I want to search for...

Permit #2023080132

Permit Details

Status: COED

Total Square Footage: 2011 sqft
Subdivision: -
Job Phone: 305-799-4886
Location Address: 24 HARGROVE GRADE
Type: CIA - COMMERCIAL INTERIOR EXTERIOR ALTERATION
Issue Date: 09/19/2023
NOC: RECORDED
Applicant name: JOHN EDWARD JAMES
Owner: REAL ESTATE DEVELOPMENT OF FLORIDA LLC

Address

32 HARGROVE GRADE

PALM COAST, FL 32164

Contracted Stated Job Value: ¤60,000.00
Job Description: Unit 2 - Interior office fitout
Type: CN

Contractor

JAMES COMMERCIAL DEVELOPMENT INC
Status Location Address State License Number Phone
ACTIVE

9950 KIRCHHERR

WEST PALM BEACH, FL 33411

CGC1514256 (Exp: 08/31/2026) 305-799-4886

Sub Contractors

BRETT ALAN THOMAS
Status Location Address State License Number Phone
INACTIVE

406 HAMLET TOAD

JACKSONVILLE, FL 32221

CFC1427822 (Exp: 08/31/2024) 904-390-0907
NEVILLE ROY BENNETT
Status Location Address State License Number Phone
ACTIVE

1802 IMPERIAL PALM DRIVE

APOPKA, FL 32172

EC0003124 (Exp: 08/31/2026) 407-920-6566
KERRY DWAIN AYLESWORTH II
Status Location Address Mailing Address State License Number Phone
ACTIVE

