I want to search for...
Permit #2023011352
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7023-00520-0040 |
| Total Square Footage: 2117 sqft |
| Block: 00520 |
| Subdivision: - |
| Job Phone: 904-200-1339 |
| Location Address: 7 WHEATFIELD DR |
| Type: FU - FIRE UNDERGROUND |
| Issue Date: 06/05/2023 |
| NOC: Unknown |
| Applicant name: JOHN CHEEK |
| Owner: NADEEM MUDASSAR |
|
Address 7 WHEATFIELD DRIVE PALM COAST, FL 32164 |
| Lot: 0040 |
| Contracted Stated Job Value: ¤1,500.00 |
| Job Description: UNDERGROUND FIRE MAIN |
| Type: CN |
Contractor
PYE-BARKER FIRE & SAFETY LLC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
8936 WESTERN WAY, SUITE 5 JACKSONVILLE, FL 32256 |
FPC16-000111 (Exp: 06/30/2026) | 904-634-7100 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR | 07/18/2023 | APPROVED | RMARTIN |
| Note: 6/8/2023 - PREVIOUS INSPECTION NOTES 6-8-23 did not hold pressure, fitting came apart, lost all pressure 6/7/2023 - PREVIOUS INSPECTION NOTES not holding (leaking) | |||
| FIRE SYSTEM FLUSH | 06/12/2023 | APPROVED | RMARTIN |
| FIRE FINAL | 06/12/2023 | FINAL APPROVED | RMARTIN |
| Note: 6/7/2023 - PREVIOUS INSPECTION NOTES Leaking (per contractor pipe will be replaced) need to call in when repaired 6/6/2023 - PREVIOUS INSPECTION NOTES need to pass all other inspections prior to final | |||
| FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR | 06/08/2023 | Disapproved - NO FEE | LMILLER |
| Note: 6-8-23 did not hold pressure, fitting came apart, lost all pressure 6/7/2023 - PREVIOUS INSPECTION NOTES not holding (leaking) | |||
| FIRE FINAL | 06/07/2023 | Disapproved - NO FEE | LMILLER |
| Note: Leaking (per contractor pipe will be replaced) need to call in when repaired 6/6/2023 - PREVIOUS INSPECTION NOTES need to pass all other inspections prior to final | |||
| FIRE MAIN PLACEMENT /SIZE/THRUST /BLOCKING | 06/07/2023 | APPROVED | LMILLER |
| FIRE MAIN HYDROSTATIC/BACKFLOW PREVENTOR | 06/07/2023 | Disapproved - NO FEE | LMILLER |
| Note: not holding (leaking) | |||
| FIRE FINAL | 06/06/2023 | Disapproved - NO FEE | LMILLER |
| Note: need to pass all other inspections prior to final |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 05/12/2023 | 05/12/2023 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| FI1 | HOLD | 04/26/2023 | 05/01/2023 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1.NFPA 13R 6.11.1 At least one fire department connection shall be provided for buildings, accessible by a fire department, that exceed 2000 ft2 (186 m2) or are more than a single story. | |||
| FI1 | HOLD | 03/27/2023 | 03/31/2023 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM This Occupancy will require a full 13-R sprinkler system. Please remove any and all reference to 13-D and design the system for 13-R for review | |||
| FI1 | HOLD | 01/27/2023 | 02/01/2023 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please provide material Spec sheets | |||
| UD1 | CANCEL | 01/27/2023 | 01/30/2023 |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 50% | (¤100.60) | 06/05/2023 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 06/05/2023 |
| INSPECTION - FIRE COMMERCIAL | ¤61.20 | 06/05/2023 |
| PLAN REVIEW - COMMERCIAL | ¤65.00 | 06/05/2023 |
| SURCHARGE FS 533.721 | ¤2.00 | 06/05/2023 |
| SURCHARGE - FS 468.631 | ¤2.00 | 06/05/2023 |
| SW ENG - INSPECTION 20 | ¤20.00 | 06/05/2023 |