I want to search for...
Permit #2023010419
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7022-00190-0690 |
| Block: 00190 |
| Subdivision: 2217 - SECTION 22-WYNNFIELD |
| Job Phone: 904-813-3820 |
| Location Address: 1 WESTLEE PL |
| Type: ME - MECHANICAL |
| Issue Date: 01/11/2023 |
| NOC: Unknown |
| Applicant name: GARY JAMES HOLLAND |
| Owner: DAVID & SUZANNE JECKOVICH |
|
Address 135 JENKISN STR SUITE 105B SAINT AUGUSTINE, FL 32086 |
| Lot: 0690 |
| Contracted Stated Job Value: ¤4,188.43 |
| Job Description: replacement of existing system |
| Type: CN |
Contractor
HOLLAND A/C & HEATING SERVICES INC
| Status | Location Address | Mailing Address | State License Number | Phone |
| INACTIVE |
5000-18 HWY 17 FLEMING ISLAND, FL 32003 |
#52 FLEMING ISLAND, FL 32003 |
CAC1817261 (Exp: 08/31/2026) | 904-813-3820 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 02/24/2023 | FINAL APPROVED | MKRASKI |
| Note: | |||
| HVAC FINAL | 02/23/2023 | Disapproved -FEE REQUIRED | MKRASKI |
| Note: 2/23/22 1. Unit is not cooling (unit must be in working order to pass inspection) 2. Float switch has been disconnected to make unit run 2/6/2023 - PREVIOUS INSPECTION NOTES 2/6/23 1. Condisation line by ODU needs to be a min of 12'' off home 2. Duct board can not be installed in place of drywall, min 1/2'' drywall require (garage is considered a fire assembly) 3. High voltage wiring is exposed outside FMC 1/19/2023 - PREVIOUS INSPECTION NOTES No permit or AHRI paperwork on site | |||
| HVAC FINAL | 02/06/2023 | Disapproved -FEE REQUIRED | MKRASKI |
| Note: 2/6/23 1. Condisation line by ODU needs to be a min of 12'' off home 2. Duct board can not be installed in place of drywall, min 1/2'' drywall require (garage is considered a fire assembly) 3. High voltage wiring is exposed outside FMC 1/19/2023 - PREVIOUS INSPECTION NOTES No permit or AHRI paperwork on site | |||
| HVAC FINAL | 01/19/2023 | Disapproved -FEE REQUIRED | MKRASKI |
| Note: No permit or AHRI paperwork on site Stopped inspection |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 02/23/2023 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 02/16/2023 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 01/20/2023 |
| ADJUSTMENT 50% | (¤45.00) | 01/11/2023 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 01/11/2023 |
| INSPECTION - MECHANICAL | ¤60.00 | 01/11/2023 |
| SURCHARGE FS 533.721 | ¤2.00 | 01/11/2023 |
| SURCHARGE - FS 468.631 | ¤2.00 | 01/11/2023 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤169.00 |