I want to search for...
Permit #2023071013
Permit Details
Status: COED
| Parcel Id: 07-11-31-7029-00730-0160 |
| CONDITIONED SPACE: 1903 sqft |
| GARAGE: 435 sqft |
| OPENED PORCH (WITH ROOF) : 182 sqft |
| OPENED PORCH (WITH ROOF) : 70 sqft |
| Total Square Footage: 2590 sqft |
| Block: 00730 |
| Subdivision: 2209 - SECTION 29-ROYAL PALMS |
| Job Phone: 202-494-2019 |
| Location Address: 4 RYMEN LN |
| Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY |
| Issue Date: 09/08/2023 |
| NOC: RECORDED |
| Applicant name: GARY ANDREW FISCHER |
| Owner: INB FUND 2, LLC |
|
Address 3670 MAGUIRE BLVD STE 220 ORLANDO, FL 32803 |
| Lot: 0160 |
| Contracted Stated Job Value: ¤175,000.00 |
| Job Description: SINGLE FAMILY RESIDENCE |
| Type: CN |
Contractor
INB HOMES
| Status | Location Address | Mailing Address | State License Number | Phone |
| ACTIVE |
3670 MAGUIRE BLVD ORLANDO, FL 32803 |
SUITE 210 ORLANDO, FL 32803 |
CGC048746 (Exp: 08/31/2026) | 407-476-8195 |
Sub Contractors
HEATH EDWARD SANFORD
| Status | Location Address | State License Number | Phone |
| ACTIVE |
126 EAST END RD SAN MATEO, FL 32187 |
CFC1429896 (Exp: 08/31/2026) | 386-871-8823 |
ROBERT MICHAEL RENNER
| Status | Location Address | State License Number | Phone |
| ACTIVE |
531 CODISCO WAY SANFORD, FL 32771 |
CAC051477 (Exp: 08/31/2026) | 407-333-2665 |
TERRY BRICE DICKERSON
| Status | Location Address | State License Number | Phone |
| ACTIVE |
4300 ST JOHN'S PARKWAY ALPHARETTA, GA 30009 |
CCC1326209 (Exp: 08/31/2026) | 407-548-6733 |
JOSEPH C WRIGHT
| Status | Location Address | Mailing Address | State License Number | Phone | Fax |
| ACTIVE |
15 HARGROVE LANE PALM COAST, FL 32137 |
UNIT 3 D PALM COAST, FL 32137 |
EC13003278 (Exp: 08/31/2026) | 386-447-9644 | 386-447-9633 |
Inspection History
| Type | Request Date | Result | Inspector |
| BLD - BUILDING FINAL | 03/27/2024 | FINAL APPROVED | AGAETANO |
| Note: 3/26/2024 - PREVIOUS INSPECTION NOTES 03-26-2024 AHU heat label not indicated. Please have AC running for inspection. | |||
| ROW - STORMWATER FINAL | 03/27/2024 | APPROVED | PFLANAGAN |
| Note: CORRECTION MADE FROM LAST INSPECTION ----------------------------------------------------------------------------------------- 3/25/24= REMOVE THE POTTY FROM THE SWALE OR THE ROAD AND PLACE IN THE DRIVEWAY 3/13/2024 - PREVIOUS INSPECTION NOTES ** 03/13/24 BUILDER WILL NEED TO RE-GRADE ACROSS REAR PROPERTY LINE AS INSPECTORS G. BERTOLA AND E. MADISON BOTH INSPECTED THIS PROPERTY . AFTER BOTH REVIEWING YOUR SUBMITTED FINAL SURVEY AND WALKING THIS SITE IT IS DETERMINED YOUR SUBMITTED FINAL SURVEY DOES NOT CAPTURE WHAT IS ACTUALLY IN THE FIELD. YOU WILL NEED TO CREATE A 4:1 SLOPE ACROSS REAR AS CURRENTLY YOU HAVE MORE THAN 8 FT DRAINING INTO THE ADJACENT PROPERTIES TO THE REAR. ** YOU ALSO BE REQUIRED TO SUBMIT A NEW FINAL SURVEY FOR REVIEW ** NEED TO ALSO REMOVE THE PORT-A-JOHN FROM THE ROAD SIDE SWALE ON RIGHT Inspector Notes from Inspection 9465 ** 03/11/24 BEFORE THE ROW FINAL IS APPROVED THE FOLLOWING CORRECTIONS ARE REQUIRED ** DRAINAGE CONVEYANCE AT 10 FT OFF BACK OF STRUCTURE NEEDS TO BE FIXED HAVING MORE FALL AWAY FROM THE STRUCTURE. ** BACK LEFT CORNER OUTLINED WITH WHITE PAINT NEEDS TO BE RAISED AS CURRENTLY YOUR STORMWATER WILL NEGATIVELY IMPACT THE ADJACENT PROPERTY IN THE LEFT REAR ____________________________________________________________________________________________________________________ | |||
