I want to search for...

Permit #2023060616

Permit Details

Status: COED

Parcel Id: 07-11-31-7009-00080-0160
CONDITIONED SPACE: 2283 sqft
GARAGE: 438 sqft
OPENED PORCH (WITH ROOF) : 197 sqft
Total Square Footage: 2918 sqft
Block: 00080
Subdivision: 2208 - SECTION 9-FLORIDA PARK
Job Phone: 386-445-9009
Location Address: 26 FARMDALE LN
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 06/26/2023
NOC: RECORDED
Applicant name: BRIAN ANDREW GAZZOLI
Owner: SEAGATE HOMES LLC

Address

185 CYPRESS POINT PARKWAY

PALM COAST, FL 32164

Lot: 0160
Contracted Stated Job Value: ¤315,000.00
Job Description: single family residence
Type: CN

Contractor

SEAGATE HOMES, LLC
Status Location Address Mailing Address State License Number Phone
ACTIVE

185 CYPRESS POINT PARKWAY

Palm Coast, FL 32137

SUITE 7

Palm Coast, FL 32137

CGC1518372 (Exp: 08/31/2026) 386-246-6132

Sub Contractors

ANDREW SCOTT DIGAETANO JR
Status Location Address State License Number Phone
ACTIVE

44 FORT CAROLINE

PALM COAST, FL 32137

CCC1331606 (Exp: 08/31/2026) 386-302-9063
RICHARD H SIMMONS JR
Status Location Address State License Number Phone Fax
ACTIVE

PO BOX 1963

BUNNELL, FL 32110

ES12001217 (Exp: 08/31/2026) 386-437-0607 386-437-1847
DENNIS GENE GAINEY
Status Location Address State License Number Phone Fax
INACTIVE

P.O. BOX 1203

Bunnell, FL 32110

CFC046004 (Exp: 08/31/2026) (386) 437-5637 386-437-3012
TIMUR ISPARYAN
Status Location Address State License Number Phone Fax
ACTIVE

