Permit #2023060808
Permit Details
Status: COED
| Parcel Id: 28-10-30-5415-00000-0350 |
| CONDITIONED SPACE: 2499 sqft |
| GARAGE: 422 sqft |
| OPENED PORCH (WITH ROOF) : 121 sqft |
| Total Square Footage: 3042 sqft |
| Subdivision: 2310 - SAWMILL BRANCH 2A |
| Job Phone: 904-219-3385 |
| Location Address: 16 HULETT WOODS RD |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 07/12/2023 |
| NOC: RECORDED |
| Applicant name: RAYMOND CLIVE CROSBY |
| Owner: DR HORTON, INC |
|
Address 4220 RACE TRACK RD ST JOHNS, FL 32259 |
| Lot: 35 |
| Contracted Stated Job Value: ¤248,900.00 |
| Job Description: SINGLE FAMILY |
| Type: CN |
Contractor
DR HORTON, INC.
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
4220 RACE TRACK RD SAINT JOHNS, FL 32259 |
CBC058997 (Exp: 08/31/2026) | 904-268-2845 | 904-899-5992 |
Sub Contractors
PAUL ERIC FORSTER
| Status | Location Address | State License Number | Phone |
| ACTIVE |
6114 GOODMAN RD JACKSONVILLE, FL 32244 |
CFC1429261 (Exp: 08/31/2026) | 904-647-1820 |
DANA SUE COOLEY
| Status | Location Address | State License Number | Phone |
| INACTIVE |
PO BOX 1718 FLAGLER BEACH, FL 32136 |
CCC1333449 (Exp: 08/31/2026) | 904-535-1680 |
JAMES M GREENSLADE
| Status | Location Address | State License Number | Phone | Fax |
| ACTIVE |
311 S BAY ST BUNNELL, FL 32110 |
EC13006083 (Exp: 08/31/2026) | 386-263-2960 | 386-263-2980 |
EDWARD DOUGLAS TENNANT
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
3370 AGRICULTURAL CENTER DRIVE ST. AUGUSTINE , FL 32092 |
CAC1813372 (Exp: 08/31/2026) | (904)829-8898 | (904)829-6587 |
Inspection History
| Type | Request Date | Result | Inspector |
| BLD - BUILDING FINAL | 03/01/2024 | FINAL APPROVED | KSANDOE |
| Note: 2/28/2024 - PREVIOUS INSPECTION NOTES 2/28/24- 1. Pleae seal exterior wall exhaust vent Left side.R402.4, OPENINGS 2. Please seal exterior wall penetration at irrigation conduit.R402.4, OPENINGS 3. Please seal hole at garage door bell transformer.R402.4, OPENINGS 4. Please seal Hole at cat 5 ceiling penetrationR402.4, OPENINGS 5. 1st floor bedroom Switchable light not working. FBC 450.3.15.2 6. Please seal arounf washer Pan discharge pipe at wall. 7. Please seal the Master bath counter top to the backsplash seam.P2705.1 – 3 | |||
| BLD - BUILDING FINAL | 02/28/2024 | Disapproved -FEE REQUIRED | JSTEWART |
| Note: 2/28/24- 1. Pleae seal exterior wall exhaust vent Left side.R402.4, OPENINGS 2. Please seal exterior wall penetration at irrigation conduit.R402.4, OPENINGS 3. Please seal hole at garage door bell transformer.R402.4, OPENINGS 4. Please seal Hole at cat 5 ceiling penetrationR402.4, OPENINGS 5. 1st floor bedroom Switchable light not working. FBC 450.3.15.2 6. Please seal arounf washer Pan discharge pipe at wall. 7. Please seal the Master bath counter top to the backsplash seam.P2705.1 – 3 | |||
| U-CROSS CONNECTION | 02/21/2024 | APPROVED | DHANEY |
| Note: 2/14/2024 - PREVIOUS INSPECTION NOTES Water meter pit full of dirt - needs cleaned for Insp. . | |||
| U -UTILITY RESIDENTIAL FINAL | 02/21/2024 | FINAL APPROVED | DHANEY |
| ROW FIELD SURVEY /GRADING CERTIFICATION | 02/20/2024 | APPROVED | GBERTOLA |
| Note: Since the house is already situated on a hill, the driveway has a 4% incline towards the road. AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. THIS INCLUDES BUT IS NOT LIMITED TO THE CULVERT PIPE ELEVATION APPROVAL FOR THE CONCRETE POUR. 2/8/2024 - PREVIOUS INSPECTION NOTES THE LEFT SIDE PROPERTY LINE NEEDS TO BE 2/1 SLOPE, IT’S TOO MUCH OF THE DROPP. CAN BE A HAZARDOUS CONDITION FOR THE HOMEOWNER DUE TO A DROOPING LINE THE SIDEWALK GOING INTO THE HOUSE CAN’T BE MORE THAN THE 2% ADA, AT THE TIME OF THE INSPECTION, IS 4.5% | |||
