Permit #2023020911

Permit Details

Status: CANCEL

Parcel Id: 09-11-30-0000-01020-0021
Block: 01020
Subdivision: -
Job Phone: 305-799-4886
Location Address: 24 HARGROVE GRADE
Type: BC - BUILDING COMMERCIAL
Issue Date: 05/05/2023
NOC: Unknown
Applicant name: JOHN EDWARD JAMES
Owner: REAL ESTATE DEVELOPMENT OF FLORIDA LLC

Address

32 HARGROVE GRADE

PALM COAST, FL 32164

Lot: 0021
Contracted Stated Job Value: ¤200,000.00
Job Description: BLDG 1 - SHELL ERECTION ONLY
Type: CN

Contractor

JAMES COMMERCIAL DEVELOPMENT INC
Status Location Address State License Number Phone
ACTIVE

9950 KIRCHHERR

WEST PALM BEACH, FL 33411

CGC1514256 (Exp: 08/31/2026) 305-799-4886

Sub Contractors

NEVILLE ROY BENNETT
Status Location Address State License Number Phone
ACTIVE

1802 IMPERIAL PALM DRIVE

APOPKA, FL 32172

EC0003124 (Exp: 08/31/2026) 407-920-6566
GARY S WELBORN
Status Location Address State License Number Phone Fax
ACTIVE

1709 North Nova Road

Holly Hill, 32117

CFC1426839 (Exp: 08/31/2026) (386) 257-1172 386-252-5979

Inspection History

Type Request Date Result Inspector
MONOLITHIC SLAB 05/12/2023 APPROVED FWILLIS
FOOTER 05/12/2023 APPROVED FWILLIS
PLUMBING 1ST ROUGH 05/10/2023 APPROVED MGIBSON
ELECTRIC 1ST ROUGH 05/09/2023 APPROVED RMARTIN
ELECTRIC 2ND ROUGH
ELECTRIC FINAL
FOUNDATION SURVEY - OFFICE USE ONLY
PLUMBING 2ND ROUGH
GRAVITY SEWER
BLD - SEWER TIE IN
PLUMBING FINAL
LINTEL
FRAMING
ROOF SHEATHING / BRACE / TIE DOWN
ABOVE CEILING
INSULATION
STOREFRONT
BUILDING FINAL
FIRE FINAL
EXTERIOR ARCHITECTURAL FEATURES
U - UTILITY COMMERCIAL FINAL