3665 SPRINK PARK ROAD

JACKSONVILLE , FL 32207

CMC1249968 (Exp: 08/31/2026) 904-245-1818 904-337-1910

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 04/26/2024 FINAL APPROVED JWALKER
ROW - STORMWATER FINAL 04/25/2024 APPROVED EMADISON
Note: ** At the time of the inspection all minimum city requirements were met. It is the builder’s responsibility to ensure that nothing changes after this Inspection is approved.
U -UTILITY RESIDENTIAL FINAL 04/19/2024 FINAL APPROVED DHANEY
ROW - STORMWATER FINAL 04/19/2024 CANCELLED BY APPLICANT EMADISON
Note: Inspector Notes from Inspection 9465 4/18/24 CORRECTION MADE. DRAINAGE WILL WORK AS AS INDICATED. ADDITIONAL CORRECTIONS MAY BE REQUIRED BEFORE ROW FINAL PASSAGE DEPENDING ON FIELD CONDITIONS. ________________________________________________________________________________________________________________________ 4/9/2024 - PREVIOUS INSPECTION NOTES 4/9/24 YOUR SWALE ON THE LEFT SIDE FACING THE ROAD IS NOT CENTERD TO YOUR SLOPES. I HAVE PAINTED WHITE LINES WHERE THE CENTER OF THE BOTTOM OF THE SWALE SHOULD BE, 8' FROM EOP AS INDICATED IN THE COPC SWALE DIAGRAM. NEEDS TO BE CORRECTED.
U-CROSS CONNECTION 04/19/2024 APPROVED DHANEY
ROW - FINAL APRON (AFTER POUR) 04/19/2024 APPROVED EMADISON
Note: ** At the time of the inspection all minimum city requirements were met. It is the builders responsibility to ensure that nothing changes after this Inspection is approved.
ROW FIELD SURVEY /GRADING CERTIFICATION 04/18/2024 APPROVED - AS NOTED FSLADISH
Note: 4/18/24 CORRECTION MADE. DRAINAGE WILL WORK AS AS INDICATED. ADDITIONAL CORRECTIONS MAY BE REQUIRED BEFORE ROW FINAL PASSAGE DEPENDING ON FIELD CONDITIONS. ________________________________________________________________________________________________________________________ 4/9/2024 - PREVIOUS INSPECTION NOTES 4/9/24 YOUR SWALE ON THE LEFT SIDE FACING THE ROAD IS NOT CENTERD TO YOUR SLOPES. I HAVE PAINTED WHITE LINES WHERE THE CENTER OF THE BOTTOM OF THE SWALE SHOULD BE, 8' FROM EOP AS INDICATED IN THE COPC SWALE DIAGRAM. NEEDS TO BE CORRECTED.
ROW- FINAL SURVEY/GRADING CERTIFICATION 04/09/2024 APPROVED FSLADISH
ROW FIELD SURVEY /GRADING CERTIFICATION 04/09/2024 Disapproved - NO FEE FSLADISH
Note: 4/9/24 YOUR SWALE ON THE LEFT SIDE FACING THE ROAD IS NOT CENTERD TO YOUR SLOPES. I HAVE PAINTED WHITE LINES WHERE THE CENTER OF THE BOTTOM OF THE SWALE SHOULD BE, 8' FROM EOP AS INDICATED IN THE COPC SWALE DIAGRAM. NEEDS TO BE CORRECTED. PHOTO ENCLOSED FOR REFERENCE.
ROW- PRE-APRON (PRE-POUR) 02/28/2024 APPROVED GBERTOLA
Note: 2/28/24= AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. THIS INCLUDES BUT IS NOT LIMITED TO THE CULVERT PIPE ELEVATION APPROVAL FOR THE CONCRETE POUR 2/20/2024 - PREVIOUS INSPECTION NOTES ** 02/20/24 POUR SITE IS UNDER WATER AT THE TIME OF THIS INSPECTION ** BUILDER ALSO NEEDS TO EXTEND FORM BOARDS OR BACKFILL FORMS TO CONTAIN CONCRETE IN POUR AREA ** SEE ATTACHED PHOTOS ___________________________________________________________________________________________________________________ 2/15/2024 - PREVIOUS INSPECTION NOTES ** 02/15/24 CULVERT PITCHED IN THE WRONG DIRECTION BUILDER NEEDS TO REVIEW THE PROVIDED SWALE PLAN FOR THE THER DIRECTIONAL FLOW OF WATER. WHICH IS LEFT TO RIGHT ** HIGH SPOT IN CENTER OF DRIVEWAY STILL NEEDS TO BE LOWERED NEED A MINIMUM OF 4 INCHES OF CONCRETE IN DRIVEWAY POUR AREA. CHECK CENTER OF OUTLINED PAINTED AREA STRINGLINE IN PLACE ____________________________________________________________________________________________________________________ 2/6/2024 - PREVIOUS INSPECTION NOTES ** 02/06/24 SITE IS TOO WET TOO POUR CULVERT HAS TOO MUCH WATER IN POUR AREA ** MATERIAL AROUND THE CULVERT IS TOO SOFT FOOT SINKS APROXIMATELY 6-8 INCHES WATER AROUND CULVERT ** NOT ENOUGH MATERIAL AROUND CULVERT CULVERT NEEDS TO BE BURIED HALF WAY UP SEE CITY OF PALM COAST RESIDENTIAL CULVERT DETAIL DRAWING 300.E (ATTACHED IN PHOTOS) ** SEE ATTACHED PHOTOS
