Permit #2023100085

Permit Details

Status: COED

Parcel Id: 42-10-30-3210-00000-0140
CONDITIONED SPACE: 3265 sqft
GARAGE: 893 sqft
OPENED PORCH (WITH ROOF) : 648 sqft
OPENED PORCH (WITH ROOF) : 64 sqft
Total Square Footage: 4870 sqft
Block: 00000
Subdivision: 2094 - CONSERVATORY AT HAMMOCK BEACH
Job Phone: (386) 446-5850
Location Address: 812 LOBLOLLY CT
Type: BR - BUILDING RESIDENTIAL -SINGLE FAMILY
Issue Date: 12/01/2023
NOC: RECORDED
Applicant name: CHARLES DALLAS RINEK
Owner: DOLLESLAGER ROGER & DINA K H&W

Address

PO BOX 352692

PALM COAST, FL 32135

Lot: 0140
Contracted Stated Job Value: ¤800,000.00
Job Description: New single family
Type: CN

Contractor

CHARLES RINEK CONSTRUCTION, INC.
Status Location Address State License Number Phone Fax
ACTIVE

P. O. Box 352502

Palm Coast, FL 32137

CGC046080 (Exp: 08/31/2026) (386) 446-5850 (386)445-9992

Sub Contractors

JONATHAN M PEARSON
Status Location Address State License Number Phone Fax
ACTIVE

209 N FORSYTH ST

BUNNELL, FL 32110

CFC1425941 (Exp: 08/31/2026) 386-597-0944 386-437-4996
PEDRO DANIEL CHINCHILLA
Status Location Address State License Number Phone
ACTIVE

324 COVENT GARDENS PL

DELTONA, FL 32725

CCC1333997 (Exp: 08/31/2026) 386-679-6228
ROBERT J CATES
Status Location Address State License Number Phone
INACTIVE

400 NORTH US HIGHWAY 1

ORMOND BEACH, FL 32174

EC13003957 (Exp: 08/31/2026) 386-672-8494
SHAWN MICHAEL HISS
Status Location Address State License Number Phone
ACTIVE

1315 LPGA BLVD

HOLLY HILL, FL 32117

CAC1813585 (Exp: 08/31/2026) (386)672-8688
PHILIP ALAN KENOVICH
Status Location Address State License Number Phone
ACTIVE

P.O. BOX 1470

HOLLY HILL, FL 32117

LG270 (Exp: 08/31/2026) (386)672-2507
MARK B SOWERS
Status Location Address State License Number Phone
ACTIVE

609 FOURTH ST

BUNNELL, FL 32110

35616 (Exp: 08/31/2026) 386-225-1753
CHARLES K DAVIS
Status Location Address State License Number Phone
ACTIVE