Review History

Department Status Date In Date Out
BLD COMPLETE 09/13/2023 09/19/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
BADMIN COMPLETE 05/04/2023 05/04/2023
Note: Released By: SCOTT THOMAS - - STHOMAS@PALMCOASTGOV.COM
BADMIN HOLD 04/30/2023 04/30/2023
Note: Held By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM We do not have a James Commercial Hvac contrator regsitered in our database. Please go to the building services webpage, under contractor registration and complete the instructions to register. Please notify us once you receive verification that you are active in our database and will will add the license to this permit. Buildingdivision@palmcoastgov.com
BLD COMPLETE 04/28/2023 05/03/2023
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
FI1 COMPLETE 04/28/2023 05/01/2023
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
FI1 HOLD 04/19/2023 04/19/2023
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM 1. OK 2. OK 4. Not accepted, Please remove the term Temporary from the fire extinguisher locations as the travel distance must be maintained. Maximum Travel distance to extinguishers exceeded per FFPC 1, 13.6.3.2.1.2.2
BLD HOLD 04/19/2023 04/19/2023
Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code-Building (FBCB), Florida Statutes (F.S.) and Florida Administrative Code (F.A.C.). B. REPEAT COMMENT: DOOR SCHEDULE ADDED TO PLAN SHEET A-1 BUT NO WINDOWS SCHEDULE AS REQUESTED. Window and door schedules. 12. REPEAT COMMENT: Permit Application: Provide electrical and plumbing contractors on permit application. New comment: New Plan Sheet A-3 "Sections and Details" indicates decorative veneer stone base mortared to gypsum base. What type of gypsum base? Exterior gypsum sheathing? Thickness? What are the fastening requirements for this veneer backing and gypsum base? Is there sufficient framing other than the steel building frame? What does the veneer manufacturer require for adhered veneer installation? Where is the water resistive barrier? Where is the flashing between dissimilar materials (e.g. between the PBR panels and veneer? Is lathing required for mortar adhered veneer? Provide a complete wall section showing all elements of the exterior envelope as well as manufacturer’s specs., backing and attachment details.
FI1 HOLD 03/31/2023 04/03/2023
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please provide a written response to each comment below in a response letter, provide clouded response changes on plan sheets and add page locations for each response. 1. OK 2. OK 3. Not accepted, the classification of hazard of contents needs to be classified with the nomenclature used in the FFPC 7th Edition (2020) as (Low, Ordinary, or High in accordance with 6.2.2.2, 6.2.2.3, and 6.2.2.4). Please add the proper classification per the FFPC 7th 101 section 6.2.2. Code analysis reveals the occupancy as a storage occupancy, please provide the classification of hazard of contents per NFPA 101, of the FFPC (2020) 42.1.5 4. Not accepted, Please remove the term Temporary from the fire extinguisher locations as the travel distance must be maintained. Maximum Travel distance to extinguishers exceeded per FFPC 1, 13.6.3.2.1.2.2 5. Please acknowledge in comment letter. Please acknowledge that the following note was added to the permit: SEPARATE PERMITS REQUIRED FOR ALL FIRE SPRINKLERS, FIRE ALARMS/NOTIFICATION, FIRE SUPPRESSION, HOOD SUPPRESSION SUYSTEMS, AND FIRE UNDERGROUND WORK BY CONTRACTORS LICENSED FOR THE SCOPE OF WORK ACCORDING TO FLORIDA STATUTES CHAPTER 633. PLANS PREPARED BY A FLORIDA LICENSED PROFESSIONAL AS WELL AS ANY SYSTEM LAYOUT PLANS SHALL BE SUBMITTED WITH EACH PERMIT. ALLOW SUFFICIENT TIME FOR PLAN REVIEW AND PLAN APPROVAL. NO WORK SHALL BE STARTED, COVERED OR OTHERWISE CONCEALED FROM VIEW UNTIL APPROVED SEPARATE PERMITS MAY BE REQUIRED FOR BDA, IN ORDER TO DETERMINE IF NEEDED PLEASE CONTACT JARRAD SHUPE (WITH FLAGLER COUNTY) AT: 386-313-4281 IN REGARDS TO GRID TESTING AND INSTALLATION OF BDA (BI-DIRECTIONAL ANTENNA) PER NFPA 1, SECTION 10.1 (7TH EDITION), NFPA 72 (2016), AND NFPA 1221 (2016). PERMIT IF REQUIRED WILL BE SUBMITTED THROUGH THE CITY OF PALM COAST
BLD HOLD 03/31/2023 04/18/2023
Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code-Building (FBCB), Florida Statutes (F.S.) and Florida Administrative Code (F.A.C.). 5. REPEAT COMMENT: Plan Sheet G-101 not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. 6. REPEAT COMMENT: Plan Sheet LS-100 not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. 10. REPEAT COMMENT: Plan Sheet A-4 not signed and sealed by a Florida licensed architect per F.S. 481 F.A.C. 16G1-16.005. 11. In addition to the above, the following plan sheets and / or information is missing: A. Complete exterior wall sections, from interior finish / surface through to exterior cladding and from foundation through to roof for each exterior wall type. B. REPEAT COMMENT: DOOR SCHEDULE ADDED TO PLAN SHEET A-1 BUT NO WINDOWS SCHEDULE AS REQUESTED. Window and door schedules. 