ROW- PRE-APRON (PRE-POUR) 02/20/2024 Disapproved -FEE REQUIRED EMADISON
Note: ** 02/20/24 POUR SITE IS UNDER WATER AT THE TIME OF THIS INSPECTION ** BUILDER ALSO NEEDS TO EXTEND FORM BOARDS OR BACKFILL FORMS TO CONTAIN CONCRETE IN POUR AREA ** SEE ATTACHED PHOTOS ___________________________________________________________________________________________________________________ 2/15/2024 - PREVIOUS INSPECTION NOTES ** 02/15/24 CULVERT PITCHED IN THE WRONG DIRECTION BUILDER NEEDS TO REVIEW THE PROVIDED SWALE PLAN FOR THE THER DIRECTIONAL FLOW OF WATER. WHICH IS LEFT TO RIGHT ** HIGH SPOT IN CENTER OF DRIVEWAY STILL NEEDS TO BE LOWERED NEED A MINIMUM OF 4 INCHES OF CONCRETE IN DRIVEWAY POUR AREA. CHECK CENTER OF OUTLINED PAINTED AREA STRINGLINE IN PLACE ____________________________________________________________________________________________________________________ 2/6/2024 - PREVIOUS INSPECTION NOTES ** 02/06/24 SITE IS TOO WET TOO POUR CULVERT HAS TOO MUCH WATER IN POUR AREA ** MATERIAL AROUND THE CULVERT IS TOO SOFT FOOT SINKS APROXIMATELY 6-8 INCHES WATER AROUND CULVERT ** NOT ENOUGH MATERIAL AROUND CULVERT CULVERT NEEDS TO BE BURIED HALF WAY UP SEE CITY OF PALM COAST RESIDENTIAL CULVERT DETAIL DRAWING 300.E (ATTACHED IN PHOTOS) ** SEE ATTACHED PHOTOS
ROW- PRE-APRON (PRE-POUR) 02/15/2024 Disapproved -FEE REQUIRED EMADISON
Note: ** 02/15/24 CULVERT PITCHED IN THE WRONG DIRECTION BUILDER NEEDS TO REVIEW THE PROVIDED SWALE PLAN FOR THE THER DIRECTIONAL FLOW OF WATER. WHICH IS LEFT TO RIGHT ** HIGH SPOT IN CENTER OF DRIVEWAY STILL NEEDS TO BE LOWERED NEED A MINIMUM OF 4 INCHES OF CONCRETE IN DRIVEWAY POUR AREA. CHECK CENTER OF OUTLINED PAINTED AREA STRINGLINE IN PLACE ____________________________________________________________________________________________________________________ 2/6/2024 - PREVIOUS INSPECTION NOTES ** 02/06/24 SITE IS TOO WET TOO POUR CULVERT HAS TOO MUCH WATER IN POUR AREA ** MATERIAL AROUND THE CULVERT IS TOO SOFT FOOT SINKS APROXIMATELY 6-8 INCHES WATER AROUND CULVERT ** NOT ENOUGH MATERIAL AROUND CULVERT CULVERT NEEDS TO BE BURIED HALF WAY UP SEE CITY OF PALM COAST RESIDENTIAL CULVERT DETAIL DRAWING 300.E (ATTACHED IN PHOTOS) ** SEE ATTACHED PHOTOS
ROW- PRE-APRON (PRE-POUR) 02/06/2024 Disapproved -FEE REQUIRED EMADISON
Note: ** 02/06/24 SITE IS TOO WET TOO POUR CULVERT HAS TOO MUCH WATER IN POUR AREA ** MATERIAL AROUND THE CULVERT IS TOO SOFT FOOT SINKS APROXIMATELY 6-8 INCHES WATER AROUND CULVERT ** NOT ENOUGH MATERIAL AROUND CULVERT CULVERT NEEDS TO BE BURIED HALF WAY UP SEE CITY OF PALM COAST RESIDENTIAL CULVERT DETAIL DRAWING 300.E (ATTACHED IN PHOTOS) ** SEE ATTACHED PHOTOS
ELECTRIC - EARLY POWER 01/26/2024 APPROVED - AS NOTED MKRASKI
Note: Emailed FPL @ 10:20
ELECTRIC - EARLY POWER 01/25/2024 Disapproved - NO FEE AGAETANO
Note: 01-25-2024 Doors locked . Need access for inspection.
INSULATION 12/15/2023 APPROVED FWILLIS
