/05/2023 | APPROVED | JWALKER |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 05/05/2023 | Disapproved -FEE REQUIRED | JWALKER |
| Note: 1. Please have a full set of approved plans onsite for all inspections. Prints in the job box are not the approved set. 2. Walked roof left side nails have been counter sunk too deep. Renail and leave underlayment off for reinspection. 3. Two down cells left side of the garage are not filled properly. | |||
| FOUND SURVEY APPROVED (OFFICE) | 05/04/2023 | APPROVED | TBAKER |
| TIE BEAM / LINTEL | 04/12/2023 | APPROVED | KSANDOE |
| MONOLITHIC SLAB | 03/30/2023 | APPROVED | JWALKER |
| Note: 3/29/2023 - PREVIOUS INSPECTION NOTES Slab is to be a minimum of 4" see note 2 on page S 1.0 of the prints. Test lines are in place. Remove excess soil and tamp. Please reinstall test lines for reinspection. | |||
| MONOLITHIC SLAB | 03/29/2023 | Disapproved - NO FEE | JWALKER |
| Note: Slab is to be a minimum of 4" see note 2 on page S 1.0 of the prints. Test lines are in place. Remove excess soil and tamp. Please reinstall test lines for reinspection. | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 03/21/2023 | APPROVED - AS NOTED | MGIBSON |
| Note: 3/17/2023 - PREVIOUS INSPECTION NOTES Please have a full set of approved prints onsite for inspection. The prints in the job box are not an approved set and are prints from 5 zollinger ln. REMOVE ALL COQUINA STONE FROM SLAB BEFORE BACKFILLING | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 03/17/2023 | Disapproved -FEE REQUIRED | JWALKER |
| Note: Please have a full set of approved prints onsite for inspection. The prints in the job box are not an approved set and are prints from 5 zollinger ln. | |||
| WATER METER INSTALLATION REQUEST | 03/16/2023 | APPROVED | CSTONE |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 06/20/2023 | 06/23/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| ENGIN1 | COMPLETE | 05/03/2023 | 05/04/2023 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 05/03/2023 | 05/03/2023 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 02/08/2023 | 02/09/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| MECH | HOLD | 02/02/2023 | 02/03/2023 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Duct layout needs to be signed by the AC contractor per 107.1 FBC Residential 2020 7th Edition | |||
| MECH | COMPLETE | 01/06/2023 | 01/06/2023 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 01/06/2023 | 01/06/2023 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| ZON | HOLD | 12/28/2022 | 12/28/2022 |
| Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Please provide width of front entry walkway on site plan/survey AC screening should be 7 gallon Please provide sod type and if irrigation will be installed Please choose Shrubs for the foundation plantings that will be toloerant in our area this shrub Arboricola is also known as Dwarf Schefflera and is on the non credit planting list. | |||
| SWALE | COMPLETE | 12/28/2022 | 04/10/2023 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 12/27/2022 | 12/28/2022 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM | |||
| CUSVC | COMPLETE | 12/27/2022 | 12/29/2022 |
| Note: Released By: HALEIGH HAND - - | |||
| ELEC | COMPLETE | 12/27/2022 | 12/28/2022 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ENGIN1 | COMPLETE | 12/27/2022 | 12/28/2022 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| LOCATE | COMPLETE | 12/27/2022 | 12/28/2022 |
| Note: Released By: CANDACE STONE - - CSTONE@PALMCOASTGOV.COM | |||
| MECH | HOLD | 12/27/2022 | 12/28/2022 |
| Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code – Plumbing REVIEW COMMENTS: 1. Design location on Energy Forms is to be Daytona Beach. 2. Form 405 is to be signed by Owner/Agent | |||
| SW1 | COMPLETE | 12/27/2022 | 01/05/2023 |
| Note: Released By: PARREN FLANAGAN - (386)986-2392 - PFLANAGAN@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| SW ENG REINSPECTION 20 | ¤20.00 | 11/29/2023 |
| SW ENG REINSPECTION 20 | ¤20.00 | 11/29/2023 |
| REINSPECTION FEE | ¤40.00 | 11/29/2023 |
| REINSPECTION FEE | ¤40.00 | 11/29/2023 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 11/29/2023 |
| PLAN REVIEW - REVISION | ¤32.50 | 07/17/2023 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 07/17/2023 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 07/17/2023 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 07/17/2023 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 04/13/2023 |
| CONTRACTOR CHANGE | ¤20.00 | 04/13/2023 |
| PLAN REVIEW - REVISION | ¤32.50 | 04/13/2023 |
| CONNECTION FEES | ¤1,166.26 | 01/23/2023 |
| SURCHARGE FS 533.721 | ¤2.47 | 01/23/2023 |
| SURCHARGE - FS 468.631 | ¤3.71 | 01/23/2023 |
| SW ENG - FOUNDATION SURVEY | ¤20.00 | 01/23/2023 |
| SW ENG INSPECTION 80 | ¤80.00 | 01/23/2023 |
| SW ENG PRE APRON | ¤30.00 | 01/23/2023 |
| SW ENG - REVIEW 20 | ¤20.00 | 01/23/2023 |
| SW ENG RES REVIEW 200 | ¤200.00 | 01/23/2023 |
| TRANS IMPACT FEE ADMIN | ¤52.92 | 01/23/2023 |
| TRANS IMPACT FEE ADMIN | (¤52.92) | 01/23/2023 |
| SEWER CREDIT | (¤1,147.00) | 01/23/2023 |
| SEWER INSPECTION | ¤25.00 | 01/23/2023 |
| SEWER CAPITAL FACILITY | ¤5,344.82 | 01/23/2023 |
| WATER CAPITAL FACILITY FEE | ¤3,923.88 | 01/23/2023 |
| SITE PLAN 30 | ¤30.00 | 01/23/2023 |
| FIRE IMPACT FEE ADMIN | ¤12.62 | 01/23/2023 |
| FIRE IMPACT FEE ADMIN | (¤12.62) | 01/23/2023 |
| FC IMPACT FEE EMS | ¤62.00 | 01/23/2023 |
| IMPACT FEE FIRE | ¤420.52 | 01/23/2023 |
| FC IMPACT FEE LAW ENFORCEMENT | ¤218.00 | 01/23/2023 |
| FC IMPACT FEE LIBRARY | ¤268.00 | 01/23/2023 |
| IMPACT FEE PARKS | ¤1,769.15 | 01/23/2023 |
| IMPACT FEE SCHOOL | ¤5,450.00 | 01/23/2023 |
| IMPACT FEE TRANSPORTATION | ¤1,764.00 | 01/23/2023 |
| WATER -IRRIGATION INSPECTION | ¤25.00 | 01/23/2023 |
| PARKS IMPACT FEE ADMIN | ¤53.07 | 01/23/2023 |
| PARKS IMPACT FEE ADMIN | (¤53.07) | 01/23/2023 |
| WATER- TURN ON | ¤25.00 | 01/23/2023 |
| ADJUSTMENT 50% | (¤366.24) | 01/23/2023 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 01/23/2023 |
| INSPECTION - RESIDENTIAL | ¤547.25 | 01/23/2023 |
| PLAN REVIEW - RESIDENTIAL | ¤155.22 | 01/23/2023 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤20,472.04 |