12. REPEAT COMMENT: Permit Application: Provide electrical and plumbing contractors on permit application. 13. Roofing Product Approval Worksheet: Product Approval number (3775.1) for metal roof panels are for a different metal building manufacturer (Dean Steel Buildings) than the metal building proposed for this project (Apec). New comment: Revised Plan Sheet A-1 “First Floor Plan” not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. New comment: New Plan Sheet A-2 “Exterior Elevations” not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. New comment: New Plan Sheet A-3 “Sections and Details” not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. New comment: Revised Plan Sheet A-4 “Roof Plan” not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. New comment: New Plan Sheet “A-3” “Sections and Details indicates decorative veneer stone base mortared to gypsum base. What type of gypsum base? Exterior gypsum sheathing? Thickness? What are the fastening requirements for this veneer backing and gypsum base? Is there sufficient framing other than the steel building frame? What does the veneer manufacture require for adhered veneer installation? Where is the water resistive barrier? Where is the flashing between dissimilar materials (e.g. between the PBR panels and veneer? Is lathing required for mortar adhered veneer? Provide a complete wall section showing all elements of the exterior envelope as well as manufacturer’s specs., backing and attachment details.
FI1 HOLD 03/17/2023 03/21/2023
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM 1. The newly provided Code Analysis indicates a note stating the building is Non Sprinklered, Please change to Sprinklered as this building requires an NFPA 13 sprinkler system per FBC 7th edition section 903. 2. The code analysis shows storage as the occupancy, please indicate S-1 or S-2 for occupancy classification. 3. Code analysis reveals the occupancy as a storage occupancy, please provide the classification of hazard of contents per NFPA 101, of the FFPC (2020) 42.1.5 4. Maximum Travel distance to extinguishers exceeded per FFPC 1, 13.6.3.2.1.2.2 5. Please acknowledge that the following note was added to the permit: SEPARATE PERMITS REQUIRED FOR ALL FIRE SPRINKLERS, FIRE ALARMS/NOTIFICATION, FIRE SUPPRESSION, HOOD SUPPRESSION SUYSTEMS, AND FIRE UNDERGROUND WORK BY CONTRACTORS LICENSED FOR THE SCOPE OF WORK ACCORDING TO FLORIDA STATUTES CHAPTER 633. PLANS PREPARED BY A FLORIDA LICENSED PROFESSIONAL AS WELL AS ANY SYSTEM LAYOUT PLANS SHALL BE SUBMITTED WITH EACH PERMIT. ALLOW SUFFICIENT TIME FOR PLAN REVIEW AND PLAN APPROVAL. NO WORK SHALL BE STARTED, COVERED OR OTHERWISE CONCEALED FROM VIEW UNTIL APPROVED SEPARATE PERMITS MAY BE REQUIRED FOR BDA, IN ORDER TO DETERMINE IF NEEDED PLEASE CONTACT JARRAD SHUPE (WITH FLAGLER COUNTY) AT: 386-313-4281 IN REGARDS TO GRID TESTING AND INSTALLATION OF BDA (BI-DIRECTIONAL ANTENNA) PER NFPA 1, SECTION 10.1 (7TH EDITION), NFPA 72 (2016), AND NFPA 1221 (2016). PERMIT IF REQUIRED WILL BE SUBMITTED THROUGH THE CITY OF PALM COAST
PLUM COMPLETE 03/17/2023 03/28/2023
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM
ELEC COMPLETE 03/17/2023 03/20/2023
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
MECH CANCEL 03/17/2023 03/20/2023
BLD HOLD 03/17/2023 03/28/2023
Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code-Building (FBCB), Florida Statutes (F.S.) and Florida Administrative Code (F.A.C.). WARNING: BUILDING CODE PLAN REVIEW COULD NOT BE COMPLETED (2ND TIME). PLAN SUBMITTAL IS INCOMPLETE AND LACKING REQUIRED PLAN SHEETS, DETAILS AND DESIGN INFORMATION NECESSARY FOR A COMPLETE REVIEW. YOU ARE ADVISED A MEETING WITH THE PROJECT ARCHITECT AND CONTRACTOR MAY BE BENEFICIAL TO ENSURE NECESSARY INFORMATION IS PROVIDED AT NEXT SUBMITTAL SO A COMPLETE REVIEW CAN BE PERFORMED AND THAT REVIEW RESULTS IN ISSUANCE OF A BUILDING PERMIT. 1. Plan Sheet G-100 not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. 2. Plan Sheet G-100 includes a "Drawing List" of plan sheets. The following plan sheets were not submitted for review: A-2 First Floor Plan, A-3 Ceiling Plan, M-3 HVAC Floor Plan and RENT-1 Leasing Plan. This is an incomplete submittal. Plan review cannot be completed. 3. In addition to the missing plan sheets identified above, it is likely additional mechanical plan sheets other than M-3 HVAC Floor Plan are missing. Where is M-1? M-2? Are there other mechanical plan sheets missing? Note: if no mechanical work is intended under this shell permit then remove reference to Plan Sheet M-3. 