Note: 12/15/23 - 12/11/2023 - PREVIOUS INSPECTION NOTES 12/11/23: Previous deficiency not resolved. * Back left shower stall needs Fireblocking (1-1/2" min. for wood or 1/2 min. for cement board) across the top plate area of the chase/pack out wall. 12/6/2023 - PREVIOUS INSPECTION NOTES need fire blocking at case in back left shower
INSULATION 12/11/2023 Disapproved -FEE REQUIRED RSIMS
Note: 12/11/23: Previous deficiency not resolved. * Back left shower stall needs Fireblocking (1-1/2" min. for wood or 1/2 min. for cement board) across the top plate area of the chase/pack out wall. 12/6/2023 - PREVIOUS INSPECTION NOTES need fire blocking at case in back left shower
LATH/BRICK/ WATER BARRIER 12/07/2023 APPROVED FWILLIS
INSULATION 12/06/2023 Disapproved - NO FEE LMILLER
Note: need fire blocking at case in back left shower R302.11 (1-6)
ALL ROUGH 11/29/2023 APPROVED AGAETANO
ROOF VALLEY & METAL 11/21/2023 APPROVED AGAETANO
WALL SHEATHING 11/09/2023 APPROVED AGAETANO
Note: Inspector Notes from Inspection 2460 11-8-2023 Sheet 9.1 Gable end not installed per plan. Check at next inspection.
ROOF SHEATHING / BRACES/TIES/DOWN CELL 11/08/2023 APPROVED - AS NOTED AGAETANO
Note: 11-8-2023 Sheet 9.1 Gable end not installed per plan. Check at next inspection.
WALL SHEATHING 11/08/2023 Disapproved - NO FEE AGAETANO
Note: 11-8-2023 Wall sheathing not nailed. Check all.
FOUND SURVEY APPROVED (OFFICE) 10/20/2023 APPROVED TBAKER
TIE BEAM / LINTEL 10/18/2023 CANCELLED BY APPLICANT PBUCKLEY
Note: 10/16/2023 - PREVIOUS INSPECTION NOTES 10/12/2023 - PREVIOUS INSPECTION NOTES 10-12-2023 1. Front coulmn rebar not installed per plan. 2. Multiple rebar not proper clearance to CMU. Inspection stopped. 10-16-2023 1. Multiple dowels not proper clearance. 2. Front column not per plan. See 4.o 20 x 20" coulmns indicated and 16" x 16" installed.
TIE BEAM / LINTEL 10/17/2023 APPROVED AGAETANO
Note: 10/17/2023 10:11:31 AM- PREVIOUS INSPECTION NOTES 10/16/2023 - PREVIOUS INSPECTION NOTES 10/12/2023 - PREVIOUS INSPECTION NOTES 10-12-2023 1. Front coulmn rebar not installed per plan. 2. Multiple rebar not proper clearance to CMU. Inspection stopped.
TIE BEAM / LINTEL 10/16/2023 Disapproved -FEE REQUIRED AGAETANO
Note: 10/12/2023 - PREVIOUS INSPECTION NOTES 10-12-2023 1. Front coulmn rebar not installed per plan. 2. Multiple rebar not proper clearance to CMU. Inspection stopped. 10-16-2023 1. Multiple dowels not proper clearance. 2. Front column not per plan. See 4.o 20 x 20" coulmns indicated and 16" x 16" installed.
TIE BEAM / LINTEL 10/12/2023 Disapproved - NO FEE AGAETANO
Note: 10-12-2023 1. Front coulmn rebar not installed per plan. 2. Multiple rebar not proper clearance to CMU. Inspection stopped.
MONOLITHIC SLAB 09/19/2023 APPROVED AGAETANO
Note: 9/18/2023 - PREVIOUS INSPECTION NOTES 09-18-2023 1. Proper clearance not met with rebar. Check all areas. 2. Compaction test not on site. 3. Rebar not istalled at columns. Inspection stopped.
MONOLITHIC SLAB 09/18/2023 Disapproved - NO FEE AGAETANO
Note: 09-18-2023 1. Proper clearance not met with rebar. Check all areas. 2. Compaction test not on site. 3. Rebar not istalled at columns. Inspection stopped.
PLUMBING 1ST ROUGH UNDERGROUND 08/29/2023 APPROVED MGIBSON
GRAVITY SEWER TEST 08/29/2023 APPROVED MGIBSON
U - SEWER TIE IN 08/29/2023 APPROVED MGIBSON
WATER METER INSTALLATION REQUEST 08/10/2023 APPROVED CBOWERMASTER
Note: 8/1/2023 8:48:12 AM- PREVIOUS INSPECTION NOTES big dirt pile
WATER METER INSTALLATION REQUEST 07/31/2023 Disapproved -FEE REQUIRED CSTONE
Note: big dirt pile

