Permit #2023010410

Permit Details

Status: FINAL

Parcel Id: 38-11-31-1915-000B0-1140
Total Square Footage: 1118 sqft
Block: 000B0
Subdivision: 2089 - EUROPEAN VILLAGE CONDO
Job Phone: 386-313-6221
Location Address: 101 PALM HARBOR PKWY
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 05/24/2023
NOC: Unknown
Applicant name: ANTHONY CRAIG GUCCIONE
Owner: LYSAKOWSKA BEATA

Address

15 RALE PLACE

PALM COAST, FL 32164

Lot: 1140
Contracted Stated Job Value: ¤2,400.00
Job Description: B 114 NON BEARING PARTITIONS
Type: CN

Contractor

GOLD COAST HOME BUILDERS INC
Status Location Address State License Number Phone
ACTIVE

P.O. BOX 354707

PALM COAST, FL 32137

CGC1507791 (Exp: 08/31/2026) 386-313-6221

Inspection History

Type Request Date Result Inspector
BUILDING FINAL 06/05/2023 FINAL APPROVED FWILLIS
Note: requesting as early as possible
FRAMING 05/30/2023 APPROVED FWILLIS

Review History

Department Status Date In Date Out
BLD COMPLETE 05/04/2023 05/11/2023
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM
FI1 COMPLETE 05/04/2023 05/11/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
BADMIN INFORMATION 05/03/2023 05/03/2023
Note: Marked INFORMATION By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM Please remove the street address from the beginning of your file names. See the Document Submittal Requirements on the permit portal for instructions on file naming convention.
ELEC COMPLETE 02/10/2023 02/10/2023
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM I disucssed alterations with owner who indicated no new electrical receptacles, switches, lighting or wiring was performed as part of this project and no existing electrical wiring, swiitches, lighting or wiring was relocated, extended or otherwise altered. Additionally, no new floor area was added to this Group B occupancy. Only a small reconfiguration of existing tennat space thorugh the addition of walls identifed on the "as-built" plan (plans sheet 003) as "3" were added. There has been no increase in occupant load and no new or altered electrical work. Based on this, this electrical review has been marked complete in order to save this notation of the decision to not require any electircal plan revisions.
MECH COMPLETE 02/10/2023 02/10/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM I disucssed alterations with owner who indicated no new mechanical duct, systems or equipment were addded and no alterations made to existing mechanical systems, ducts, or equipment were made. No new floor area in this Group B occupancy was added. Only a small reconfiguration of existing tennat space thorugh the addition of walls identifed on the "as-built" plan (plans sheet 003) as "3" were added - all other walls and enclosed rooms and spaces were existing. Based on this, the mechanical review has been marked complete in order to save this notation of the decision to not require any mechanical plan revisions.
PLUM COMPLETE 02/10/2023 02/10/2023
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM I disucssed alterations with owner who indicated no new plumbing fixtures were added, no new bathrooms created and no expansion to floor area in this Group B occupancy was added. Only a small reconfiguration of existing tennat space thorugh the addition of walls identifed on the "as-built" plan (plans sheet 003) as "3" were added. Based on this, there has been no increase in occupant load and work not significant enough or involving existing bathrooms that would require either alterations to existing bathrooms and / or an increase in number of plumbing fixtures. Based on this, the plumbing review has been marked complete in order to save this notation of the decision to not require any plumbing revisions.
BLD HOLD 01/09/2023 01/18/2023
Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code REVIEW COMMENTS: 1. Provide a Code Analyst per the 2020 7th Edition Florida Building Code Existing. 2. Provide previous use and proposed use per Chapter 3, 2020 7th Edition Florida Building Code. 3. Revise Floor Plan to reflect the walls added. 4. Provide Occupant Load per Table 1004.5. 5. Provide size of egress doors. 6. Provide Travel Egress from the most remote point. Note: A full review was not completed. Further comments could be generated from future submittals.
DSD COMPLETE 01/09/2023 01/09/2023
Note: Released By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM
ELEC HOLD 01/09/2023 01/18/2023
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Provide code analysis showing level of alteration per FBC Existing building 2020 7Th edition 2. Submit electric plan
FI1 HOLD 01/09/2023 01/19/2023
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM All comments per NFPA 2020 7th Edition and or FBC 2020 7th Edition Please provide a response letter addressing all of the comments below. 1. Please provide life safety plan with exit signs, emergency lighting, fire extinguisher locations types and sizes, travel distance to fire extinguishers from the most remote locations, and travel distance to exits, fire wall types in hours per FFPC I Fire Code 10.14.3.4.3 2. Pease provide occupancy type, and adjacent Occupancy types if any for review 3. Please be advised the following note was placed on the permit regarding fire protection, alarms, etc. Any construction alterations having effect on the building fire sprinkler system and or fire alarm system layout and coverage, shall be addressed by a fire protection contractor under a separate permit prior to project completion and approval per FFPC, NFPA 1, Fire Code section 1.12.8 Additional comments are likely after second submittal
MECH HOLD 01/09/2023 01/20/2023
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide code analysis showing level of alteration per FBC Existing building 2020 7Th edition 2. Provide duct layout showing supply, return, fresh air, and exhaust with proposed changes 3. Provide Ventilation calculation per Table 403.3.1.1 FBC Mechanical 2020 7Th edition 4. Provide details for ventilation in nail stations per Table 403.3.1.1 Footnote h FBC Mechanical 2020 7Th edition
PLUM HOLD 01/09/2023 01/18/2023
Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code – Plumbing REVIEW COMMENTS: 1. Provide required plumbing fixtures per Table 403.1. 2. Provide a Plumbing Riser for fixtures added.
UD1 COMPLETE 01/09/2023 01/09/2023
Note: Released By: CHRIS JOHNSON - (386)986-2384 - CJOHNSON@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 50% (¤100.00) 05/24/2023
ADMINISTRATIVE - COMMERCIAL ¤75.00 05/24/2023
INSPECTION COMMERCIAL ¤60.00 05/24/2023
PLAN REVIEW - COMMERCIAL ¤65.00 05/24/2023
SURCHARGE FS 533.721 ¤2.00 05/24/2023
SURCHARGE - FS 468.631 ¤2.01 05/24/2023
SITE PLAN 30 ¤30.00 05/24/2023
Fees Total Due: ¤0.00 Total Paid: ¤134.01