Permit #2023071063
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7034-00760-0080 |
| Block: 00760 |
| Subdivision: 0 - |
| Job Phone: 904-794-2665 |
| Location Address: 40 EGRET TR |
| Type: ME - MECHANICAL |
| Issue Date: 07/25/2023 |
| NOC: Unknown |
| Applicant name: DAVID FRANKLIN POWELL |
| Owner: GRIFFITH JACK E & PATRICIA M H&W LIFE ESTATE |
|
Address 40 EGRET TRAIL PALM COAST, FL 32164 |
| Lot: 0080 |
| Contracted Stated Job Value: ¤8,233.00 |
| Job Description: HVAC Change Out Like for Like Tonnage |
| Type: CN |
Contractor
POWELL HEATING & AIR CONDITIONING
| Status | Location Address | State License Number | Phone | Fax |
| INACTIVE |
2610 Dobbs Road St. Augustine, FL 32086 |
CAC053851 (Exp: 08/31/2026) | 904-794-2665 | 904-794-2329 |
Inspection History
| Type | Request Date | Result | Inspector |
| HVAC FINAL | 09/28/2023 | APPROVED | RSIMS |
| Note: 9/19/2023 - PREVIOUS INSPECTION NOTES 9/18/23: No answer after ringing door bell & knocking twice. Waited 5 minutes. 8/4/2023 - PREVIOUS INSPECTION NOTES 8/4/23: 1). Disconnect on top of the unit is not securely fastened. Should be mounted securely to the wall. 2). MC flex cable/jacket is pulled out of the connector at the ceiling plate and is missing an Anti-short as required. Please check the side that ties into the disconnect for an Anti-short also.(NEC300.4 - Wire protection from damage) | |||
| HVAC FINAL | 09/19/2023 | Disapproved -FEE REQUIRED | RSIMS |
| Note: 9/18/23: No answer after ringing door bell & knocking twice. Waited 5 minutes. 8/4/2023 - PREVIOUS INSPECTION NOTES 8/4/23: 1). Disconnect on top of the unit is not securely fastened. Should be mounted securely to the wall. 2). MC flex cable/jacket is pulled out of the connector at the ceiling plate and is missing an Anti-short as required. Please check the side that ties into the disconnect for an Anti-short also.(NEC300.4 - Wire protection from damage) | |||
| HVAC FINAL | 08/04/2023 | Disapproved - NO FEE | RSIMS |
| Note: 8/4/23: Please mark the heating coil installed more promenently & identify breaker size for the heating coil also on the unit label. 1). Disconnect on top of the unit is not securely fastened. Shound be mounted securely to the wall. 2). MC flex cable/jacket is pulled out of the connector at the ceiling plate and is missing an Anti-short as required. Please check the side that ties into the disconnect for an Anti-short also.(NEC300.4 - Wire protection from damage) |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 09/22/2023 |
| SURCHARGE FS 533.721 | ¤2.00 | 07/25/2023 |
| SURCHARGE - FS 468.631 | ¤2.00 | 07/25/2023 |
| ADJUSTMENT 50% | (¤45.00) | 07/25/2023 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 07/25/2023 |
| INSPECTION - MECHANICAL | ¤60.00 | 07/25/2023 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤89.00 |