Permit #2023090510
Permit Details
Status: CANCEL
| Parcel Id: 08-12-31-5835-00000-0020 |
| Total Square Footage: 5870 sqft |
| Block: 00000 |
| Subdivision: 2323 - WILTON AT PAL M COAST |
| Job Phone: (904)529-5257 |
| Location Address: 700 LINWOOD ROW |
| Type: FS - FIRE SPRINKLER WET COMMERCIAL |
| Issue Date: 02/08/2024 |
| NOC: RECORDED |
| Applicant name: JOHN P SWANSON |
| Owner: WILTON RESIDENCES LLC |
|
Address 500 OFFICE PARK DRIVE STE 215 BRIMINGHAM, AL 35223 |
| Lot: 0020 |
| Contracted Stated Job Value: ¤20,000.00 |
| Job Description: BLDG 9 fire sprinkler system |
| Type: CN |
Contractor
SWANSON FIRE PROTECTION LLC
| Status | Location Address | Mailing Address | State License Number | Phone | Fax |
| ACTIVE |
2220 COUNTY ROAD 210 W. JACKSONVILLE, FL 32259 |
SUITE 108-139 JACKSONVILLE, FL 32259 |
1944800012003 (Exp: 06/30/2026) | (904)529-5257 | (904)529-5258 |
Inspection History
| Type | Request Date | Result | Inspector |
| FIRE SPRINKLER 1ST ROUGH | 03/28/2024 | APPROVED | JMUNSON |
| FIRE SPRINKLER HYDROSTATIC TEST | 03/28/2024 | APPROVED | JMUNSON |
| FIRE SPRINKLER FINAL |
Review History
| Department | Status | Date In | Date Out |
| FI1 | COMPLETE | 03/25/2024 | 03/25/2024 |
| Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM | |||
| UD1 | COMPLETE | 03/25/2024 | 03/27/2024 |
| Note: Released By: GREG DEGLER - - GDEGLER@PALMCOASTGOV.COM | |||
| FI1 | COMPLETE | 02/07/2024 | 02/08/2024 |
| Note: Released By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM | |||
| FI1 | HOLD | 01/25/2024 | 02/01/2024 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM 12. Repeat comment. Response could not be accepted, the riser diagram on Building 9 still shows only one gauge. If the plan sheets had been individually uploaded as required, we could have rejected sheet 35 of 37. Seeing how the pages are uploaded as a single file the documents need revision for correction. We are not placing the permit on hold, we are however placing a hold on inspections until such time as the sheet has been corrected. Please provide pressure gauges for supply and system side of riser per NFPA 13r 6.12.1 and 6.12.2 | |||
| FI1 | HOLD | 01/02/2024 | 01/12/2024 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM (The plan sheets submitted need to be separated and individually electronically signed). (We need digitally signed plans for review) (Plans submitted online must be digitally signed. There is a guide to digital signatures on the permit portal page). http://docs.palmcoastgov.com/departments/building/online/digital-signatures.pdf 1. OK 2. OK 3. OK 4. OK 5. OK 6. OK 7. OK 8. OK 9. OK 10. OK 11. OK 12. OK 13. Response could not be accepted, the riser diagrams on Building 9 still shows only one gauge. Please provide pressure gauges for supply and system side of riser per NFPA 13r 6.12.1 and 6.12.2 | |||
| FI1 | HOLD | 12/18/2023 | 01/02/2024 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM The response could not be accepted, (we need digitally signed plans for review), All plan pages need digital signatures), (Plans submitted online must be digitally signed. There is a guide to digital signatures on the permit portal page). http://docs.palmcoastgov.com/departments/building/online/digital-signatures.pdf 1. No permit may be issued for any building construction, erection, alteration, modification, repair, or addition unless the applicant for such permit provides to the enforcing agency which issues the permit any of the following documents which apply to the construction for which the permit is to be issued and which shall be prepared by or under the direction of an engineer registered under Chapter 471, Florida Statutes: 105.3.1.2 (please provide signed sealed sprinkler design for review). Fire sprinkler documents for any new building or addition which includes a fire sprinkler system which contains 50 or more sprinkler heads. Personnel as authorized by chapter 633 Florida Statutes, may design a fire sprinkler system of 49 or fewer heads.. 2. Please upload manufacture docs and device specs with listings for review. 