I want to search for...
Permit #2023051053
Permit Details
Status: FINAL
| Parcel Id: 22-11-30-0000-01030-0010 |
| Total Square Footage: 14052 sqft |
| Block: 01030 |
| Subdivision: - |
| Job Phone: (386)672-1950 |
| Location Address: 5625 US HWY 1 |
| Type: CM - COMMERCIAL MECHANICAL |
| Issue Date: 05/22/2023 |
| NOC: RECORDED |
| Applicant name: RICHARD LEE VONBROCKEN |
| Owner: CHRIST THE KING EVANGELICAL LUTHERAN CHURCH AND PR |
|
Address 5625 N US HIGHWAY 1 PALM COAST, FL 32164 |
| Lot: 0010 |
| Contracted Stated Job Value: ¤63,601.00 |
| Job Description: Replace (9) existing system with (9) new Carrier (1) 3, (3) 4, (5) 5 ton |
| Type: CN |
Contractor
VON-AIRE INC.
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
1738 STATE AVE HOLLY HILL, FL 32117 |
CAC035516 (Exp: 08/31/2026) | (386)672-1950 | (386)672-1952 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC OTHER | 08/09/2023 | CANCELLED BY INSPECTOR | CPISCITELLI |
| HVAC FINAL | 08/09/2023 | FINAL APPROVED | CPISCITELLI |
| Note: 7/19/2023 - PREVIOUS INSPECTION NOTES 1. Missing locking cap on F7-1 2. Leaking supply plenum on F4 3. Leaking return plenum on F7-3 4. All 5 ton AHU secondary drain pans are too small. Need 3 inches wider and longer than AHU. 5. Missing smoke detector AHU F6 (5Ton) | |||
| HVAC OTHER | 07/19/2023 | CANCELLED BY INSPECTOR | CPISCITELLI |
| HVAC FINAL | 07/19/2023 | Disapproved -FEE REQUIRED | CPISCITELLI |
| Note: 1. Missing locking cap on F7-1 2. Leaking supply plenum on F4 3. Leaking return plenum on F7-3 4. All 5 ton AHU secondary drain pans are too small. Need 3 inches wider and longer than AHU. 5. Missing smoke detector AHU F6 (5Ton) |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 05/22/2023 | 05/22/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| MECH | HOLD | 05/19/2023 | 05/19/2023 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide AHRI documents for different tonnage systems. 2. Provide fan data for 5 ton systems | |||
| ZON | COMPLETE | 05/19/2023 | 05/19/2023 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION - COMMERCIAL | ¤60.00 | 08/08/2023 |
| SURCHARGE FS 533.721 | ¤2.00 | 05/22/2023 |
| SURCHARGE - FS 468.631 | ¤2.00 | 05/22/2023 |
| SITE PLAN 15 | ¤15.00 | 05/22/2023 |
| ADJUSTMENT 50% | (¤83.75) | 05/22/2023 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 05/22/2023 |
| INSPECTION - MECHANICAL | ¤60.00 | 05/22/2023 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 05/22/2023 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤162.75 |