Permit #2023011439

Permit Details

Status: FINAL

Parcel Id: 20-12-31-2964-00000-0650
Block: 00000
Subdivision: 2307 - GRAND LANDINGS PHASE 4
Job Phone: 386-212-2958
Location Address: 157 WOOD STORK LN
Type: PO - POOL
Issue Date: 02/27/2023
NOC: RECORDED
Applicant name: COBY KYLE MOORE
Owner: BULLOCK ERNESTINE & BRUCE BULLOCK

Address

157 WOOD STORK LN

PALM COAST, FL 32164

Lot: 0650
Contracted Stated Job Value: ¤66,000.00
Job Description: Swimming pool with deck- screen by others
Type: CN

Contractor

CM DESIGNS INC.
Status Location Address State License Number Phone Fax
ACTIVE

1050 ROBERTS STREET

ORMOND BEACH, FL 32174

CPC1456991 (Exp: 08/31/2026) (386)615-7425 386-676-2963

Sub Contractors

GREGORY ALAN WARD
Status Location Address State License Number Phone
INACTIVE

P.O. BOX 731453

ORMOND BEACH, FL 32174

EC13005000 (Exp: 08/31/2026) 386-566-7248

Inspection History

Type Request Date Result Inspector
POOL FINAL 12/15/2023 FINAL APPROVED BTAYLOR
Note: 12/12/2023 - PREVIOUS INSPECTION NOTES 12/12/23: As previously noted during Inspection 2620, the Pool Heater requires 4 FPA anchors (FBC-M1307.2). Inspector Notes from Inspection 2610 5/9/23: I had to secure the safety fence for you. Please make sure it stays in place (as required) while not working. 5/5/2023 - PREVIOUS INSPECTION NOTES 5/5/23: 1). Footer does not consistently follow any of the approved footers on the Master Pool plan. 2). Clearance to rebar is not met in multiple places. (R404.1.2.3.7.4) 3). Safety fence is down & not installed properly. Safety fence must remain in tact during all times that the pool is not being actively worked on with personnel on-site.
POOL FINAL 12/12/2023 Disapproved -FEE REQUIRED RSIMS
Note: 12/12/23: As previously noted during Inspection 2620, the Pool Heater requires 4 FPA anchors (FBC-M1307.2). Inspector Notes from Inspection 2610 5/9/23: I had to secure the safety fence for you. Please make sure it stays in place (as required) while not working. 5/5/2023 - PREVIOUS INSPECTION NOTES 5/5/23: 1). Footer does not consistently follow any of the approved footers on the Master Pool plan. 2). Clearance to rebar is not met in multiple places. (R404.1.2.3.7.4) 3). Safety fence is down & not installed properly. Safety fence must remain in tact during all times that the pool is not being actively worked on with personnel on-site.
ROW FIELD SURVEY /GRADING CERTIFICATION 12/11/2023 APPROVED TPOLACEK
Note: 12/11/23 UPON WALKING PROPERTY DETERMINED THERE ARE NO ADVERSE DRAINAGE CONDITIONS At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved ___________________________________________________________________________ 11/17/2023 - PREVIOUS INSPECTION NOTES 11/17/23 GRADE IS NOT MATCHED. WATER IS POOLING IN THE MIDDLE, NOT MOVING FORWARD. NEED TO MATCH GRADE OD EXISTING SOD. SEE PHOTO FOR REFERENCE. 8/14/2023 - PREVIOUS INSPECTION NOTES NEED TO FIX DRAINAGE ON LEFT SIDE OF HOUSE WATER IS SITTING
ROW - FINAL INSPECTION 12/11/2023 APPROVED - AS NOTED TPOLACEK
Note: 12/11/23 UPON WALKING PROPERTY DETERMINED THERE ARE NO ADVERSE DRAINAGE CONDITIONS At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved ** NO ROW DAMAGE PRESENT AT TIME OF THIS INSPECTION _________________________________________________________________ 12/8/2023 - PREVIOUS INSPECTION NOTES 11/17/2023 - PREVIOUS INSPECTION NOTES 11/17/23 GRADE IS NOT MATCHED. WATER IS POOLING IN THE MIDDLE, NOT MOVING FORWARD. NEED TO MATCH GRADE OF EXISTING SOD. A FIELD SURVEY WAS NOT SCHEDULED PRIR TO THIS INSPECTION, SO YOU WERE FEE'D ON YUOR FIELD, I WILL NOT FEE YOU ON THIS INSPECTION. NEED TO MAKE CORRECTIONS BEFORE SCHEDULING FINAL INSPECTION. SEE PHOTO FOR REFERENCE. __________________________________________________________________________________________________________________________ 8/14/2023 - PREVIOUS INSPECTION NOTES NEED TO FIX DRAINAGE ON LEFT SIDE OF HOUSE WATER IS SITTING. 8/16/2023 - PREVIOUS INSPECTION NOTES NEED TO FIX AREA ON THE LEFT SIDE OF HOUSE WATER IS SITTING AND WAY TO WET