3. The plans are not clear as to the dimensions and clearances at the stairs, landings, and doorways. Please be sure there is no encroachment by any components of the sprinkler riser, valves, assembly, supply/fdc etc. into the required minimum dimensions of the floor level/landings at stairs and required door landing/door swing. 4. Per the attached e-mail, there will be a separate permit for the FDC and Standpipe for the courtyard standpipe as discussed with CBO Buckley. Please remove the standpipe and FDC form the courtyard as this will be a separate permit. Also, the FDC would need to be moved of the building per the AHJ and the interior courtyard FDC would need to be changed to a sandpipe connection as the is not and FDC connection 5. On Sheet 9 of 37 the fire calculation plate shows three standpipes, there are four standpipes please correct the calculation plate for review. FBC 107.3 6. Please upload all pertinent information on the fire pump as per NFPA 20 7. Please upload the material specs for the fire pump and jocky pump. FBC 107.3 8. Please reconcile the notes, schematics, and Sprinkler riser diagram on sheet 3 of 37 (Notes and schematics do not match). FBC 107.3. 9. Note 10, 15, and 15 E. on sheet 3 of 37 calls for year versions of 2007 (The correct year should be 2016). 10. Note 15 E. on sheet 3 of 37 should include Both NFPA 13r and FBC section 903 for notes regarding open breezeways, open ended breezeways, corridors, stairs, etc. 11. Please add a note stating the standpipes/sprinklers will be erected such that they will be available and operable for firefighting on and with each level of vertical construction per FBC 903.2.1.2 12. Please supply legend for sprinkler types on the sprinkler pages 13. Please provide pressure gauges for supply and system side of riser per NFPA 13r 6.12.1 and 6.12.2 | |||
| FI1 | HOLD | 11/03/2023 | 11/17/2023 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM BUILDING DIVISION (FIRE) REVIEW WAS NOT COMPLETED. NO RESPONSE LETTER PROVIDED BY DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE INDICATING REVISIONS THAT CORRECTIONS WERE MADE TO THE PLANS TO ADDRESS REVIEW COMMENTS BELOW AND NO INDICATION OF PLAN SHEETS WHERE REVISIONS WERE MADE. IT IS CUSTOMARY TO PROVIDE A RESPONSE LETTER WITH THIS INFORMATION. PLEASE PROVIDE RESPONSE LETTER FOR REVIEW OF SUBMITTAL 1. No permit may be issued for any building construction, erection, alteration, modification, repair, or addition unless the applicant for such permit provides to the enforcing agency which issues the permit any of the following documents which apply to the construction for which the permit is to be issued and which shall be prepared by or under the direction of an engineer registered under Chapter 471, Florida Statutes: 105.3.1.2 (please provide signed sealed sprinkler design for review). Fire sprinkler documents for any new building or addition which includes a fire sprinkler system which contains 50 or more sprinkler heads. Personnel as authorized by chapter 633 Florida Statutes, may design a fire sprinkler system of 49 or fewer heads.. 2. Please upload manufacture docs and device specs with listings for review. 3. The plans are not clear as to the dimensions and clearances at the stairs, landings, and doorways. Please be sure there is no encroachment by any components of the sprinkler riser, valves, assembly, supply/fdc etc. into the required minimum dimensions of the floor level/landings at stairs and required door landing/door swing. 4. Per the attached e-mail, there will be a separate permit for the FDC and Standpipe for the courtyard standpipe as discussed with CBO Buckley. Please remove the standpipe and FDC form the courtyard as this will be a separate permit. Also, the FDC would need to be moved of the building per the AHJ and the interior courtyard FDC would need to be changed to a sandpipe connection as the is not and FDC connection 5. On Sheet 9 of 37 the fire calculation plate shows three standpipes, there are four standpipes please correct the calculation plate for review. FBC 107.3 6. Please upload all pertinent information on the fire pump as per NFPA 20 7. Please upload the material specs for the fire pump and jocky pump. FBC 107.3 8. Please reconcile the notes, schematics, and Sprinkler riser diagram on sheet 3 of 37 (Notes and schematics do not match). FBC 107.3. 