2820 LEWIS SPEEDWAY

ST AUGUSTINE, FL 32084

STE B

ST AUGUSTINE, FL 32084

CAC1820713 (Exp: 08/31/2026) 904-342-5709

Inspection History

Type Request Date Result Inspector
BUILDING FINAL 05/08/2024 FINAL APPROVED FWILLIS
Note: 5/7/2024 - PREVIOUS INSPECTION NOTES cancelled per Contractor Via Phone message
BUILDING FINAL 05/07/2024 CANCELLED BY APPLICANT LMILLER
Note: cancelled per Contractor Via Phone message
FIRE FINAL 05/06/2024 APPROVED RMARTIN
U - UTILITY COMMERCIAL FINAL 05/03/2024 CANCELLED BY APPLICANT LFITZGERALD
U - UTILITY COMMERCIAL FINAL 05/03/2024 APPROVED - AS NOTED LFITZGERALD
Note: *** NOTES ADDED BY LFITZGERALD 5/3/2024 12:44:01 PM *** see note unit 1 5/3/2024 - PREVIOUS INSPECTION NOTES
PLUMBING FINAL 05/03/2024 APPROVED MGIBSON
Note: 4/5/2024 - PREVIOUS INSPECTION NOTES
FIREWALL PENETRATIONS 04/29/2024 APPROVED LMILLER
Note: 4/26/2024 - PREVIOUS INSPECTION NOTES 2-26-24 cancelled per contractor via phone call 4/24/2024 - PREVIOUS INSPECTION NOTES 4-24-24 penetrations are not per plans see fire penetration details on approved plans 107.3.1 Inspector Notes from Inspection 3470 4/18/27 M.E.P'S MET ON SITE 4/17/2024 - PREVIOUS INSPECTION NOTES 4/17/24 ALL PLAN REVISIONS THAT PERTAIN TO THE ABOVE CEILING INSPECTION NEED TO BE APPROVED AND ON SITE FOR PROPER INSPECTION, ALSO CONTRACTOR NEEDS TO CALL IN INSPECTIONS THAT ARE ON THE SHELL PERMIT ASAP, BUILDOUTS FOR THE UNITS WILL NOT RECEIVE FINALS UNTIL SHELL PERMIT IS CLOSED/FINALED OUT. 4/9/2024 - PREVIOUS INSPECTION NOTES
ELECTRIC FINAL 04/26/2024 FINAL APPROVED MKRASKI
FIREWALL PENETRATIONS 04/26/2024 CANCELLED BY APPLICANT LMILLER
Note: 2-26-24 cancelled per contractor via phone call 4/24/2024 - PREVIOUS INSPECTION NOTES 4-24-24 penetrations are not per plans see fire penetration details on approved plans 107.3.1 Inspector Notes from Inspection 3470 4/18/27 M.E.P'S MET ON SITE 4/17/2024 - PREVIOUS INSPECTION NOTES 4/17/24 ALL PLAN REVISIONS THAT PERTAIN TO THE ABOVE CEILING INSPECTION NEED TO BE APPROVED AND ON SITE FOR PROPER INSPECTION, ALSO CONTRACTOR NEEDS TO CALL IN INSPECTIONS THAT ARE ON THE SHELL PERMIT ASAP, BUILDOUTS FOR THE UNITS WILL NOT RECEIVE FINALS UNTIL SHELL PERMIT IS CLOSED/FINALED OUT. 4/9/2024 - PREVIOUS INSPECTION NOTES
ELECTRIC FINAL 04/24/2024 Disapproved - NO FEE RMARTIN
Note: Need to lable all circuits correctly inside panels, need to have main blanks installed in panels, no openings can be inside panels, need to have gfci protection on outlets by the sinks all units, need to check all HVAC breakers to make sure they are labled correctly and MOCP matches units
FIREWALL PENETRATIONS 04/24/2024 Disapproved -FEE REQUIRED LMILLER