| ROW - STORMWATER FINAL | 02/20/2024 | APPROVED | GBERTOLA |
| Note: Since the house is already situated on a hill, the driveway has a 4% incline towards the road. AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. THIS INCLUDES BUT IS NOT LIMITED TO THE CULVERT PIPE ELEVATION APPROVAL FOR THE CONCRETE POUR. | |||
| ROW - FINAL APRON (AFTER POUR) | 02/20/2024 | APPROVED | GBERTOLA |
| Note: Since the house is already situated on a hill, the driveway has a 4% incline towards the road. AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. THIS INCLUDES BUT IS NOT LIMITED TO THE CULVERT PIPE ELEVATION APPROVAL FOR THE CONCRETE POUR. | |||
| U-CROSS CONNECTION | 02/14/2024 | Disapproved - NO FEE | DHANEY |
| Note: Water meter pit full of dirt - needs cleaned for Insp. . | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 02/08/2024 | APPROVED | GBERTOLA |
| Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. THIS INCLUDES BUT IS NOT LIMITED TO THE CULVERT PIPE ELEVATION APPROVAL FOR THE CONCRETE POUR. | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 02/08/2024 | Disapproved - NO FEE | GBERTOLA |
| Note: THE LEFT SIDE PROPERTY LINE NEEDS TO BE 2/1 SLOPE, IT’S TOO MUCH OF THE DROPP. CAN BE A HAZARDOUS CONDITION FOR THE HOMEOWNER DUE TO A DROOPING LINE THE SIDEWALK GOING INTO THE HOUSE CAN’T BE MORE THAN THE 2% ADA, AT THE TIME OF THE INSPECTION, IS 4.5% | |||
| U - SEWER TIE IN | 01/31/2024 | APPROVED - AS NOTED | MGIBSON |
| Note: THIS WAS A VIRTUAL INSPECTION | |||
| GRAVITY SEWER TEST | 01/31/2024 | APPROVED - AS NOTED | MGIBSON |
| Note: THIS WAS A VIRTUAL INSPECTION | |||
| ELECTRIC - EARLY POWER | 01/19/2024 | APPROVED | JSTEWART |
| Note: 1/18/2024 - PREVIOUS INSPECTION NOTES 1/18/24: House is locked up tight. Need access for Inspection. 1/17/2024 - PREVIOUS INSPECTION NOTES 1/17/24- Not ready, Electrician onsite. | |||
| ROW- PRE-APRON (PRE-POUR) | 01/19/2024 | APPROVED | TPOLACEK |
| Note: 01/19/24 AT THE TIME FROM THE TIME OF THE INSPECTION OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL BEFORE POURING. | |||
| ELECTRIC - EARLY POWER | 01/18/2024 | Disapproved - NO FEE | RSIMS |
| Note: 1/18/24: House is locked up tight. Need access for Inspection. 1/17/2024 - PREVIOUS INSPECTION NOTES 1/17/24- Not ready, Electrician onsite. | |||
| ELECTRIC - EARLY POWER | 01/17/2024 | Disapproved - NO FEE | JSTEWART |
| Note: 1/17/24- Not ready, Electrician onsite. | |||
| INSULATION | 12/21/2023 | APPROVED | RSIMS |
| Note: 12/20/2023 - PREVIOUS INSPECTION NOTES 12/20/23: Walked with Superintendent. * Still missing firestop in multiple locations. 12/19/2023 - PREVIOUS INSPECTION NOTES 12/19/23: 1). Firestop missing at 1st floor top plate penetration: right wall & back bedroom. Marked with FS on stud. 2). Missing firestop at all strap penetrations from 1st floor joist bays to 2nd floor. 3). Missing firestop behind stairwell right side.Marked with FS. 4). Missing firestop at 2nd floor front bathroom water lines through bottom plate. 5). Missing firestop at stairwell joist separation. 6). 2nd floor Plumbing & HVAC pipe chases: Fireblocking plywood at top plates does not meet the 1-1/2" minimum thickness as required. R302.11.1 Inspector Notes from Inspection 2420 12/14/23: Check at Insulation Inspection. 1). No water pressure. 2). Nail plates needed at double top plate for washer drain pan. 11/28/2023 - PREVIOUS INSPECTION NOTES 11/28/23: Cancelled by Applicant via text at @ 12:06. 10/11/2023 - PREVIOUS INSPECTION NOTES 10/11/23: Inspection stopped! Incomplete Inspection. ** Need revision submitted to & approved by the City for an Engineer's letter approving the EXCESSIVE cut out sections of @ 90% of the TJI floor joist trusses. other examples: ** Bathroom exhaust not sealed properly at the exterior wall / Wires not phased out / 5ft. head not holding. | |||
