Permit Details
Status: CANCEL
| Parcel Id: 09-11-30-0000-01020-0021 |
| Block: 01020 |
| Subdivision: - |
| Job Phone: 305-799-4886 |
| Location Address: 24 HARGROVE GRADE |
| Type: BC - BUILDING COMMERCIAL |
| Issue Date: 05/05/2023 |
| NOC: Unknown |
| Applicant name: JOHN EDWARD JAMES |
| Owner: REAL ESTATE DEVELOPMENT OF FLORIDA LLC |
|
Address 32 HARGROVE GRADE PALM COAST, FL 32164 |
| Lot: 0021 |
| Contracted Stated Job Value: ¤200,000.00 |
| Job Description: BLDG 1 - SHELL ERECTION ONLY |
| Type: CN |
Contractor
JAMES COMMERCIAL DEVELOPMENT INC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
9950 KIRCHHERR WEST PALM BEACH, FL 33411 |
CGC1514256 (Exp: 08/31/2026) | 305-799-4886 |
Sub Contractors
NEVILLE ROY BENNETT
| Status | Location Address | State License Number | Phone |
| ACTIVE |
1802 IMPERIAL PALM DRIVE APOPKA, FL 32172 |
EC0003124 (Exp: 08/31/2026) | 407-920-6566 |
GARY S WELBORN
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
1709 North Nova Road Holly Hill, 32117 |
CFC1426839 (Exp: 08/31/2026) | (386) 257-1172 | 386-252-5979 |
Inspection History
| Type | Request Date | Result | Inspector |
| MONOLITHIC SLAB | 05/12/2023 | APPROVED | FWILLIS |
| FOOTER | 05/12/2023 | APPROVED | FWILLIS |
| PLUMBING 1ST ROUGH | 05/10/2023 | APPROVED | MGIBSON |
| ELECTRIC 1ST ROUGH | 05/09/2023 | APPROVED | RMARTIN |
| ELECTRIC 2ND ROUGH | |||
| ELECTRIC FINAL | |||
| FOUNDATION SURVEY - OFFICE USE ONLY | |||
| PLUMBING 2ND ROUGH | |||
| GRAVITY SEWER | |||
| BLD - SEWER TIE IN | |||
| PLUMBING FINAL | |||
| LINTEL | |||
| FRAMING | |||
| ROOF SHEATHING / BRACE / TIE DOWN | |||
| ABOVE CEILING | |||
| INSULATION | |||
| STOREFRONT | |||
| BUILDING FINAL | |||
| FIRE FINAL | |||
| EXTERIOR ARCHITECTURAL FEATURES | |||
| U - UTILITY COMMERCIAL FINAL |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 09/13/2023 | 09/19/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| BADMIN | COMPLETE | 05/04/2023 | 05/04/2023 |
| Note: Released By: SCOTT THOMAS - - STHOMAS@PALMCOASTGOV.COM | |||
| BADMIN | HOLD | 04/30/2023 | 04/30/2023 |
| Note: Held By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM We do not have a James Commercial Hvac contrator regsitered in our database. Please go to the building services webpage, under contractor registration and complete the instructions to register. Please notify us once you receive verification that you are active in our database and will will add the license to this permit. Buildingdivision@palmcoastgov.com | |||
| BLD | COMPLETE | 04/28/2023 | 05/03/2023 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| FI1 | COMPLETE | 04/28/2023 | 05/01/2023 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| FI1 | HOLD | 04/19/2023 | 04/19/2023 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM 1. OK 2. OK 4. Not accepted, Please remove the term Temporary from the fire extinguisher locations as the travel distance must be maintained. Maximum Travel distance to extinguishers exceeded per FFPC 1, 13.6.3.2.1.2.2 | |||
| BLD | HOLD | 04/19/2023 | 04/19/2023 |
| Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code-Building (FBCB), Florida Statutes (F.S.) and Florida Administrative Code (F.A.C.). B. REPEAT COMMENT: DOOR SCHEDULE ADDED TO PLAN SHEET A-1 BUT NO WINDOWS SCHEDULE AS REQUESTED. Window and door schedules. 12. REPEAT COMMENT: Permit Application: Provide electrical and plumbing contractors on permit application. New comment: New Plan Sheet A-3 "Sections and Details" indicates decorative veneer stone base mortared to gypsum base. What type of gypsum base? Exterior gypsum sheathing? Thickness? What are the fastening requirements for this veneer backing and gypsum base? Is there sufficient framing other than the steel building frame? What does the veneer manufacturer require for adhered veneer installation? Where is the water resistive barrier? Where is the flashing between dissimilar materials (e.g. between the PBR panels and veneer? Is lathing required for mortar adhered veneer? Provide a complete wall section showing all elements of the exterior envelope as well as manufacturer’s specs., backing and attachment details. | |||
| FI1 | HOLD | 03/31/2023 | 04/03/2023 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please provide a written response to each comment below in a response letter, provide clouded response changes on plan sheets and add page locations for each response. 1. OK 2. OK 3. Not accepted, the classification of hazard of contents needs to be classified with the nomenclature used in the FFPC 7th Edition (2020) as (Low, Ordinary, or High in accordance with 6.2.2.2, 6.2.2.3, and 6.2.2.4). Please add the proper classification per the FFPC 7th 101 section 6.2.2. Code analysis reveals the occupancy as a storage occupancy, please provide the classification of hazard of contents per NFPA 101, of the FFPC (2020) 42.1.5 4. Not accepted, Please remove the term Temporary from the fire extinguisher locations as the travel distance must be maintained. Maximum Travel distance to extinguishers exceeded per FFPC 1, 13.6.3.2.1.2.2 5. Please acknowledge in comment letter. Please acknowledge that the following note was added to the permit: SEPARATE PERMITS REQUIRED FOR ALL FIRE SPRINKLERS, FIRE ALARMS/NOTIFICATION, FIRE SUPPRESSION, HOOD SUPPRESSION SUYSTEMS, AND FIRE UNDERGROUND WORK BY CONTRACTORS LICENSED FOR THE SCOPE OF WORK ACCORDING TO FLORIDA STATUTES CHAPTER 633. PLANS PREPARED BY A FLORIDA LICENSED PROFESSIONAL AS WELL AS ANY SYSTEM LAYOUT PLANS SHALL BE SUBMITTED WITH EACH PERMIT. ALLOW SUFFICIENT TIME FOR PLAN REVIEW AND PLAN APPROVAL. NO WORK SHALL BE STARTED, COVERED OR OTHERWISE CONCEALED FROM VIEW UNTIL APPROVED SEPARATE PERMITS MAY BE REQUIRED FOR BDA, IN ORDER TO DETERMINE IF NEEDED PLEASE CONTACT JARRAD SHUPE (WITH FLAGLER COUNTY) AT: 386-313-4281 IN REGARDS TO GRID TESTING AND INSTALLATION OF BDA (BI-DIRECTIONAL ANTENNA) PER NFPA 1, SECTION 10.1 (7TH EDITION), NFPA 72 (2016), AND NFPA 1221 (2016). PERMIT IF REQUIRED WILL BE SUBMITTED THROUGH THE CITY OF PALM COAST | |||
| BLD | HOLD | 03/31/2023 | 04/18/2023 |
| Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code-Building (FBCB), Florida Statutes (F.S.) and Florida Administrative Code (F.A.C.). 5. REPEAT COMMENT: Plan Sheet G-101 not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. 6. REPEAT COMMENT: Plan Sheet LS-100 not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. 10. REPEAT COMMENT: Plan Sheet A-4 not signed and sealed by a Florida licensed architect per F.S. 481 F.A.C. 16G1-16.005. 11. In addition to the above, the following plan sheets and / or information is missing: A. Complete exterior wall sections, from interior finish / surface through to exterior cladding and from foundation through to roof for each exterior wall type. B. REPEAT COMMENT: DOOR SCHEDULE ADDED TO PLAN SHEET A-1 BUT NO WINDOWS SCHEDULE AS REQUESTED. Window and door schedules. 12. REPEAT COMMENT: Permit Application: Provide electrical and plumbing contractors on permit application. 