4. Plan Sheet G-100 does not provide a complete list of Drawings or Plans. The architect of record is obligated to provide a complete list / index of plans per F.A.C. 61G1-16.003. The following plan sheets have been omitted from the list: Plan Sheet F001 Notes & Foundation Details, Plan Sheet F002 Foundation Plan, Plan Sheet P0.1 Plumbing General Information, Plan Sheet P1.1 Sanitary Plan, Plan Sheet P2.1 Domestic Water Plan, Plan Sheet 3.1 Riser Diagrams, Plan Sheet E0.1 Electrical Legend and Specifications (mis-labeled on Drawing List), Plan Sheet E0.2 Electrical Site Plan, Plan Sheet E0.3 Site Photometrics Plan, Plan Sheet E0.4 Lighting Details, Plan Sheet E1.1 Electrical Plan, Plan Sheet E1.2 Lighting Plan. 5. Plan Sheet G-101 not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. File is corrupted and a majority of printed text is illegible. No review completed. 6. Plan Sheet LS-100 not signed and sealed by a Florida licensed architect per F.S. 481 and F.A.C. 16G1-16.005. 7. Plan Sheet LS-100 contains incomplete code analysis information. Provide the following: A. Under Applicable Codes section, add 2020 Florida Building Code-Mechanical, 2020 Florida Building Code-Mechanical, 2020 Florida Building Code-Energy Conservation, 2017 National Electric Code. B. Under Use and Occupancy Classification provide complete reference to storage occupancy type. Per FBCB Section 311.1, indicate whether proposed occupancy is S-1 Moderate Hazard Storage per Section 311.2 or S-2 Low Hazard Storage per Section 311.3. 8. Under Building Height and Area provide the following: A. Actual number of stories based on proposed occupancy and construction type vs. Allowable number of stories based on proposed occupancy and construction type. FBCB Section 504. B. Allowable floor area based on proposed occupancy and construction type. (note: as shown, actual floor area exceeds allowable floor area for non-sprinkled S-1 Moderate Hazard Storage building of Type IIB construction. Please reconcile actual area vs. allowable area. See FBCB Sections 503, 504, and 506. 9. Plan Sheet A1 has been rejected by the Building Division and will not be reviewed and shall not be a part of any approved plans by the City. A foundation plan (Plan Sheets F001, F002) prepared by a Florida licensed professional engineer has been previously submitted and is controlling. 10. Plan Sheet A-4 not signed and sealed by a Florida licensed architect per F.S. 481 F.A.C. 16G1-16.005. 11. In addition to the above, the following plan sheets and / or information is missing: A. Complete exterior wall sections, from interior finish / surface through to exterior cladding and from foundation through to roof for each exterior wall type. B. Window and door schedules. C. Gutters and downspout sizing, materials, locations. Metal building manufacturer specifies gutters but not capacity. Capacity (sizing) must be determined in accordance with the Florida Building Code-Plumbing per FBCB Section 1514.4.3. 12. Permit Application: Provide electrical and plumbing contractors on permit application. 13. Roofing Product Approval Worksheet: Product Approval number (3775.1) for metal roof panels are for a different metal building manufacturer (Dean Steel Buildings) than the metal building proposed for this project (Apec).
ARCHR COMPLETE 03/17/2023 03/31/2023
Note: Released By: RICHARD PICATAGI - (386)986-3760 - RPICATAGI@PALMCOASTGOV.COM
ARCHR HOLD 02/17/2023 03/06/2023
Note: Held By: RICHARD PICATAGI - (386)986-3760 - RPICATAGI@PALMCOASTGOV.COM Applicant must provided exterior facade colors and accent colors in the building plans including color name, index # and LRV
BLD HOLD 02/17/2023 03/06/2023
Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM Incomplete plan submittal. No plan review performed. Provide all architectural plan sheets signed and sealed by a Florida licensed architect. Provide all MEP plan sheets signed and sealed by a Florida licensed professional engiener. Provide all associated, supporting documents such as Florida PRoduct Approval Number worksheet, Palm Coast Roofing Worksheet, Revise permit application to include all MEP sub-contractors.
DSD COMPLETE 02/17/2023 02/21/2023
Note: Released By: JACQUELINE GONZALEZ - (386)986-3751 - JGONZALEZ@PALMCOASTGOV.COM
ELEC CANCEL 02/17/2023 02/24/2023
FI1 HOLD 02/17/2023 02/24/2023
Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM Please provide a written response to each comment below in a response letter, provide clouded response changes on plan sheets and add page locations for each response. 1. Please include FFPC 7th edition in the code analysis 2. Please include FBC 7th edition in the code analysis 3. Please provide a code analysis and be sure to include, Use and occupancy classification per FBC chapter 3, General building heights and area per FBC chapter 5, and Types of construction per FBC chapter 6,
MECH CANCEL 02/17/2023 02/21/2023
Note: not needed
PLUM HOLD 02/17/2023 03/06/2023
Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM Provide complete plumbing plans for potable water distribution sytem and drain, waste, vent system. Include all plumbing fixtures specifrications, water pipe and sanitary drainage materials specifcations, isometric drawings, pipe sizes, etc.
UD1 COMPLETE 02/17/2023 03/02/2023
Note: Released By: BRICE WRIGHT - -