| INSULATION | 12/20/2023 | Disapproved -FEE REQUIRED | RSIMS |
| Note: 12/20/23: Walked with Superintendent. * Still missing firestop in multiple locations. 12/19/2023 - PREVIOUS INSPECTION NOTES 12/19/23: 1). Firestop missing at 1st floor top plate penetration: right wall & back bedroom. Marked with FS on stud. 2). Missing firestop at all strap penetrations from 1st floor joist bays to 2nd floor. 3). Missing firestop behind stairwell right side.Marked with FS. 4). Missing firestop at 2nd floor front bathroom water lines through bottom plate. 5). Missing firestop at stairwell joist separation. 6). 2nd floor Plumbing & HVAC pipe chases: Fireblocking plywood at top plates does not meet the 1-1/2" minimum thickness as required. R302.11.1 Inspector Notes from Inspection 2420 12/14/23: Check at Insulation Inspection. 1). No water pressure. 2). Nail plates needed at double top plate for washer drain pan. 11/28/2023 - PREVIOUS INSPECTION NOTES 11/28/23: Cancelled by Applicant via text at @ 12:06. 10/11/2023 - PREVIOUS INSPECTION NOTES 10/11/23: Inspection stopped! Incomplete Inspection. ** Need revision submitted to & approved by the City for an Engineer's letter approving the EXCESSIVE cut out sections of @ 90% of the TJI floor joist trusses. other examples: ** Bathroom exhaust not sealed properly at the exterior wall / Wires not phased out / 5ft. head not holding. | |||
| INSULATION | 12/19/2023 | Disapproved -FEE REQUIRED | RSIMS |
| Note: 12/19/23: 1). Firestop missing at 1st floor top plate penetration: right wall & back bedroom. Marked with FS on stud. 2). Missing firestop at all strap penetrations from 1st floor joist bays to 2nd floor. 3). Missing firestop behind stairwell right side.Marked with FS. 4). Missing firestop at 2nd floor front bathroom water lines through bottom plate. 5). Missing firestop at stairwell joist separation. 6). 2nd floor Plumbing & HVAC pipe chases: Fireblocking plywood at top plates does not meet the 1-1/2" minimum thickness as required. R302.11.1 Inspector Notes from Inspection 2420 12/14/23: Check at Insulation Inspection. 1). No water pressure. 2). Nail plates needed at double top plate for washer drain pan. 11/28/2023 - PREVIOUS INSPECTION NOTES 11/28/23: Cancelled by Applicant via text at @ 12:06. 10/11/2023 - PREVIOUS INSPECTION NOTES 10/11/23: Inspection stopped! Incomplete Inspection. ** Need revision submitted to & approved by the City for an Engineer's letter approving the EXCESSIVE cut out sections of @ 90% of the TJI floor joist trusses. other examples: ** Bathroom exhaust not sealed properly at the exterior wall / Wires not phased out / 5ft. head not holding. | |||
| ALL ROUGH | 12/14/2023 | APPROVED - AS NOTED | RSIMS |
| Note: 12/14/23: Check at Insulation Inspection. 1). No water pressure. 2). Nail plates needed at double top plate for washer drain pan. 11/28/2023 - PREVIOUS INSPECTION NOTES 11/28/23: Cancelled by Applicant via text at @ 12:06. 10/11/2023 - PREVIOUS INSPECTION NOTES 10/11/23: Inspection stopped! Incomplete Inspection. ** Need revision submitted to & approved by the City for an Engineer's letter approving the EXCESSIVE cut out sections of @ 90% of the TJI floor joist trusses. other examples: ** Bathroom exhaust not sealed properly at the exterior wall / Wires not phased out / 5ft. head not holding. | |||
| ALL ROUGH | 11/28/2023 | CANCELLED BY APPLICANT | RSIMS |