Note: 4-24-24 penetrations are not per plans see fire penetration details on approved plans 107.3.1 Inspector Notes from Inspection 3470 4/18/27 M.E.P'S MET ON SITE 4/17/2024 - PREVIOUS INSPECTION NOTES 4/17/24 ALL PLAN REVISIONS THAT PERTAIN TO THE ABOVE CEILING INSPECTION NEED TO BE APPROVED AND ON SITE FOR PROPER INSPECTION, ALSO CONTRACTOR NEEDS TO CALL IN INSPECTIONS THAT ARE ON THE SHELL PERMIT ASAP, BUILDOUTS FOR THE UNITS WILL NOT RECEIVE FINALS UNTIL SHELL PERMIT IS CLOSED/FINALED OUT. 4/9/2024 - PREVIOUS INSPECTION NOTES
HVAC FINAL 04/24/2024 APPROVED CPISCITELLI
Note: 4/23/2024 - PREVIOUS INSPECTION NOTES Missing locking caps Drain need to be extended
HVAC FINAL 04/23/2024 Disapproved -FEE REQUIRED CPISCITELLI
Note: Missing locking caps Drain need to be extended
ABOVE CEILING 04/18/2024 APPROVED - AS NOTED RMARTIN
Note: 4/18/27 M.E.P'S MET ON SITE 4/17/2024 - PREVIOUS INSPECTION NOTES 4/17/24 ALL PLAN REVISIONS THAT PERTAIN TO THE ABOVE CEILING INSPECTION NEED TO BE APPROVED AND ON SITE FOR PROPER INSPECTION, ALSO CONTRACTOR NEEDS TO CALL IN INSPECTIONS THAT ARE ON THE SHELL PERMIT ASAP, BUILDOUTS FOR THE UNITS WILL NOT RECEIVE FINALS UNTIL SHELL PERMIT IS CLOSED/FINALED OUT. 4/9/2024 - PREVIOUS INSPECTION NOTES
ABOVE CEILING 04/17/2024 Disapproved - NO FEE RMARTIN
Note: 4/17/24 ALL PLAN REVISIONS THAT PERTAIN TO THE ABOVE CEILING INSPECTION NEED TO BE APPROVED AND ON SITE FOR PROPER INSPECTION, ALSO CONTRACTOR NEEDS TO CALL IN INSPECTIONS THAT ARE ON THE SHELL PERMIT ASAP, BUILDOUTS FOR THE UNITS WILL NOT RECEIVE FINALS UNTIL SHELL PERMIT IS CLOSED/FINALED OUT. 4/9/2024 - PREVIOUS INSPECTION NOTES
ABOVE CEILING 04/09/2024 CANCELLED BY APPLICANT RMARTIN
INSULATION 04/08/2024 APPROVED FWILLIS
FIREWALL FINAL 04/08/2024 FINAL APPROVED FWILLIS
HVAC FINAL 04/05/2024 CANCELLED BY APPLICANT CPISCITELLI
Note: Inspector Notes from Inspection 3140 Need to see traps on condensate pumps Need to see balancing dampers in supply and fresh air duct Need to see exhaust fans installed Nee to see fresh air duct installed Need to have a revision for hanging unit with a letter stating the framing can handle the load of the unit Need to have a revision showing UL detais for line sets and drain lines Need to mark heaters on AHU's
PLUMBING FINAL 04/05/2024 CANCELLED BY APPLICANT MGIBSON
HVAC ROUGH 03/21/2024 APPROVED - AS NOTED CPISCITELLI
Note: Need to see traps on condensate pumps Need to see balancing dampers in supply and fresh air duct Need to see exhaust fans installed Nee to see fresh air duct installed Need to have a revision for hanging unit with a letter stating the framing can handle the load of the unit Need to have a revision showing UL detais for line sets and drain lines Need to mark heaters on AHU's
FIREWALL NAILING 02/28/2024 APPROVED FWILLIS
ELECTRIC 2ND ROUGH 02/12/2024 APPROVED MKRASKI
ELECTRIC 2ND ROUGH 02/08/2024 PARTIALLY APPROVED RMARTIN
Note: STILL NEED TO LOOK AT REST ROOM WALLS
PLUMBING 2ND ROUGH 01/23/2024 APPROVED MGIBSON
FRAMING 01/18/2024 APPROVED FWILLIS
FIREWALL FRAMING 01/17/2024 APPROVED FWILLIS