| BLD - BUILDING FINAL | 03/26/2024 | Disapproved - NO FEE | AGAETANO |
| Note: 03-26-2024 AHU heat label not indicated. Please have AC running for inspection. | |||
| ROW - FINAL APRON (AFTER POUR) | 03/25/2024 | APPROVED | GBERTOLA |
| Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. THIS INCLUDES BUT IS NOT LIMITED TO THE CULVERT PIPE ELEVATION APPROVAL FOR THE CONCRETE POUR 3/13/2024 - PREVIOUS INSPECTION NOTES Inspector Notes from Inspection 9465 ** 03/11/24 BEFORE THE ROW FINAL IS APPROVED THE FOLLOWING CORRECTIONS ARE REQUIRED ** DRAINAGE CONVEYANCE AT 10 FT OFF BACK OF STRUCTURE NEEDS TO BE FIXED HAVING MORE FALL AWAY FROM THE STRUCTURE. ** BACK LEFT CORNER OUTLINED WITH WHITE PAINT NEEDS TO BE RAISED AS CURRENTLY YOUR STORMWATER WILL NEGATIVELY IMPACT THE ADJACENT PROPERTY IN THE LEFT REAR ____________________________________________________________________________________________________________________ | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 03/25/2024 | APPROVED | GBERTOLA |
| Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. THIS INCLUDES BUT IS NOT LIMITED TO THE CULVERT PIPE ELEVATION APPROVAL FOR THE CONCRETE POUR 3/22/2024 - PREVIOUS INSPECTION NOTES 03/22/24 FINAL SURVEY MUST PASS BEFORE FIELD SURVEY CAN BE SCHEDULED ----------------------------------------------------------------------------------------- 3/19/2024 - PREVIOUS INSPECTION NOTES ** 03/19/24 BUILDER WILL NEED TO RE-SUBMIT A NEW FINAL SURVEY THAT CAPTURE ALL CHANGES MADE TO GRADE OF TGIS PROPERTY, BEFORE THE FIELD SURVEY CAN BE RESULTED | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 03/25/2024 | APPROVED | GBERTOLA |
| Note: 3/25/24=AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. THIS INCLUDES BUT IS NOT LIMITED TO THE CULVERT PIPE ELEVATION APPROVAL FOR THE CONCRETE POUR 3/22/2024 - PREVIOUS INSPECTION NOTES 03/22/24 IN THE LAST 3 SURVEYS THE NUMBERS OFF THE BACK OF THE STRUCTURE HAVE NOT MET CITY REQUIREMENTS. THERE MUST BE AT LEAST 6" FALL IN THE FIRST 10' OFF THE BACK OF THE STRUCTURE. PLEASE MAKE CORRECTIONS IN FIELD AS WELL AS ON TYHE SURVEY. Sec 300, Drawing 300.D, Drainage from the structure is to be a 6 inch (5%) minimum slope for the first 10’ 3/13/2024 2:56:08 PM- PREVIOUS INSPECTION NOTES ** 03/13/24 SEE NOTES FROM TODAYS ROW FINAL | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 03/22/2024 | Disapproved - NO FEE | TPOLACEK |
| Note: 03/22/24 FINAL SURVEY MUST PASS BEFORE FIELD SURVEY CAN BE SCHEDULED ----------------------------------------------------------------------------------------- 3/19/2024 - PREVIOUS INSPECTION NOTES ** 03/19/24 BUILDER WILL NEED TO RE-SUBMIT A NEW FINAL SURVEY THAT CAPTURE ALL CHANGES MADE TO GRADE OF TGIS PROPERTY, BEFORE THE FIELD SURVEY CAN BE RESULTED | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 03/22/2024 | Disapproved - NO FEE | TPOLACEK |
