I want to search for...
Permit #2023050052
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7002-00010-0250 |
| Block: 00010 |
| Subdivision: 2218 - SECTION 2-FLORIDA PARK |
| Job Phone: 719-717-0211 |
| Location Address: 49 FARRADAY LN |
| Type: EL - ELECTRICAL |
| Issue Date: 05/05/2023 |
| NOC: Unknown |
| Applicant name: JOHN THOMAS BONACCORSO |
| Owner: SHONER RENEE S & ROBIN R SHONER H&W |
|
Address 49 FARRADAY LN PALM COAST, FL 32137 |
| Lot: 0250 |
| Contracted Stated Job Value: ¤2,000.00 |
| Job Description: ELEC SERVICE CHANGE 200A |
| Type: CN |
Contractor
BONACCORSO ELECTRIC SERVICE TECHNOLOGY LLC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
62 FOREST HILL DR PALM COAST, FL 32137 |
EC0002298 (Exp: 08/31/2026) | 719-717-0211 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 09/05/2023 | FINAL APPROVED | AGAETANO |
| Note: 8/29/2023 11:51:23 AM- PREVIOUS INSPECTION NOTES City Hall and City Facilities will be closed Wednesday August 30th. Inspections will not be performed Wednesday; August 30th. Inspections scheduled for Wednesday will cancelled. Please reschedule when you are ready for the inspection. Please be advised, if our community experiences damage, Building Inspectors priority will be providing damage assessment of the area and inspections will be postponed. Please monitor your emails to stay informed. 8/16/2023 - PREVIOUS INSPECTION NOTES 8/16/23 Ground wire goes up into service conduit @ meter main, but comes out inside main electrical panel in branch circuit conduit. Ground must run entire length inside feeder conduit 7/21/2023 - PREVIOUS INSPECTION NOTES 7/21/23 Need to have service ground inside service conduit going through attic not in seperate conduit per NEC 250 and NEC 300.3B 7/20/2023 - PREVIOUS INSPECTION NOTES 6/23/2023 - PREVIOUS INSPECTION NOTES 06-23-2023 Contractor not ready and will reschedule when complete. 07-20-2023 Contractor not ready. | |||
| ELECTRIC FINAL | 08/30/2023 | CANCELLED BY APPLICANT | BBEMBRY |
| Note: City Hall and City Facilities will be closed Wednesday August 30th. Inspections will not be performed Wednesday; August 30th. Inspections scheduled for Wednesday will cancelled. Please reschedule when you are ready for the inspection. Please be advised, if our community experiences damage, Building Inspectors priority will be providing damage assessment of the area and inspections will be postponed. Please monitor your emails to stay informed. 8/16/2023 - PREVIOUS INSPECTION NOTES 8/16/23 Ground wire goes up into service conduit @ meter main, but comes out inside main electrical panel in branch circuit conduit. Ground must run entire length inside feeder conduit 7/21/2023 - PREVIOUS INSPECTION NOTES 7/21/23 Need to have service ground inside service conduit going through attic not in seperate conduit per NEC 250 and NEC 300.3B 7/20/2023 - PREVIOUS INSPECTION NOTES 6/23/2023 - PREVIOUS INSPECTION NOTES 06-23-2023 Contractor not ready and will reschedule when complete. 07-20-2023 Contractor not ready. | |||
| ELECTRIC SERVICE CHANGE | 08/24/2023 | CANCELLED BY APPLICANT | WEB |
| ELECTRIC FEEDER | 08/24/2023 | CANCELLED BY APPLICANT | WEB |
| ELECTRIC FINAL | 08/16/2023 | Disapproved -FEE REQUIRED | MKRASKI |
| Note: 8/16/23 Ground wire goes up into service conduit @ meter main, but comes out inside main electrical panel in branch circuit conduit. Ground must run entire length inside feeder conduit 7/21/2023 - PREVIOUS INSPECTION NOTES 7/21/23 Need to have service ground inside service conduit going through attic not in seperate conduit per NEC 250 and NEC 300.3B 7/20/2023 - PREVIOUS INSPECTION NOTES 6/23/2023 - PREVIOUS INSPECTION NOTES 06-23-2023 Contractor not ready and will reschedule when complete. 07-20-2023 Contractor not ready. | |||
| ELECTRIC FINAL | 07/21/2023 | Disapproved - NO FEE | RMARTIN |
| Note: 7/21/23 Need to have service ground inside service conduit going through attic not in seperate conduit per NEC 250 and NEC 300.3B 7/20/2023 - PREVIOUS INSPECTION NOTES 6/23/2023 - PREVIOUS INSPECTION NOTES 06-23-2023 Contractor not ready and will reschedule when complete. 07-20-2023 Contractor not ready. | |||
| ELECTRIC FINAL | 07/20/2023 | Disapproved - NO FEE | AGAETANO |
| Note: 6/23/2023 - PREVIOUS INSPECTION NOTES 06-23-2023 Contractor not ready and will reschedule when complete. 07-20-2023 Contractor not ready. | |||
| ELECTRIC FINAL | 06/23/2023 | Disapproved - NO FEE | AGAETANO |
| Note: 06-23-2023 Contractor not ready and will reschedule when complete. |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 05/01/2023 | 05/01/2023 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 08/24/2023 |
| SURCHARGE FS 533.721 | ¤2.00 | 05/05/2023 |
| SURCHARGE - FS 468.631 | ¤2.00 | 05/05/2023 |
| ADJUSTMENT 50% | (¤61.25) | 05/05/2023 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 05/05/2023 |
| INSPECTION- ELECTRICAL | ¤60.00 | 05/05/2023 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 05/05/2023 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤105.25 |