Review History

Department Status Date In Date Out
ELEC COMPLETE 11/17/2023 11/28/2023
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ENGIN1 COMPLETE 10/19/2023 10/20/2023
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON COMPLETE 10/19/2023 10/19/2023
Note: Released By: LIBBY MUSGROVE - (386)986-3780 - LMUSGROVE@PALMCOASTGOV.COM
MECH COMPLETE 08/17/2023 08/21/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ELEC COMPLETE 06/23/2023 06/26/2023
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
SWALE COMPLETE 06/14/2023 07/26/2023
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
BLD COMPLETE 06/13/2023 06/15/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
CUSVC COMPLETE 06/13/2023 06/15/2023
Note: Released By: HALEIGH HAND - - HHAND@PALMCOASTGOV.COM
ELEC HOLD 06/13/2023 06/20/2023
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. . Need correct outlet spacing NEC 2017 210.52 Bed 3
ENGIN1 COMPLETE 06/13/2023 06/14/2023
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
GAS CANCEL 06/13/2023 06/13/2023
LOCATE COMPLETE 06/13/2023 06/15/2023
Note: Released By: CANDACE STONE - (386)986-2539 - CSTONE@PALMCOASTGOV.COM
MECH COMPLETE 06/13/2023 06/15/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
SW1 COMPLETE 06/13/2023 06/21/2023
Note: Released By: PARREN FLANAGAN - (386)986-2392 - PFLANAGAN@PALMCOASTGOV.COM
ZON COMPLETE 06/13/2023 06/13/2023
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
PLENV COMPLETE 06/13/2023 06/21/2023
Note: Released By: CAROL MINI - - CJMINI@PALMCOASTGOV.COM CJM 6/15/2023 No gopher tortoise burrows found. Staff recommends installing silt fence to keep gt's from entering the property.

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
CONTRACTOR CHANGE ¤20.00 04/26/2024
PLAN REVIEW - REVISION ¤32.50 04/26/2024
REINSPECTION RESIDENTIAL ¤40.00 04/26/2024
REINSPECTION RESIDENTIAL ¤40.00 04/26/2024
SW ENG REINSPECTION 30 ¤30.00 04/26/2024
SW ENG REINSPECTION 30 ¤30.00 04/26/2024
SW ENG REINSPECTION 30 ¤30.00 04/26/2024
SW ENG - REVIEW 20 ¤20.00 06/26/2023
SW ENG RES REVIEW 200 ¤200.00 06/26/2023
TRANS IMPACT FEE ADMIN ¤54.36 06/26/2023
TRANS IMPACT FEE ADMIN (¤54.36) 06/26/2023
SEWER CREDIT (¤1,147.00) 06/26/2023
SEWER INSPECTION ¤25.00 06/26/2023
SEWER CAPITAL FACILITY ¤5,344.82 06/26/2023
WATER CAPITAL FACILITY FEE ¤3,923.88 06/26/2023
SITE PLAN 30 ¤30.00 06/26/2023
CONNECTION FEES ¤1,166.26 06/26/2023
WATER- TURN ON ¤25.00 06/26/2023
ADJUSTMENT 50% (¤570.98) 06/26/2023
ADMINISTRATIVE RESIDENTIAL ¤30.00 06/26/2023
INSPECTION - RESIDENTIAL ¤866.25 06/26/2023
PLAN REVIEW - RESIDENTIAL ¤245.70 06/26/2023
FIRE IMPACT FEE ADMIN ¤12.62 06/26/2023
FIRE IMPACT FEE ADMIN (¤12.62) 06/26/2023
FC IMPACT FEE EMS ¤62.00 06/26/2023
IMPACT FEE FIRE ¤420.52 06/26/2023
FC IMPACT FEE LAW ENFORCEMENT ¤218.00 06/26/2023
FC IMPACT FEE LIBRARY ¤268.00 06/26/2023
IMPACT FEE PARKS ¤1,769.15 06/26/2023
IMPACT FEE SCHOOL ¤5,450.00 06/26/2023
IMPACT FEE TRANSPORTATION ¤1,812.00 06/26/2023
WATER -IRRIGATION INSPECTION ¤25.00 06/26/2023
PARKS IMPACT FEE ADMIN ¤53.07 06/26/2023
PARKS IMPACT FEE ADMIN (¤53.07) 06/26/2023
SURCHARGE FS 533.721 ¤5.71 06/26/2023
SURCHARGE - FS 468.631 ¤8.57 06/26/2023
SW ENG - FOUNDATION SURVEY ¤20.00 06/26/2023
SW ENG INSPECTION 80 ¤80.00 06/26/2023
SW ENG PRE APRON ¤30.00 06/26/2023
Fees Total Due: ¤0.00 Total Paid: ¤20,550.38