U -UTILITY RESIDENTIAL FINAL 12/11/2023 CANCELLED BY APPLICANT TPOLACEK
Note: SORRY lARRY SCHEDULED BY ACCIDENT
U -UTILITY RESIDENTIAL FINAL 12/11/2023 FINAL APPROVED JHARDING
Note: 12/8/2023 - PREVIOUS INSPECTION NOTES SORRY lARRY SCHEDULED BY ACCIDENT
ROW - FINAL INSPECTION 12/08/2023 CANCELLED BY APPLICANT TPOLACEK
Note: 11/17/2023 - PREVIOUS INSPECTION NOTES 11/17/23 GRADE IS NOT MATCHED. WATER IS POOLING IN THE MIDDLE, NOT MOVING FORWARD. NEED TO MATCH GRADE OF EXISTING SOD. A FIELD SURVEY WAS NOT SCHEDULED PRIR TO THIS INSPECTION, SO YOU WERE FEE'D ON YUOR FIELD, I WILL NOT FEE YOU ON THIS INSPECTION. NEED TO MAKE CORRECTIONS BEFORE SCHEDULING FINAL INSPECTION. SEE PHOTO FOR REFERENCE. __________________________________________________________________________________________________________________________ 8/14/2023 - PREVIOUS INSPECTION NOTES NEED TO FIX DRAINAGE ON LEFT SIDE OF HOUSE WATER IS SITTING. 8/16/2023 - PREVIOUS INSPECTION NOTES NEED TO FIX AREA ON THE LEFT SIDE OF HOUSE WATER IS SITTING AND WAY TO WET
ROW - FINAL INSPECTION 11/17/2023 Disapproved - NO FEE FSLADISH
Note: 11/17/23 GRADE IS NOT MATCHED. WATER IS POOLING IN THE MIDDLE, NOT MOVING FORWARD. NEED TO MATCH GRADE OF EXISTING SOD. A FIELD SURVEY WAS NOT SCHEDULED PRIR TO THIS INSPECTION, SO YOU WERE FEE'D ON YUOR FIELD, I WILL NOT FEE YOU ON THIS INSPECTION. NEED TO MAKE CORRECTIONS BEFORE SCHEDULING FINAL INSPECTION. SEE PHOTO FOR REFERENCE. __________________________________________________________________________________________________________________________ 8/14/2023 - PREVIOUS INSPECTION NOTES NEED TO FIX DRAINAGE ON LEFT SIDE OF HOUSE WATER IS SITTING. 8/16/2023 - PREVIOUS INSPECTION NOTES NEED TO FIX AREA ON THE LEFT SIDE OF HOUSE WATER IS SITTING AND WAY TO WET
ROW FIELD SURVEY /GRADING CERTIFICATION 11/17/2023 Disapproved -FEE REQUIRED FSLADISH
Note: 11/17/23 GRADE IS NOT MATCHED. WATER IS POOLING IN THE MIDDLE, NOT MOVING FORWARD. NEED TO MATCH GRADE OD EXISTING SOD. SEE PHOTO FOR REFERENCE. 8/14/2023 - PREVIOUS INSPECTION NOTES NEED TO FIX DRAINAGE ON LEFT SIDE OF HOUSE WATER IS SITTING
ROW - FINAL INSPECTION 08/16/2023 Disapproved - NO FEE PFLANAGAN
Note: NEED TO FIX AREA ON THE LEFT SIDE OF HOUSE WATER IS SITTING AND WAY TO WET
ROW- FINAL SURVEY/GRADING CERTIFICATION 08/14/2023 APPROVED PFLANAGAN
Note: At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved.
ROW FIELD SURVEY /GRADING CERTIFICATION 08/14/2023 Disapproved - NO FEE PFLANAGAN
Note: NEED TO FIX DRAINAGE ON LEFT SIDE OF HOUSE WATER IS SITTING
ELECTRIC AND ALARM 06/14/2023 APPROVED - AS NOTED RSIMS
Note: 6/14/23: Will need the following items resolved before Pool Final can be approved. 1). Pool heater only has one anchor. Requires 4 anchors. 2). Free standing Hot Tub - cover will need to be removed to verify proper grounding/bonding, wire size and breaker size.
POOL DECK 05/09/2023 APPROVED - AS NOTED RSIMS
Note: 5/9/23: I had to secure the safety fence for you. Please make sure it stays in place (as required) while not working. 5/5/2023 - PREVIOUS INSPECTION NOTES 5/5/23: 1). Footer does not consistently follow any of the approved footers on the Master Pool plan. 2). Clearance to rebar is not met in multiple places. (R404.1.2.3.7.4) 3). Safety fence is down & not installed properly. Safety fence must remain in tact during all times that the pool is not being actively worked on with personnel on-site.
POOL DECK 05/05/2023 Disapproved -FEE REQUIRED RSIMS
Note: 5/5/23: 1). Footer does not consistently follow any of the approved footers on the Master Pool plan. 2). Clearance to rebar is not met in multiple places. (R404.1.2.3.7.4) 3). Safety fence is down & not installed properly. Safety fence must remain in tact during all times that the pool is not being actively work on with personnel on-site.
STEEL AND GROUND 03/27/2023 APPROVED RSIMS