Review History

Department Status Date In Date Out
MECH COMPLETE 04/17/2024 04/17/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
MECH HOLD 04/04/2024 04/09/2024
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide attachment details to framing for AHU showing onsite conditions. 2. Provide note on plan stating weight of AHU can be supported by the decking 3. Provide firestop system to show onsite conditions for copper lines with aramaflex and PVC through the firewalls
ELEC COMPLETE 09/13/2023 09/14/2023
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
MECH COMPLETE 09/13/2023 09/18/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
BLD COMPLETE 09/13/2023 09/19/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
MECH HOLD 08/18/2023 08/31/2023
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Requirements need to be 100% addressed in comcheck 2. Heatload conflicts with equipment sizing. Revise equipment to match heatload
FI1 COMPLETE 08/18/2023 08/31/2023
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ELEC HOLD 08/18/2023 08/29/2023
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Comcheck checklist needs to be 100% addressed.
BLD HOLD 08/18/2023 09/01/2023
Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM ALL COMMENTS BELOW PER THE 2020 FLORIDA BUILDING CODE AND 2020 FLORIDA ACCESSIBILITY CODE 1. OK. 2. OK. 3. OK. 4. OK. 5. OK. 6. REPEAT COMMENT. REVISION NOT ACCEPTED. BUILDING SHELL AND CORE PLANS IDENTIFY BUILDING AS TYPE IIB. BUILDING DOES NOT QUALIFY AS A TYPE IIIB BUILDING. EXTERIOR LOAD BEARING WALLS (STEEL COLUMNS) ARE NOT 2 HOUR FIRE-RESISTIVE RATED CONSTRUCTION PER SECTION 602.3, TABLE 601 AND SECTION 704.10. EXTERIOR NON-LOAD BEARING WALL ELEMENTS FOR EXTERIOR WALL LOCATED LESS THAN 30 FEET TO PROPERTY LINE ARE NOT 1 HOUR FIRE-RESISTIVE RATED CONSTRUCTION PER SECTION 602.3, TABLE 601 AND TABLE 602. CHANGE CONSTRUCTION TYPE BACK TO TYPE IIB AND REMOVE WOOD FRAMING . Building is Type IIB construction - no wood framing allowed. Revise Plan Sheet A-5 to remove all references to wood framing. Provide framing plan using non-combustible materials. Section 602.2. 7. OK. MR. CHANCELLOR, PLEASE CALL ME ABOUT THIS ITEM IN RELATION TO NO. 6 ABOVE. THANK YOU. 8. OK. 9. OK.
BLD HOLD 08/02/2023 08/16/2023
Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM ALL COMMENTS BELOW PER THE 2029 FLORIDA BUILDING CODE AND 2020 FLORIDA ACCESSIBILITY CODE 1. Provide code analysis showing separate occupancy classifications for warehouse and business office per Chapter 3 FBC Building 2020 7Th edition 2. Provide accessibility turning radius dimension for bathroom on plans FBC-Accessibility Section 304.3.1 3. Door type A to have kick plate in accordance with 2020 FBC-Accessibility Section 404.4.2.10 or meet Exception No. 2. Reconcile. 4. Provide internally illuminated exit signs above exit door from warehouse to hall, and from hall to office and above exterior door from office. It appears an exit sign is represented at exterior door (X inside a circle) but there is no key stating what it is. Section 1013.5. and 1013.6. 5. Provide means of egress illumination in warehouse, hall and office. Provide symbol at each location and keyed reference. Section 1008.1 through 1008.3.4. Means of egress illumination must be sufficient to provide one (1) foot candle of lighting measured at the floor level Section 1008.3.5. 6. Building is Type IIB construction - no wood framing allowed. Revise Plan Sheet A-5 to remove all references to wood framing. Provide framing plan using non-combustible materials. Section 602.2. 7. Provide floor-ceiling design live and dead loads consistent with required storage design loads for area above office, hall and bathroom space. Include dead loads for ceiling drywall. Section 1606, 1607, Table 1607.1. 8. Provide complete wall sections for all interior wall partition types. All wall partitions to be of non-combustible materials due to building being classified as Type IIB construction. 9. Provide bathroom wall and floor finish schedule. Section 1210.2.1, 1219.2.2.
DSD COMPLETE 08/02/2023 08/03/2023
Note: Released By: JACQUELINE GONZALEZ - (386)986-3751 - JGONZALEZ@PALMCOASTGOV.COM
ELEC HOLD 08/02/2023 08/15/2023
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Submit a lighting plan 2. Lighting plan needs to show lighting control switch that complys with FBC Energy 2020 C405.2.1, C405.2.1.1 , C405.2.1.2 3. Submit energy calcs.
FI1 HOLD 08/02/2023 08/15/2023
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide emergency exit sign in hallway from bathroom to Office area. 2. Fire Sprinker pages have been rejected. Fire Protection needs to be designed by Florida Licensed Fire Protection Engineer and uploaded as a separate permit to the shell building address. This will need to be completed prior to release of final inspection of shell building
MECH HOLD 08/02/2023 08/09/2023
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide Energy Calculations per C407 FBC Energy Conservation 2020 7Th edition 2. Provide Heatload Calculation per C403.2.1 FBC Energy Conservation 2020 7Th edition 3. Provide typical Ductwork and AHU details showing hanging, installation and balancing dampers per Chapter 603 FBC Mechanical 2020 7th edition
PLUM COMPLETE 08/02/2023 08/16/2023
Note: Released By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM
UD1 COMPLETE 08/02/2023 08/03/2023
Note: Released By: BRICE WRIGHT - (386)986-2398 - BWRIGHT@PALMCOASTGOV.COM

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
ADDITIONAL FEE ¤40.00 03/26/2025
REINSPECTION - COMMERCIAL ¤60.00 05/06/2024
REINSPECTION - COMMERCIAL ¤60.00 05/06/2024
CONTRACTOR CHANGE ¤20.00 05/06/2024
SURCHARGE FS 533.721 ¤2.82 09/19/2023
SURCHARGE - FS 468.631 ¤4.23 09/19/2023
SITE PLAN 30 ¤30.00 09/19/2023
ADJUSTMENT 50% (¤282.00) 09/19/2023
ADMINISTRATIVE - COMMERCIAL ¤75.00 09/19/2023
INSPECTION COMMERCIAL ¤420.00 09/19/2023
PLAN REVIEW - COMMERCIAL ¤69.00 09/19/2023
Fees Total Due: ¤0.00 Total Paid: ¤499.05