| Note: 03/22/24 IN THE LAST 3 SURVEYS THE NUMBERS OFF THE BACK OF THE STRUCTURE HAVE NOT MET CITY REQUIREMENTS. THERE MUST BE AT LEAST 6" FALL IN THE FIRST 10' OFF THE BACK OF THE STRUCTURE. PLEASE MAKE CORRECTIONS IN FIELD AS WELL AS ON TYHE SURVEY. Sec 300, Drawing 300.D, Drainage from the structure is to be a 6 inch (5%) minimum slope for the first 10’ 3/13/2024 2:56:08 PM- PREVIOUS INSPECTION NOTES ** 03/13/24 SEE NOTES FROM TODAYS ROW FINAL | |||
| ROW FIELD SURVEY /GRADING CERTIFICATION | 03/19/2024 | Disapproved - NO FEE | EMADISON |
| Note: ** 03/19/24 BUILDER WILL NEED TO RE-SUBMIT A NEW FINAL SURVEY THAT CAPTURE ALL CHANGES MADE TO GRADE OF TGIS PROPERTY, BEFORE THE FIELD SURVEY CAN BE RESULTED | |||
| ROW- PROJECT STATUS | 03/15/2024 | APPROVED | GBERTOLA |
| Note: AT THE TIME OF THE INSPECTION, ALL MINIMUM CITY REQUIREMENTS WERE MET. IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT NOTHING CHANGES AFTER THIS INSPECTION IS APPROVED. | |||
| ROW - FINAL APRON (AFTER POUR) | 03/13/2024 | Disapproved - NO FEE | EMADISON |
| Note: Inspector Notes from Inspection 9465 ** 03/11/24 BEFORE THE ROW FINAL IS APPROVED THE FOLLOWING CORRECTIONS ARE REQUIRED ** DRAINAGE CONVEYANCE AT 10 FT OFF BACK OF STRUCTURE NEEDS TO BE FIXED HAVING MORE FALL AWAY FROM THE STRUCTURE. ** BACK LEFT CORNER OUTLINED WITH WHITE PAINT NEEDS TO BE RAISED AS CURRENTLY YOUR STORMWATER WILL NEGATIVELY IMPACT THE ADJACENT PROPERTY IN THE LEFT REAR ____________________________________________________________________________________________________________________ | |||
| BLD - BUILDING FINAL | 03/13/2024 | CANCELLED BY APPLICANT | WEB |
| U-CROSS CONNECTION | 03/13/2024 | APPROVED - AS NOTED | LFITZGERALD |
| Note: no irr-no cross connection | |||
| ROW - STORMWATER FINAL | 03/13/2024 | Disapproved - NO FEE | EMADISON |
| Note: ** 03/13/24 BUILDER WILL NEED TO RE-GRADE ACROSS REAR PROPERTY LINE AS INSPECTORS G. BERTOLA AND E. MADISON BOTH INSPECTED THIS PROPERTY . AFTER BOTH REVIEWING YOUR SUBMITTED FINAL SURVEY AND WALKING THIS SITE IT IS DETERMINED YOUR SUBMITTED FINAL SURVEY DOES NOT CAPTURE WHAT IS ACTUALLY IN THE FIELD. YOU WILL NEED TO CREATE A 4:1 SLOPE ACROSS REAR AS CURRENTLY YOU HAVE MORE THAN 8 FT DRAINING INTO THE ADJACENT PROPERTIES TO THE REAR. ** YOU ALSO BE REQUIRED TO SUBMIT A NEW FINAL SURVEY FOR REVIEW ** NEED TO ALSO REMOVE THE PORT-A-JOHN FROM THE ROAD SIDE SWALE ON RIGHT Inspector Notes from Inspection 9465 ** 03/11/24 BEFORE THE ROW FINAL IS APPROVED THE FOLLOWING CORRECTIONS ARE REQUIRED ** DRAINAGE CONVEYANCE AT 10 FT OFF BACK OF STRUCTURE NEEDS TO BE FIXED HAVING MORE FALL AWAY FROM THE STRUCTURE. ** BACK LEFT CORNER OUTLINED WITH WHITE PAINT NEEDS TO BE RAISED AS CURRENTLY YOUR STORMWATER WILL NEGATIVELY IMPACT THE ADJACENT PROPERTY IN THE LEFT REAR ____________________________________________________________________________________________________________________ | |||