Review History

Department Status Date In Date Out
ZON COMPLETE 02/27/2023 02/27/2023
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
ELEC COMPLETE 02/08/2023 02/09/2023
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
MECH COMPLETE 02/08/2023 02/09/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ZON HOLD 02/08/2023 02/08/2023
Note: Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM Waiting on screen enclosure for review
BLD COMPLETE 02/08/2023 02/14/2023
Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM
BLD HOLD 01/30/2023 02/01/2023
Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM Provide a current City of Palm Coast Pool Safety Form.
ELEC HOLD 01/30/2023 01/31/2023
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM Need to reference the correct NEC code year. note 21
MECH HOLD 01/30/2023 01/31/2023
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide completed City of Palm Coast TDH form found on city portal
SW1 COMPLETE 01/30/2023 02/03/2023
Note: Released By: EDWARD MADISON - - EMADISON@PALMCOASTGOV.COM
ZON HOLD 01/30/2023 02/01/2023
Note: Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM Waiting on screen enclosure for review .

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 12/14/2023
SW ENG REINSPECTION 20 ¤20.00 12/08/2023
REINSPECTION RESIDENTIAL ¤40.00 05/08/2023
SW ENG - REVIEW 20 ¤20.00 02/27/2023
SITE PLAN 30 ¤30.00 02/27/2023
SURCHARGE FS 533.721 ¤2.00 02/27/2023
SURCHARGE - FS 468.631 ¤2.00 02/27/2023
SW ENG INSPECTION 40 ¤40.00 02/27/2023
ADJUSTMENT 50% (¤127.50) 02/27/2023
ADMINISTRATIVE RESIDENTIAL ¤30.00 02/27/2023
INSPECTION- POOL ¤160.00 02/27/2023
PLAN REVIEW - RESIDENTIAL ¤65.00 02/27/2023
Fees Total Due: ¤0.00 Total Paid: ¤321.50