13. Roofing Product Approval Worksheet: Product Approval number (3775.1) for metal roof panels are for a different metal building manufacturer (Dean Steel Buildings) than the metal building proposed for this project (Apec). New comment: Revised Plan Sheet A-1 “First Floor Plan” not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. New comment: New Plan Sheet A-2 “Exterior Elevations” not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. New comment: New Plan Sheet A-3 “Sections and Details” not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. New comment: Revised Plan Sheet A-4 “Roof Plan” not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. New comment: New Plan Sheet “A-3” “Sections and Details indicates decorative veneer stone base mortared to gypsum base. What type of gypsum base? Exterior gypsum sheathing? Thickness? What are the fastening requirements for this veneer backing and gypsum base? Is there sufficient framing other than the steel building frame? What does the veneer manufacture require for adhered veneer installation? Where is the water resistive barrier? Where is the flashing between dissimilar materials (e.g. between the PBR panels and veneer? Is lathing required for mortar adhered veneer? Provide a complete wall section showing all elements of the exterior envelope as well as manufacturer’s specs., backing and attachment details. | |||
| FI1 | HOLD | 03/17/2023 | 03/21/2023 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM 1. The newly provided Code Analysis indicates a note stating the building is Non Sprinklered, Please change to Sprinklered as this building requires an NFPA 13 sprinkler system per FBC 7th edition section 903. 2. The code analysis shows storage as the occupancy, please indicate S-1 or S-2 for occupancy classification. 3. Code analysis reveals the occupancy as a storage occupancy, please provide the classification of hazard of contents per NFPA 101, of the FFPC (2020) 42.1.5 4. Maximum Travel distance to extinguishers exceeded per FFPC 1, 13.6.3.2.1.2.2 5. Please acknowledge that the following note was added to the permit: SEPARATE PERMITS REQUIRED FOR ALL FIRE SPRINKLERS, FIRE ALARMS/NOTIFICATION, FIRE SUPPRESSION, HOOD SUPPRESSION SUYSTEMS, AND FIRE UNDERGROUND WORK BY CONTRACTORS LICENSED FOR THE SCOPE OF WORK ACCORDING TO FLORIDA STATUTES CHAPTER 633. PLANS PREPARED BY A FLORIDA LICENSED PROFESSIONAL AS WELL AS ANY SYSTEM LAYOUT PLANS SHALL BE SUBMITTED WITH EACH PERMIT. ALLOW SUFFICIENT TIME FOR PLAN REVIEW AND PLAN APPROVAL. NO WORK SHALL BE STARTED, COVERED OR OTHERWISE CONCEALED FROM VIEW UNTIL APPROVED SEPARATE PERMITS MAY BE REQUIRED FOR BDA, IN ORDER TO DETERMINE IF NEEDED PLEASE CONTACT JARRAD SHUPE (WITH FLAGLER COUNTY) AT: 386-313-4281 IN REGARDS TO GRID TESTING AND INSTALLATION OF BDA (BI-DIRECTIONAL ANTENNA) PER NFPA 1, SECTION 10.1 (7TH EDITION), NFPA 72 (2016), AND NFPA 1221 (2016). PERMIT IF REQUIRED WILL BE SUBMITTED THROUGH THE CITY OF PALM COAST | |||
| PLUM | COMPLETE | 03/17/2023 | 03/28/2023 |
| Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 03/17/2023 | 03/20/2023 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| MECH | CANCEL | 03/17/2023 | 03/20/2023 |
| BLD | HOLD | 03/17/2023 | 03/28/2023 |
| Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code-Building (FBCB), Florida Statutes (F.S.) and Florida Administrative Code (F.A.C.). WARNING: BUILDING CODE PLAN REVIEW COULD NOT BE COMPLETED (2ND TIME). PLAN SUBMITTAL IS INCOMPLETE AND LACKING REQUIRED PLAN SHEETS, DETAILS AND DESIGN INFORMATION NECESSARY FOR A COMPLETE REVIEW. YOU ARE ADVISED A MEETING WITH THE PROJECT ARCHITECT AND CONTRACTOR MAY BE BENEFICIAL TO ENSURE NECESSARY INFORMATION IS PROVIDED AT NEXT SUBMITTAL SO A COMPLETE REVIEW CAN BE PERFORMED AND THAT REVIEW RESULTS IN ISSUANCE OF A BUILDING PERMIT. 1. Plan Sheet G-100 not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. 2. Plan Sheet G-100 includes a "Drawing List" of plan sheets. The following plan sheets were not submitted for review: A-2 First Floor Plan, A-3 Ceiling Plan, M-3 HVAC Floor Plan and RENT-1 Leasing Plan. This is an incomplete submittal. Plan review cannot be completed. 3. In addition to the missing plan sheets identified above, it is likely additional mechanical plan sheets other than M-3 HVAC Floor Plan are missing. Where is M-1? M-2? Are there other mechanical plan sheets missing? Note: if no mechanical work is intended under this shell permit then remove reference to Plan Sheet M-3. 4. Plan Sheet G-100 does not provide a complete list of Drawings or Plans. The architect of record is obligated to provide a complete list / index of plans per F.A.C. 61G1-16.003. The following plan sheets have been omitted from the list: Plan Sheet F001 Notes & Foundation Details, Plan Sheet F002 Foundation Plan, Plan Sheet P0.1 Plumbing General Information, Plan Sheet P1.1 Sanitary Plan, Plan Sheet P2.1 Domestic Water Plan, Plan Sheet 3.1 Riser Diagrams, Plan Sheet E0.1 Electrical Legend and Specifications (mis-labeled on Drawing List), Plan Sheet E0.2 Electrical Site Plan, Plan Sheet E0.3 Site Photometrics Plan, Plan Sheet E0.4 Lighting Details, Plan Sheet E1.1 Electrical Plan, Plan Sheet E1.2 Lighting Plan. 5. Plan Sheet G-101 not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. File is corrupted and a majority of printed text is illegible. No review completed. 6. Plan Sheet LS-100 not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. 7. Plan Sheet LS-100 contains incomplete code analysis information. Provide the following: A. Under Applicable Codes section, add 2020 Florida Building Code-Mechanical, 2020 Florida Building Code-Mechanical, 2020 Florida Building Code-Energy Conservation, 2017 National Electric Code. B. Under Use and Occupancy Classification provide complete reference to storage occupancy type. Per FBCB Section 311.1, indicate whether proposed occupancy is S-1 Moderate Hazard Storage per Section 311.2 or S-2 Low Hazard Storage per Section 311.3. 8. Under Building Height and Area provide the following: A. Actual number of stories based on proposed occupancy and construction type vs. Allowable number of stories based on proposed occupancy and construction type. FBCB Section 504. B. Allowable floor area based on proposed occupancy and construction type. (note: as shown, actual floor area exceeds allowable floor area for non-sprinkled S-1 Moderate Hazard Storage building of Type IIB construction. Please reconcile actual area vs. allowable area. See FBCB Sections 503, 504, and 506. 9. Plan Sheet A1 has been rejected by the Building Division and will not be reviewed and shall not be a part of any approved plans by the City. A foundation plan (Plan Sheets F001, F002) prepared by a Florida licensed professional engineer has been previously submitted and is controlling. 10. Plan Sheet A-4 not signed and sealed by a Florida licensed architect per F.S. 481 F.A.C. 16G1-16.005. 11. In addition to the above, the following plan sheets and / or information is missing: A. Complete exterior wall sections, from interior finish / surface through to exterior cladding and from foundation through to roof for each exterior wall type. B. Window and door schedules. C. Gutters and downspout sizing, materials, locations. Metal building manufacturer specifies gutters but not capacity. Capacity (sizing) must be determined in accordance with the Florida Building Code-Plumbing per FBCB Section 1514.4.3. 12. Permit Application: Provide electrical and plumbing contractors on permit application. 13. Roofing Product Approval Worksheet: Product Approval number (3775.1) for metal roof panels are for a different metal building manufacturer (Dean Steel Buildings) than the metal building proposed for this project (Apec). | |||