9. Note 10, 15, and 15 E. on sheet 3 of 37 calls for year versions of 2007 (The correct year should be 2016). 10. Note 15 E. on sheet 3 of 37 should include Both NFPA 13r and FBC section 903 for notes regarding open breezeways, open ended breezeways, corridors, stairs, etc. 11. Please add a note stating the standpipes/sprinklers will be erected such that they will be available and operable for firefighting on and with each level of vertical construction per FBC 903.2.1.2 12. Please supply legend for sprinkler types on the sprinkler pages 13. Please provide pressure gauges for supply and system side of riser per NFPA 13r 6.12.1 and 6.12.2 | |||
| FI1 | HOLD | 09/13/2023 | 09/26/2023 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM 1. No permit may be issued for any building construction, erection, alteration, modification, repair, or addition unless the applicant for such permit provides to the enforcing agency which issues the permit any of the following documents which apply to the construction for which the permit is to be issued and which shall be prepared by or under the direction of an engineer registered under Chapter 471, Florida Statutes: 105.3.1.2 (please provide signed sealed sprinkler design for review). Fire sprinkler documents for any new building or addition which includes a fire sprinkler system which contains 50 or more sprinkler heads. Personnel as authorized by chapter 633 Florida Statutes, may design a fire sprinkler system of 49 or fewer heads.. 2. Please upload manufacture docs and device specs with listings for review. 3. The plans are not clear as to the dimensions and clearances at the stairs, landings, and doorways. Please be sure there is no encroachment by any components of the sprinkler riser, valves, assembly, supply/fdc etc. into the required minimum dimensions of the floor level/landings at stairs and required door landing/door swing. 4. Per the attached e-mail, there will be a separate permit for the FDC and Standpipe for the courtyard standpipe as discussed with CBO Buckley. Please remove the standpipe and FDC form the courtyard as this will be a separate permit. Also, the FDC would need to be moved of the building per the AHJ and the interior courtyard FDC would need to be changed to a sandpipe connection as the is not and FDC connection 5. On Sheet 9 of 37 the fire calculation plate shows three standpipes, there are four standpipes please correct the calculation plate for review. FBC 107.3 6. Please upload all pertinent information on the fire pump as per NFPA 20 7. Please upload the material specs for the fire pump and jocky pump. FBC 107.3 8. Please reconcile the notes, schematics, and Sprinkler riser diagram on sheet 3 of 37 (Notes and schematics do not match). FBC 107.3. 9. Note 10, 15, and 15 E. on sheet 3 of 37 calls for year versions of 2007 (The correct year should be 2016). 10. Note 15 E. on sheet 3 of 37 should include Both NFPA 13r and FBC section 903 for notes regarding open breezeways, open ended breezeways, corridors, stairs, etc. 11. Please add a note stating the standpipes/sprinklers will be erected such that they will be available and operable for firefighting on and with each level of vertical construction per FBC 903.2.1.2 12. Please supply legend for sprinkler types on the sprinkler pages 13. Please provide pressure gauges for supply and system side of riser per NFPA 13r 6.12.1 and 6.12.2 | |||
| UD1 | COMPLETE | 09/13/2023 | 09/19/2023 |
| Note: Released By: BRICE WRIGHT - (386)986-2398 - BWRIGHT@PALMCOASTGOV.COM |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 50% | (¤188.50) | 02/08/2024 |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | 02/08/2024 |
| INSPECTION - FIRE COMMERCIAL | ¤72.00 | 02/08/2024 |
| PLAN REVIEW - COMMERCIAL | ¤230.00 | 02/08/2024 |
| SURCHARGE FS 533.721 | ¤2.00 | 02/08/2024 |
| SURCHARGE - FS 468.631 | ¤2.83 | 02/08/2024 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤193.33 |