| U -UTILITY RESIDENTIAL FINAL | 03/13/2024 | FINAL APPROVED | LFITZGERALD |
| ROW FIELD SURVEY /GRADING CERTIFICATION | 03/12/2024 | Disapproved - NO FEE | EMADISON |
| Note: 03/13/24 SEE NOTES FROM TODAYS ROW FINAL ** 03/11/24 BEFORE THE ROW FINAL IS APPROVED THE FOLLOWING CORRECTIONS ARE REQUIRED ** DRAINAGE CONVEYANCE AT 10 FT OFF BACK OF STRUCTURE NEEDS TO BE FIXED HAVING MORE FALL AWAY FROM THE STRUCTURE. ** BACK LEFT CORNER OUTLINED WITH WHITE PAINT NEEDS TO BE RAISED AS CURRENTLY YOUR STORMWATER WILL NEGATIVELY IMPACT THE ADJACENT PROPERTY IN THE LEFT REAR ____________________________________________________________________________________________________________________ | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 03/11/2024 | Disapproved - NO FEE | EMADISON |
| Note: Inspector Notes from Inspection 9465 ** 03/11/24 BEFORE THE ROW FINAL IS APPROVED THE FOLLOWING CORRECTIONS ARE REQUIRED ** DRAINAGE CONVEYANCE AT 10 FT OFF BACK OF STRUCTURE NEEDS TO BE FIXED HAVING MORE FALL AWAY FROM THE STRUCTURE. ** BACK LEFT CORNER OUTLINED WITH WHITE PAINT NEEDS TO BE RAISED AS CURRENTLY YOUR STORMWATER WILL NEGATIVELY IMPACT THE ADJACENT PROPERTY IN THE LEFT REAR ____________________________________________________________________________________________________________________ | |||
| ROW- PROJECT STATUS | 03/08/2024 | APPROVED | PFLANAGAN |
| Note: MEET WITH GRADE GUY AND BILL WITH INB FOR THE GRADE OFF THE BACK OF HOUSE GRADING NEEDS TO BE DONE | |||
| ROW- FINAL SURVEY/GRADING CERTIFICATION | 03/01/2024 | Disapproved - NO FEE | PFLANAGAN |
| Note: YOU DO NOT HAVE THE MINIMUM OF FALL OFF THE BACK OF THE HOUSE. Florida Building Code, Residential, Chapter 4, R401.3F Drainage from the structure is to be a 6 inch (5%) minimum slope for the first 10’. | |||
| ROW- PRE-APRON (PRE-POUR) | 02/13/2024 | APPROVED - AS NOTED | FSLADISH |
| Note: 2/13/24 PIPE IS GOOD. LET BILL CM KNOW TO MAKE SURE ANY WATER IS OUT OF THE POUR AREA AND MITERED END FOOTERS ARE DUG OUT TO COPC 6" X 6" SPECS IF ANY DIRT HAS WASHED IN. APPROVING THIS PREPOUR AS NOTED .. AT THE TIME OF THE INSPECTION CULVERT PIPE IS GOOD IS READY TO POUR, IF RAIN PLEASE, BUILDER SHOULD DOUBLE CHECK CULVERT ELEVATIONS MAKE SURE IS 3000 PSI CONCRETE REINFORCED WITH WWF 6X6.W1.4 MESH OR FIBERGLASS REINFORCED CONCRETE (FRC) DRAWING 300,E RESIDENTIAL CULVERT DETAIL BEFORE POURING. At the time of the inspection all minimum city requirements were met. It is the builders responsibiliy to ensure that nothing changes after this Inspection is approved. This includes but is not limited to, the Culvert Pipe Elevation from the time of the inspection approval to the concrete pour. | |||
| U - SEWER TIE IN | 02/08/2024 | APPROVED | MGIBSON |
| Note: Inspector Notes from Inspection 2060 REMOVE 6'' FERNCO FROM FOOTER AT EXIT OF MAIN SEWER DRAIN, AND PROVIDE PORTABLE RESTROOM BEFORE SLAB INSPECTION | |||
| GRAVITY SEWER TEST | 02/08/2024 | APPROVED | MGIBSON |
| Note: Inspector Notes from Inspection 2060 REMOVE 6'' FERNCO FROM FOOTER AT EXIT OF MAIN SEWER DRAIN, AND PROVIDE PORTABLE RESTROOM BEFORE SLAB INSPECTION | |||