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADJUSTMENT 50% (¤902.50) 05/05/2023
ADMINISTRATIVE - COMMERCIAL ¤75.00 05/05/2023
INSPECTION COMMERCIAL ¤1,400.00 05/05/2023
INSPECTION - FIRE COMMERCIAL ¤50.00 05/05/2023
PLAN REVIEW - COMMERCIAL ¤280.00 05/05/2023
FC IMPACT FEE EMS ¤68.00 05/05/2023
FC IMPACT FEE EMS ¤111.00 05/05/2023
IMPACT FEE FIRE ¤11,560.00 05/05/2023
IMPACT FEE FIRE ¤2,040.00 05/05/2023
FC IMPACT FEE LAW ENFORCEMENT ¤426.00 05/05/2023
FC IMPACT FEE LAW ENFORCEMENT ¤272.00 05/05/2023
IMPACT FEE TRANSPORTATION ¤12,015.00 05/05/2023
IMPACT FEE TRANSPORTATION ¤8,075.00 05/05/2023
SURCHARGE FS 533.721 ¤9.56 05/05/2023
SURCHARGE - FS 468.631 ¤14.35 05/05/2023
SITE PLAN 30 ¤30.00 05/05/2023
Fees Total Due: ¤0.00 Total Paid: ¤35,523.41