Permit #2023050052

Permit Details

Status: FINAL

Parcel Id: 07-11-31-7002-00010-0250
Block: 00010
Subdivision: 2218 - SECTION 2-FLORIDA PARK
Job Phone: 719-717-0211
Location Address: 49 FARRADAY LN
Type: EL - ELECTRICAL
Issue Date: 05/05/2023
NOC: Unknown
Applicant name: JOHN THOMAS BONACCORSO
Owner: SHONER RENEE S & ROBIN R SHONER H&W

Address

49 FARRADAY LN

PALM COAST, FL 32137

Lot: 0250
Contracted Stated Job Value: ¤2,000.00
Job Description: ELEC SERVICE CHANGE 200A
Type: CN

Contractor

BONACCORSO ELECTRIC SERVICE TECHNOLOGY LLC
Status Location Address State License Number Phone
ACTIVE

62 FOREST HILL DR

PALM COAST, FL 32137

EC0002298 (Exp: 08/31/2026) 719-717-0211

Inspection History

Type Request Date Result Inspector
ELECTRIC FINAL 09/05/2023 FINAL APPROVED AGAETANO
Note: 8/29/2023 11:51:23 AM- PREVIOUS INSPECTION NOTES City Hall and City Facilities will be closed Wednesday August 30th. Inspections will not be performed Wednesday; August 30th. Inspections scheduled for Wednesday will cancelled. Please reschedule when you are ready for the inspection. Please be advised, if our community experiences damage, Building Inspectors priority will be providing damage assessment of the area and inspections will be postponed. Please monitor your emails to stay informed. 8/16/2023 - PREVIOUS INSPECTION NOTES 8/16/23 Ground wire goes up into service conduit @ meter main, but comes out inside main electrical panel in branch circuit conduit. Ground must run entire length inside feeder conduit 7/21/2023 - PREVIOUS INSPECTION NOTES 7/21/23 Need to have service ground inside service conduit going through attic not in seperate conduit per NEC 250 and NEC 300.3B 7/20/2023 - PREVIOUS INSPECTION NOTES 6/23/2023 - PREVIOUS INSPECTION NOTES 06-23-2023 Contractor not ready and will reschedule when complete. 07-20-2023 Contractor not ready.
ELECTRIC FINAL 08/30/2023 CANCELLED BY APPLICANT BBEMBRY
Note: City Hall and City Facilities will be closed Wednesday August 30th. Inspections will not be performed Wednesday; August 30th. Inspections scheduled for Wednesday will cancelled. Please reschedule when you are ready for the inspection. Please be advised, if our community experiences damage, Building Inspectors priority will be providing damage assessment of the area and inspections will be postponed. Please monitor your emails to stay informed. 8/16/2023 - PREVIOUS INSPECTION NOTES 8/16/23 Ground wire goes up into service conduit @ meter main, but comes out inside main electrical panel in branch circuit conduit. Ground must run entire length inside feeder conduit 7/21/2023 - PREVIOUS INSPECTION NOTES 7/21/23 Need to have service ground inside service conduit going through attic not in seperate conduit per NEC 250 and NEC 300.3B 7/20/2023 - PREVIOUS INSPECTION NOTES 6/23/2023 - PREVIOUS INSPECTION NOTES 06-23-2023 Contractor not ready and will reschedule when complete. 07-20-2023 Contractor not ready.
ELECTRIC SERVICE CHANGE 08/24/2023 CANCELLED BY APPLICANT WEB
ELECTRIC FEEDER 08/24/2023 CANCELLED BY APPLICANT WEB
ELECTRIC FINAL 08/16/2023 Disapproved -FEE REQUIRED MKRASKI
Note: 8/16/23 Ground wire goes up into service conduit @ meter main, but comes out inside main electrical panel in branch circuit conduit. Ground must run entire length inside feeder conduit 7/21/2023 - PREVIOUS INSPECTION NOTES 7/21/23 Need to have service ground inside service conduit going through attic not in seperate conduit per NEC 250 and NEC 300.3B 7/20/2023 - PREVIOUS INSPECTION NOTES 6/23/2023 - PREVIOUS INSPECTION NOTES 06-23-2023 Contractor not ready and will reschedule when complete. 07-20-2023 Contractor not ready.
ELECTRIC FINAL 07/21/2023 Disapproved - NO FEE RMARTIN
Note: 7/21/23 Need to have service ground inside service conduit going through attic not in seperate conduit per NEC 250 and NEC 300.3B 7/20/2023 - PREVIOUS INSPECTION NOTES 6/23/2023 - PREVIOUS INSPECTION NOTES 06-23-2023 Contractor not ready and will reschedule when complete. 07-20-2023 Contractor not ready.
ELECTRIC FINAL 07/20/2023 Disapproved - NO FEE AGAETANO
Note: 6/23/2023 - PREVIOUS INSPECTION NOTES 06-23-2023 Contractor not ready and will reschedule when complete. 07-20-2023 Contractor not ready.
ELECTRIC FINAL 06/23/2023 Disapproved - NO FEE AGAETANO
Note: 06-23-2023 Contractor not ready and will reschedule when complete.

Review History

Department Status Date In Date Out
ELEC COMPLETE 05/01/2023 05/01/2023
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 08/24/2023
SURCHARGE FS 533.721 ¤2.00 05/05/2023
SURCHARGE - FS 468.631 ¤2.00 05/05/2023
ADJUSTMENT 50% (¤61.25) 05/05/2023
ADMINISTRATIVE RESIDENTIAL ¤30.00 05/05/2023
INSPECTION- ELECTRICAL ¤60.00 05/05/2023
PLAN REVIEW - MISC 32.50 ¤32.50 05/05/2023
Fees Total Due: ¤0.00 Total Paid: ¤105.25