| ELECTRIC - EARLY POWER | 01/19/2024 | APPROVED | JWALKER |
| Note: Inspector Notes from Inspection 2200 Toilet facilities will need to be cleaned prior to any further inspections. | |||
| PEP TANK INSTALLATION REQUEST | 01/10/2024 | APPROVED | BVITALE |
| Note: 1/5/2024 3:00:13 PM- PREVIOUS INSPECTION NOTES DUMPSTER IS IN THE WAY-NEEDS TO BE REMOVED | |||
| PEP TANK INSTALLATION REQUEST | 01/05/2024 | Disapproved -FEE REQUIRED | TCHURCHILL |
| Note: DUMPSTER IS IN THE WAY-NEEDS TO BE REMOVED | |||
| LATH/BRICK/ WATER BARRIER | 12/22/2023 | APPROVED | JWALKER |
| INSULATION | 12/19/2023 | APPROVED | JWALKER |
| ELECTRIC-TUG | 12/15/2023 | APPROVED - AS NOTED | JWALKER |
| Note: Toilet facilities will need to be cleaned prior to any further inspections. | |||
| ALL ROUGH | 12/14/2023 | APPROVED | JWALKER |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 12/12/2023 | APPROVED | JWALKER |
| Note: 12/6/2023 - PREVIOUS INSPECTION NOTES 12/6/23: Not Fully resolved. 1). (2) HJ03 trusses still missing anchors 2). Truss T 26 only has 1 of 2 truss plates installed & the installed plate does not extend fully across block. Still missing vapor barrier on 2" x 12"s 3). Remains unresolved. 4). Middle truss web repair does not meet MiTek requirements. 5). Remains unresolved. 12/4/2023 - PREVIOUS INSPECTION NOTES Front entry: 1. Truss T-25, (2) HJO3, and The CJ trusses all missing hold down anchors. 2. All trusses and the 2 x 12 beams are to be place on a truss plate or have a moisture barrier where the lumber comes in contact with the CMU. Installed moisture barriers check all areas at the front entry. 3. The T-28 and (3) T-29 truss left side H10A truss anchors are concealed cannot see attachment to the beam. 4. The center truss T-29 at the front entry has a broken web member and will need to be repaired as per the mitek broken web repair engineering. 5. The 2x12 beam where it land on the CMU wall left side of the front entry door opening missing hold down anchors. | |||
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 12/06/2023 | Disapproved -FEE REQUIRED | RSIMS |
| Note: 12/6/23: Not Fully resolved. 1). (2) HJ03 trusses still missing anchors 2). Truss T 26 only has 1 of 2 truss plates installed & the installed plate does not extend fully across block. Still missing vapor barrier on 2" x 12"s 3). Remains unresolved. 4). Middle truss web repair does not meet MiTek requirements. 5). Remains unresolved. 12/4/2023 - PREVIOUS INSPECTION NOTES Front entry: 1. Truss T-25, (2) HJO3, and The CJ trusses all missing hold down anchors. 2. All trusses and the 2 x 12 beams are to be place on a truss plate or have a moisture barrier where the lumber comes in contact with the CMU. Installed moisture barriers check all areas at the front entry. 3. The T-28 and (3) T-29 truss left side H10A truss anchors are concealed cannot see attachment to the beam. 4. The center truss T-29 at the front entry has a broken web member and will need to be repaired as per the mitek broken web repair engineering. 5. The 2x12 beam where it land on the CMU wall left side of the front entry door opening missing hold down anchors. | |||