| Note: 11/28/23: Cancelled by Applicant via text at @ 12:06. 10/11/2023 - PREVIOUS INSPECTION NOTES 10/11/23: Inspection stopped! Incomplete Inspection. ** Need revision submitted to & approved by the City for an Engineer's letter approving the EXCESSIVE cut out sections of @ 90% of the TJI floor joist trusses. other examples: ** Bathroom exhaust not sealed properly at the exterior wall / Wires not phased out / 5ft. head not holding. | |||
| ALL ROUGH | 10/11/2023 | Disapproved -FEE REQUIRED | RSIMS |
| Note: 10/11/23: Inspection stopped! Incomplete Inspection. ** Need revision submitted to & approved by the City for an Engineer's letter approving the EXCESSIVE cut out sections of @ 90% of the TJI floor joist trusses. other examples: ** Bathroom exhaust not sealed properly at the exterior wall / Wires not phased out / 5ft. head not holding. | |||
| LATH/BRICK/ WATER BARRIER | 10/11/2023 | APPROVED | RSIMS |
| ELECTRIC-TUG | 10/04/2023 | APPROVED | RMARTIN |
| ROOF VALLEY & METAL | 09/21/2023 | APPROVED | JSTEWART |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 09/20/2023 | APPROVED | JSTEWART |
| Note: 9/12/2023 - PREVIOUS INSPECTION NOTES 1. Bottom plate to studs are missing SDWC 15450 2. Hold downs in front room are not tightened down 3. Job box needs to be cleaned up with full set of prints for inspector 4. SDWC screws that are installed are not installed per detail (ST-5 13) Stopped inspection not ready 9/6/23- Inspector verified 2 coil straps from 1st floor to 2nd floor at front Right corner ONLY. Okay to hang hardy wall board. | |||
| WALL SHEATHING | 09/20/2023 | APPROVED | JSTEWART |
| Note: 9/12/2023 - PREVIOUS INSPECTION NOTES Wall sheathing passed just need to check that both sides of garage wall returns are sheathed on both sides after tie down inspection | |||
| WALL SHEATHING | 09/12/2023 | PARTIALLY APPROVED | MKRASKI |
| Note: Wall sheathing passed just need to check that both sides of garage wall returns are sheathed on both sides after tie down inspection | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 09/12/2023 | Disapproved - NO FEE | MKRASKI |
| Note: 1. Bottom plate to studs are missing SDWC 15450 2. Hold downs in front room are not tightened down 3. Job box needs to be cleaned up with full set of prints for inspector 4. SDWC screws that are installed are not installed per detail (ST-5 13) Stopped inspection not ready 9/6/23- Inspector verified 2 coil straps from 1st floor to 2nd floor at front Right corner ONLY. Okay to hang hardy wall board. | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 09/06/2023 | CANCELLED BY APPLICANT | JSTEWART |
| Note: 9/6/23- Added a tie down inspection for 2 coil strap at front right corner 2nd floor to 1st floor, so Hardy wall board can be installed. | |||
| TIE DOWN | 09/06/2023 | APPROVED - AS NOTED | JSTEWART |
| Note: 9/6/23- Inspector verified 2 coil straps from 1st floor to 2nd floor at front Right corner ONLY. Okay to hang hardy wall board. | |||
| FOUND SURVEY APPROVED (OFFICE) | 08/17/2023 | APPROVED | TDOAK |
| MONOLITHIC SLAB | 08/11/2023 | APPROVED | FWILLIS |
| Note: 8/10/2023 - PREVIOUS INSPECTION NOTES 8/10/23: No Stamped Approved Plans in Permit Box laying against a pile of dirt. (FBC 107.3.1) | |||
| MONOLITHIC SLAB | 08/10/2023 | Disapproved -FEE REQUIRED | RSIMS |
| Note: 8/10/23: No Stamped Approved Plans in Permit Box laying against a pile of dirt. (FBC 107.3.1) | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 08/08/2023 | APPROVED | MGIBSON |
| WATER METER INSTALLATION REQUEST | 08/03/2023 | APPROVED | CBOWERMASTER |
Review History
| Department | Status | Date In | Date Out |
