Status: FINAL

Parcel Id: 07-11-31-7034-00760-0080
Block: 00760
Subdivision: 0 -
Job Phone: 904-794-2665
Location Address: 40 EGRET TR
Type: ME - MECHANICAL
Issue Date: 07/25/2023
NOC: Unknown
Applicant name: DAVID FRANKLIN POWELL
Owner: GRIFFITH JACK E & PATRICIA M H&W LIFE ESTATE

Address

40 EGRET TRAIL

PALM COAST, FL 32164

Lot: 0080
Contracted Stated Job Value: ¤8,233.00
Job Description: HVAC Change Out Like for Like Tonnage
Type: CN

Contractor

POWELL HEATING & AIR CONDITIONING
Status Location Address State License Number Phone Fax
INACTIVE

2610 Dobbs Road

St. Augustine, FL 32086

CAC053851 (Exp: 08/31/2026) 904-794-2665 904-794-2329

Inspection History

Type Request Date Result Inspector
HVAC FINAL 09/28/2023 APPROVED RSIMS
Note: 9/19/2023 - PREVIOUS INSPECTION NOTES 9/18/23: No answer after ringing door bell & knocking twice. Waited 5 minutes. 8/4/2023 - PREVIOUS INSPECTION NOTES 8/4/23: 1). Disconnect on top of the unit is not securely fastened. Should be mounted securely to the wall. 2). MC flex cable/jacket is pulled out of the connector at the ceiling plate and is missing an Anti-short as required. Please check the side that ties into the disconnect for an Anti-short also.(NEC300.4 - Wire protection from damage)
HVAC FINAL 09/19/2023 Disapproved -FEE REQUIRED RSIMS
Note: 9/18/23: No answer after ringing door bell & knocking twice. Waited 5 minutes. 8/4/2023 - PREVIOUS INSPECTION NOTES 8/4/23: 1). Disconnect on top of the unit is not securely fastened. Should be mounted securely to the wall. 2). MC flex cable/jacket is pulled out of the connector at the ceiling plate and is missing an Anti-short as required. Please check the side that ties into the disconnect for an Anti-short also.(NEC300.4 - Wire protection from damage)
HVAC FINAL 08/04/2023 Disapproved - NO FEE RSIMS
Note: 8/4/23: Please mark the heating coil installed more promenently & identify breaker size for the heating coil also on the unit label. 1). Disconnect on top of the unit is not securely fastened. Shound be mounted securely to the wall. 2). MC flex cable/jacket is pulled out of the connector at the ceiling plate and is missing an Anti-short as required. Please check the side that ties into the disconnect for an Anti-short also.(NEC300.4 - Wire protection from damage)

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
REINSPECTION RESIDENTIAL ¤40.00 09/22/2023
SURCHARGE FS 533.721 ¤2.00 07/25/2023
SURCHARGE - FS 468.631 ¤2.00 07/25/2023
ADJUSTMENT 50% (¤45.00) 07/25/2023
ADMINISTRATIVE RESIDENTIAL ¤30.00 07/25/2023
INSPECTION - MECHANICAL ¤60.00 07/25/2023
Fees Total Due: ¤0.00 Total Paid: ¤89.00