| ROOF VALLEY & METAL | 12/04/2023 | APPROVED | JWALKER |
| WALL SHEATHING | 12/04/2023 | APPROVED | JWALKER |
| ROOF SHEATHING / BRACES/TIES/DOWN CELL | 12/04/2023 | Disapproved - NO FEE | JWALKER |
| Note: Front entry: 1. Truss T-25, (2) HJO3, and The CJ trusses all missing hold down anchors. 2. All trusses and the 2 x 12 beams are to be place on a truss plate or have a moisture barrier where the lumber comes in contact with the CMU. Installed moisture barriers check all areas at the front entry. 3. The T-28 and (3) T-29 truss left side H10A truss anchors are concealed cannot see attachment to the beam. 4. The center truss T-29 at the front entry has a broken web member and will need to be repaired as per the mitek broken web repair engineering. 5. The 2x12 beam where it land on the CMU wall left side of the front entry door opening missing hold down anchors. | |||
| FOUND SURVEY APPROVED (OFFICE) | 12/01/2023 | APPROVED | TBAKER |
| TIE BEAM / LINTEL | 11/13/2023 | APPROVED | JWALKER |
| MONOLITHIC SLAB | 11/02/2023 | APPROVED | JWALKER |
| Note: 11/1/2023 - PREVIOUS INSPECTION NOTES 1. Page S-2.0 of the plans are missing. Please have a full set of plans onsite for all inspections. 2. UFER ground is not installed. 3. Minimum depth of the slab is to be 4" thick. See plans. Test string lines left in place. Remove and tamp excess soil and reistall string lines. | |||
| MONOLITHIC SLAB | 11/01/2023 | Disapproved - NO FEE | JWALKER |
| Note: 1. Page S-2.0 of the plans are missing. Please have a full set of plans onsite for all inspections. 2. UFER ground is not installed. 3. Minimum depth of the slab is to be 4" thick. See plans. Test string lines left in place. Remove and tamp excess soil and reistall string lines. | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 10/26/2023 | APPROVED - AS NOTED | MGIBSON |
| Note: REMOVE 6'' FERNCO FROM FOOTER AT EXIT OF MAIN SEWER DRAIN, AND PROVIDE PORTABLE RESTROOM BEFORE SLAB INSPECTION | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 10/20/2023 | CANCELLED BY APPLICANT | WEB |
| WATER METER INSTALLATION REQUEST | 10/04/2023 | APPROVED | CBOWERMASTER |
Review History
| Department | Status | Date In | Date Out |
| MECH | COMPLETE | 03/14/2024 | 03/14/2024 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 01/24/2024 | 01/25/2024 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ENGIN1 | COMPLETE | 12/01/2023 | 12/01/2023 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 12/01/2023 | 12/01/2023 |
| Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM | |||
| ENGIN1 | HOLD | 10/25/2023 | 10/25/2023 |
| Note: Held By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM Formboard survey is unaaceptable as foundation survey. Please submit Foundation Survey showing location, dimensions and elevation of finished concrete foundation/slab. | |||
| ZON | COMPLETE | 10/25/2023 | 10/25/2023 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 08/03/2023 | 08/03/2023 |
| Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 08/03/2023 | 08/07/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 07/24/2023 | 07/27/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| CUSVC | COMPLETE | 07/24/2023 | 07/24/2023 |
| Note: Released By: HALEIGH HAND - - HHAND@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 07/24/2023 | 07/25/2023 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| ENGIN1 | COMPLETE | 07/24/2023 | 07/24/2023 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| GAS | CANCEL | 07/24/2023 | 07/25/2023 |
| LOCATE | COMPLETE | 07/24/2023 | 07/25/2023 |
| Note: Released By: CANDACE BOWERMASTER - - CBOWERMASTER@PALMCOASTGOV.COM | |||
| MECH | COMPLETE | 07/24/2023 | 07/25/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| SW1 | COMPLETE | 07/24/2023 | 07/31/2023 |
| Note: Released By: ROBERT GROSS - (386)986-4769 - RGROSS@PALMCOASTGOV.COM | |||
| ZON | HOLD | 07/24/2023 | 07/26/2023 |
| Note: Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM Elevation page: Add banding to garage as it faces the right of way | |||
| SWALE | COMPLETE | 07/24/2023 | 09/12/2023 |
| Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM | |||
| BADMIN | COMPLETE | 07/24/2023 | 08/07/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| SW ENG REINSPECTION 20 | ¤20.00 | 03/25/2024 |
| UTILITY PEP REINSPECTION | ¤40.00 | 03/15/2024 |
| SW ENG REINSPECTION 20 | ¤20.00 | 03/15/2024 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 03/15/2024 |
| CONNECTION FEES | ¤1,166.26 | 09/08/2023 |
| FIRE IMPACT FEE ADMIN | ¤12.62 | 09/08/2023 |
| FIRE IMPACT FEE ADMIN | (¤12.62) | 09/08/2023 |
| FC IMPACT FEE EMS | ¤62.00 | 09/08/2023 |
| IMPACT FEE FIRE | ¤420.52 | 09/08/2023 |
| FC IMPACT FEE LAW ENFORCEMENT | ¤218.00 | 09/08/2023 |
| FC IMPACT FEE LIBRARY | ¤268.00 | 09/08/2023 |
| IMPACT FEE PARKS | ¤1,769.15 | 09/08/2023 |
| IMPACT FEE SCHOOL | ¤5,450.00 | 09/08/2023 |
| IMPACT FEE TRANSPORTATION | ¤1,812.00 | 09/08/2023 |
| WATER -IRRIGATION INSPECTION | ¤25.00 | 09/08/2023 |
| PARKS IMPACT FEE ADMIN | ¤53.07 | 09/08/2023 |
| PARKS IMPACT FEE ADMIN | (¤53.07) | 09/08/2023 |
| SURCHARGE FS 533.721 | ¤4.37 | 09/08/2023 |
| SURCHARGE - FS 468.631 | ¤6.55 | 09/08/2023 |
| SW ENG - FOUNDATION SURVEY | ¤20.00 | 09/08/2023 |
| SW ENG INSPECTION 80 | ¤80.00 | 09/08/2023 |
| SW ENG PRE APRON | ¤30.00 | 09/08/2023 |
| SEWER CREDIT | (¤1,342.00) | 09/08/2023 |
| SEWER INSPECTION | ¤25.00 | 09/08/2023 |
| SEWER CAPITAL FACILITY | ¤5,344.82 | 09/08/2023 |
| WATER CAPITAL FACILITY FEE | ¤3,923.88 | 09/08/2023 |
| SITE PLAN 30 | ¤30.00 | 09/08/2023 |
| SW ENG - REVIEW 20 | ¤20.00 | 09/08/2023 |
| SW ENG RES REVIEW 200 | ¤200.00 | 09/08/2023 |
| TRANS IMPACT FEE ADMIN | ¤54.36 | 09/08/2023 |
| TRANS IMPACT FEE ADMIN | (¤54.36) | 09/08/2023 |
| WATER- TURN ON | ¤25.00 | 09/08/2023 |
| ADJUSTMENT 50% | (¤436.84) | 09/08/2023 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 09/08/2023 |
| INSPECTION - RESIDENTIAL | ¤657.25 | 09/08/2023 |
| PLAN REVIEW - RESIDENTIAL | ¤186.42 | 09/08/2023 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤20,115.38 |