| BLD | COMPLETE | 12/07/2023 | 12/12/2023 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 12/04/2023 | 12/06/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| BLD | HOLD | 11/22/2023 | 11/28/2023 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Repair documents need to be signed and sealed by a Florida Licensed P.E. | |||
| ENGIN1 | COMPLETE | 08/17/2023 | 08/17/2023 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 08/17/2023 | 08/17/2023 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 07/10/2023 | 07/11/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| URB | COMPLETE | 06/16/2023 | 07/05/2023 |
| Note: Released By: JOHN BEAUDET - (386)986-2456 - JBEAUDET@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 06/15/2023 | 06/16/2023 |
| Note: Released By: JPI | |||
| CUSVC | COMPLETE | 06/15/2023 | 06/16/2023 |
| Note: Released By: HALEIGH HAND - - HHAND@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 06/15/2023 | 06/20/2023 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ENGIN1 | COMPLETE | 06/15/2023 | 06/15/2023 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| GAS | CANCEL | 06/15/2023 | 06/20/2023 |
| LOCATE | COMPLETE | 06/15/2023 | 06/20/2023 |
| Note: Released By: CANDACE STONE - (386)986-2539 - CSTONE@PALMCOASTGOV.COM | |||
| MECH | HOLD | 06/15/2023 | 06/20/2023 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Direction house faces on Heatload does not match the site plan. Revise to match per R405.4.2.1 FBC Energy Conservation 2020 7Th Edition | |||
| SW1 | COMPLETE | 06/15/2023 | 06/21/2023 |
| Note: Released By: PARREN FLANAGAN - (386)986-2392 - PFLANAGAN@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 06/15/2023 | 06/16/2023 |
| Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 02/29/2024 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 02/29/2024 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 02/29/2024 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 02/29/2024 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 02/29/2024 |
| CONNECTION FEES | ¤25.00 | 07/12/2023 |
| FIRE IMPACT FEE ADMIN | ¤12.62 | 07/12/2023 |
| FIRE IMPACT FEE ADMIN | (¤12.62) | 07/12/2023 |
| FC IMPACT FEE EMS | ¤62.00 | 07/12/2023 |
| IMPACT FEE FIRE | ¤420.52 | 07/12/2023 |
| FC IMPACT FEE LAW ENFORCEMENT | ¤218.00 | 07/12/2023 |
| FC IMPACT FEE LIBRARY | ¤268.00 | 07/12/2023 |
| IMPACT FEE PARKS | ¤1,769.15 | 07/12/2023 |
| IMPACT FEE SCHOOL | ¤5,450.00 | 07/12/2023 |
| IMPACT FEE TRANSPORTATION | ¤3,311.00 | 07/12/2023 |
| WATER -IRRIGATION INSPECTION | ¤25.00 | 07/12/2023 |
| PARKS IMPACT FEE ADMIN | ¤53.07 | 07/12/2023 |
| PARKS IMPACT FEE ADMIN | ¤53.07 | 07/12/2023 |
| SURCHARGE FS 533.721 | ¤5.43 | 07/12/2023 |
| SURCHARGE - FS 468.631 | ¤8.14 | 07/12/2023 |
| SW ENG - FOUNDATION SURVEY | ¤20.00 | 07/12/2023 |
| SW ENG INSPECTION 80 | ¤80.00 | 07/12/2023 |
| SW ENG PRE APRON | ¤30.00 | 07/12/2023 |
| SW ENG - REVIEW 20 | ¤20.00 | 07/12/2023 |
| SW ENG RES REVIEW 200 | ¤200.00 | 07/12/2023 |
| TRANS IMPACT FEE ADMIN | ¤99.33 | 07/12/2023 |
| TRANS IMPACT FEE ADMIN | (¤99.33) | 07/12/2023 |
| SEWER INSPECTION | ¤25.00 | 07/12/2023 |
| SEWER CAPITAL FACILITY | ¤2,803.23 | 07/12/2023 |
| WATER CAPITAL FACILITY FEE | ¤2,605.24 | 07/12/2023 |
| SITE PLAN 30 | ¤30.00 | 07/12/2023 |
| WATER-METER | ¤505.39 | 07/12/2023 |
| WATER-METER | ¤419.86 | 07/12/2023 |
| ADJUSTMENT 50% | (¤542.74) | 07/12/2023 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 07/12/2023 |
| INSPECTION - RESIDENTIAL | ¤822.25 | 07/12/2023 |
| PLAN REVIEW - RESIDENTIAL | ¤233.22 | 07/12/2023 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤19,149.83 |