I want to search for...
Permit #2023050414
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7004-00090-0090 |
| OPENED PORCH (WITH ROOF) : 237 sqft |
| Total Square Footage: 237 sqft |
| Block: 00090 |
| Subdivision: 2203 - SECTION 4-COUNTRY CLUB COVE |
| Job Phone: (386)445-9424 |
| Location Address: 18 CLAYMONT CT N |
| Type: BA - BUILDING ADDITION |
| Issue Date: 05/09/2023 |
| NOC: Unknown |
| Applicant name: JOSE LOPEZ |
| Owner: TURNER, SCOTT & SARA |
|
Address 18 CLAYMONT CT N PALM COAST, FL 32137 |
| Lot: 0090 |
| Contracted Stated Job Value: ¤100.00 |
| Job Description: BUILDING ADDITION REF# 2021100150 |
| Type: CN |
| Original Permit #: 2021100150 |
Contractor
JOSE LOPEZ CONSTRUCTION, INC.
| Status | Location Address | State License Number | Phone |
| ACTIVE |
14 UTILITY DRIVE #12 BUNNELL, FL 32110 |
CRC1327719 (Exp: 08/31/2026) | (386)445-9424 |
Inspection History
| Type | Request Date | Result | Inspector |
| BLD - BUILDING FINAL | 09/01/2022 | FINAL APPROVED | AGAETANO |
| ROW - FINAL INSPECTION | 09/01/2022 | Disapproved -FEE REQUIRED | RGROSS |
| Note: Sod needed in the bare earth area on the left side of the driveway in the ROW. Seed and straw needed on the bare earth area near the right front corner of the house. | |||
| U -UTILITY RESIDENTIAL FINAL | 09/01/2022 | FINAL APPROVED | DHANEY |
| STEM WALL FOUNDATION | 08/31/2022 | APPROVED | DCUSHING |
| Note: THIS IS A REINSPECTION Tried calling contractor. Need clarification of stem wall foundation. Stem wall has been completed. | |||
| STEM WALL FOUNDATION | 08/29/2022 | Disapproved - NO FEE | AGAETANO |
| Note: Tried calling contractor. Need clarification of stem wall foundation. Stem wall has been completed. | |||
| INSULATION | 04/18/2022 | APPROVED | AGAETANO |
| ALL ROUGH | 04/14/2022 | APPROVED | AGAETANO |
| Note: THIS IS A REINSPECTION Grounding wires not connected at the exterior roof ceiling area. | |||
| WALL SHEATHING | 04/14/2022 | APPROVED | AGAETANO |
| Note: THIS IS A REINSPECTION Gable sheathing not nailed completely to the framing members. | |||
| WALL SHEATHING | 04/13/2022 | Disapproved - NO FEE | AGAETANO |
| Note: Gable sheathing not nailed completely to the framing members. | |||
| ALL ROUGH | 04/13/2022 | Disapproved - NO FEE | AGAETANO |
| Note: Grounding wires not connected at the exterior roof ceiling area. | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 04/07/2022 | APPROVED | AGAETANO |
| MONOLITHIC SLAB | 03/07/2022 | APPROVED | LMILLER |
| FOOTER | 01/18/2022 | APPROVED | AGAETANO |
Review History
| Department | Status | Date In | Date Out |
| PLFM | COMPLETE | 04/21/2022 | 04/21/2022 |
| Note: Released By: JORDAN MYERS, C.F.M - (386)986-2320 - JMYERS@PALMCOASTGOV.COM Screen enclosure is not part of the livable structure, no elevation certificates will be required. | |||
| BLD | COMPLETE | 11/16/2021 | 11/17/2021 |
| Note: Released By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM | |||
| SW1 | COMPLETE | 11/16/2021 | 11/19/2021 |
| Note: Released By: GABRIEL BERTOLA - (386)225-3840 - GBERTOLA@PALMCOASTGOV.COM | |||
| BLD | HOLD | 11/01/2021 | 11/02/2021 |
| Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code-Building PLAN REVIEW COMMENTS: 1. OK 2. Proposed stairs are shown. Provide handrails per R311.7.8 and guards per R312. (Repeat Comment) 3. OK 4. Previous plans show 2 x 4 ceiling joist at 24 inches. Revised show 2 x 12 LVL. Are LVL’s to be used as Ceiling Joist or will the 2 x 4 be used? Provide size and spacing of proposed ceiling joist. 5. Simpson HUC410Z is called-out to attach proposed beam to existing structure. Per the manufacture, this connector is to be used with (4) 2 x 10’s. Plans call for (2) 2 x 12. Revise the connector for the type of proposed construction. (Repeat Comment) 6. Simpson H2.5 is called-out for Rafter to Ridge connector. As mentioned previously, this connector is not for this application. See the proposed manufacture for the correct connector required. 7. Section for post at roof, post and footing shows the proposed beam to notched into the post. As per previous comment, the notch is greater than 50 percent of the post. Resubmission calls for a Simpson HUC412. Per Simpson the HUC412 is mounted to the beam. Provide which is correct and revise plans to show the correct attachment method is to be used. | |||
| ZON | COMPLETE | 11/01/2021 | 11/02/2021 |
| Note: Released By: CINDY CHIRI-GONCALVES - - CGONCALVES@PALMCOASTGOV.COM | |||
| SW1 | HOLD | 11/01/2021 | 11/08/2021 |
| Note: Held By: ROBERT GROSS - (386)986-4769 - RGROSS@PALMCOASTGOV.COM See Checklist in attachments dated 11/8/21 for highlighted items that need corrected on the site plan to be approved by storm water. | |||
| BLD | HOLD | 10/06/2021 | 10/07/2021 |
| Note: Held By: HAROLD ALLEN - (386)986-2357 - HALLEN@PALMCOASTGOV.COM All comments below per the 2020 Florida Building Code-Building PLAN REVIEW COMMENTS: 1. Provide a completed City of Palm Coast Roofing Worksheet. 2. Proposed stairs are shown. Provide handrails per R311.7.8 and guards per R312. 3. Provide Product Approval for the proposed vinyl soffit to be installed. 4. 2 x 4 ceiling joist are called-out. Maximum span for a 2 x 4 #2 Southern Yellow Pine celling joist is 6 foot 6 inches at 24 inches on center. 5. Simpson HUC410Z is called-out to attach proposed beam to existing structure. Per the manufacture, this connector is to be used with (4) 2 x 10’s. Plans call for (2) 2 x 12. Revise the connector for the type of proposed construction. 6. Simpson H2.5 is called-out for Rafter to Ridge connector. As mentioned previously, this connector is not for this application. See the proposed manufacture for the correct connector required. 7. Proposed post being notched more than 50 percent as well as a coil strap is called-out. Notching a post greater than 50 percent is prohibited. The proposed coil strap does not provide lateral support. | |||
| ELEC | COMPLETE | 10/06/2021 | 10/08/2021 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| MECH | CANCEL | 10/06/2021 | 10/07/2021 |
| Note: not needed | |||
| PLUM | CANCEL | 10/06/2021 | 10/07/2021 |
| SW1 | COMPLETE | 10/06/2021 | 10/12/2021 |
| Note: Released By: ROBERT GROSS - (386)986-4769 - RGROSS@PALMCOASTGOV.COM | |||
| ZON | HOLD | 10/06/2021 | 10/07/2021 |
| Note: Held By: CINDY CHIRI-GONCALVES - - CGONCALVES@PALMCOASTGOV.COM Please demonstrate that the 75% impervious maximum is not eceeded. Please provide the calculations. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 50% | (¤45.00) | 05/09/2023 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 05/09/2023 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 05/09/2023 |
| SURCHARGE FS 533.721 | ¤2.00 | 05/09/2023 |
| SURCHARGE - FS 468.631 | ¤2.00 | 05/09/2023 |
| SW ENG - INSPECTION 20 | ¤20.00 | 05/09/2023 |
| SW ENG REINSPECTION 20 | ¤20.00 | 05/09/2023 |
| SW ENG - REVIEW 20 | ¤20.00 | 05/09/2023 |
| SITE PLAN 30 | ¤30.00 | 05/09/2023 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤139.00 |