| ARCHR | COMPLETE | 03/17/2023 | 03/31/2023 |
| Note: Released By: RICHARD PICATAGI - (386)986-3760 - RPICATAGI@PALMCOASTGOV.COM | |||
| ARCHR | HOLD | 02/17/2023 | 03/06/2023 |
| Note: Held By: RICHARD PICATAGI - (386)986-3760 - RPICATAGI@PALMCOASTGOV.COM Applicant must provided exterior facade colors and accent colors in the building plans including color name, index # and LRV | |||
| BLD | HOLD | 02/17/2023 | 03/06/2023 |
| Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM Incomplete plan submittal. No plan review performed. Provide all architectural plan sheets signed and sealed by a Florida licensed architect. Provide all MEP plan sheets signed and sealed by a Florida licensed professional engiener. Provide all associated, supporting documents such as Florida PRoduct Approval Number worksheet, Palm Coast Roofing Worksheet, Revise permit application to include all MEP sub-contractors. | |||
| DSD | COMPLETE | 02/17/2023 | 02/21/2023 |
| Note: Released By: JACQUELINE GONZALEZ - (386)986-3751 - JGONZALEZ@PALMCOASTGOV.COM | |||
| ELEC | CANCEL | 02/17/2023 | 02/24/2023 |
| FI1 | HOLD | 02/17/2023 | 02/24/2023 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please provide a written response to each comment below in a response letter, provide clouded response changes on plan sheets and add page locations for each response. 1. Please include FFPC 7th edition in the code analysis 2. Please include FBC 7th edition in the code analysis 3. Please provide a code analysis and be sure to include, Use and occupancy classification per FBC chapter 3, General building heights and area per FBC chapter 5, and Types of construction per FBC chapter 6, | |||
| MECH | CANCEL | 02/17/2023 | 02/21/2023 |
| Note: not needed | |||
| PLUM | HOLD | 02/17/2023 | 03/06/2023 |
| Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM Provide complete plumbing plans for potable water distribution sytem and drain, waste, vent system. Include all plumbing fixtures specifrications, water pipe and sanitary drainage materials specifcations, isometric drawings, pipe sizes, etc. | |||
| UD1 | COMPLETE | 02/17/2023 | 03/02/2023 |
| Note: Released By: BRICE WRIGHT - - |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 50% | (¤902.50) | 05/05/2023 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 05/05/2023 |
| INSPECTION COMMERCIAL | ¤1,400.00 | 05/05/2023 |
| INSPECTION - FIRE COMMERCIAL | ¤50.00 | 05/05/2023 |
| PLAN REVIEW - COMMERCIAL | ¤280.00 | 05/05/2023 |
| FC IMPACT FEE EMS | ¤68.00 | 05/05/2023 |
| FC IMPACT FEE EMS | ¤111.00 | 05/05/2023 |
| IMPACT FEE FIRE | ¤11,560.00 | 05/05/2023 |
| IMPACT FEE FIRE | ¤2,040.00 | 05/05/2023 |
| FC IMPACT FEE LAW ENFORCEMENT | ¤426.00 | 05/05/2023 |
| FC IMPACT FEE LAW ENFORCEMENT | ¤272.00 | 05/05/2023 |
| IMPACT FEE TRANSPORTATION | ¤12,015.00 | 05/05/2023 |
| IMPACT FEE TRANSPORTATION | ¤8,075.00 | 05/05/2023 |
| SURCHARGE FS 533.721 | ¤9.56 | 05/05/2023 |
| SURCHARGE - FS 468.631 | ¤14.35 | 05/05/2023 |
| SITE PLAN 30 | ¤30.00 | 05/05/2023 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤35,523.41 |