3000 E MOODY BLVD BLDG 2

BUNNELL , FL 32110

EC13004270 (Exp: 08/31/2026) 386-931-6614

Inspection History

Type Request Date Result Inspector
BLD - BUILDING FINAL 02/04/2025 FINAL APPROVED HCAMACHO
Note: 2/3/2025 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JSTEWART 2/3/2025 12:28:21 PM *** Items listed previous inspection are rectified. Life Saftey: Unable to final, Building final until Gas connection from Propane tank to Building entry is complete, test gauge still on the building entry point. (Part of Permit, no seperate permit). G2417.1.1 (406.1.1) Inspections. 1/31/2025 - PREVIOUS INSPECTION NOTES 1. Missing lock on Wall Oven breaker. 2. Missing lock on Cook top Breaker. 3. Wrong Breaker on "A" Airhandler. 4. Missing 6" A/C Vent cover on the outside soffit. 5. Missing Termite Certificate on Breaker Panel.
BLD - BUILDING FINAL 02/03/2025 Disapproved - NO FEE JSTEWART
Note: *** NOTES ADDED BY JSTEWART 2/3/2025 12:28:21 PM *** Items listed previous inspection are rectified. Life Saftey: Unable to final, Building final until Gas connection from Propane tank to Building entry is complete, test gauge still on the building entry point. (Part of Permit, no seperate permit). G2417.1.1 (406.1.1) Inspections. 1/31/2025 - PREVIOUS INSPECTION NOTES 1. Missing lock on Wall Oven breaker. 2. Missing lock on Cook top Breaker. 3. Wrong Breaker on "A" Airhandler. 4. Missing 6" A/C Vent cover on the outside soffit. 5. Missing Termite Certificate on Breaker Panel.
BLD - BUILDING FINAL 01/31/2025 Disapproved - NO FEE HCAMACHO
Note: 1. Missing lock on Wall Oven breaker. 2. Missing lock on Cook top Breaker. 3. Wrong Breaker on "A" Airhandler. 4. Missing 6" A/C Vent cover on the outside soffit. 5. Missing Termite Certificate on Breaker Panel.
ROW - FINAL APRON (AFTER POUR) 01/31/2025 APPROVED EMADISON
Note: ** At the time of the inspection all minimum city requirements were met. It is the builder’s responsibility to ensure that nothing changes after this Inspection is approved.
ROW - STORMWATER FINAL 01/31/2025 APPROVED EMADISON
Note: ** At the time of the inspection all minimum city requirements were met. It is the builder’s responsibility to ensure that nothing changes after this Inspection is approved.
U -UTILITY RESIDENTIAL FINAL 01/30/2025 APPROVED - AS NOTED LFITZGERALD
Note: irrigation meter is instaled where is not required/needed since this community is master reclaim irrigatin-this should of been addressed n the u-crossinspectin-since owner would be charged monthly for something not beinguse-i informed Donald-bldg super to contact utility
ROW - FINAL APRON (AFTER POUR) 01/30/2025 Disapproved - NO FEE EMADISON
Note: ** 01/30/25 NEED TO SET AND SECURE PAVERS THAT WERE REMOVED AT GARAGE OPENING ON RIGHT SIDE WHERE GUTTER DRAIN WAS INSTALLED ** BRASS CLEANOUT CAP NEEDS TO BE LOWERED SO IT IS FLUCH WITH PAVERS NOT SITTING ON TOP OF PAVERS
ROW- FINAL SURVEY/GRADING CERTIFICATION 01/29/2025 APPROVED EMADISON
ROW FIELD SURVEY /GRADING CERTIFICATION 01/29/2025 APPROVED - AS NOTED EMADISON
Note: ** 01/29/25 BEFORE ROW STORMWATER FINAL BUILDER NEEDS TO RAISE ALL POP-UP DRAINS ON TOP OF THE SOD TO PREVENT WASH OUTS FROM UNDERNEATH SOD
ROW- PRE-APRON (PRE-POUR) 11/21/2024 APPROVED PFLANAGAN
Note: READY TO LAY PAVERS ------------------------------------------------------------------------- 11/8/2024 - PREVIOUS INSPECTION NOTES READY TO POUR APRON AND PAVER RESTRAINTS ONLY. BEFORE NEXT PRE POUR ALL PAVER BASE NEEDS TO SPREAD AND COMPACTED TO CITY'S STANDARDS WITH NO PAVERS LAID AT THE TIME OF THE INSPECTION. ALL CONCRETE NEEDS TO BE A MINIMUM OF 3000PSI WITH FIBER OR WITH METAL MESH IN THE CONCRETE TO MEET ALL CITY'S STANDARDS. At the time of the inspection all minimum city requirements were met. It is the builders and the homowners responsibility to ensure that nothing changes after this Inspection is approved. It will not be on the city if any changes after this inspection.
ROW- PAVER RESTRAINTS 11/08/2024 APPROVED PFLANAGAN
Note: ALL CONCRETE NEEDS TO BE A MINIMUM OF 3000PSI WITH FIBER OR WITH METAL MESH IN THE CONCRETE TO MEET ALL CITY'S STANDARDS. At the time of the inspection all minimum city requirements were met. It is the builders and the homowners responsibility to ensure that nothing changes after this Inspection is approved. It will not be on the city if any changes after this inspection.
ROW- PRE-APRON (PRE-POUR) 11/08/2024 PARTIALLY APPROVED PFLANAGAN
Note: READY TO POUR APRON AND PAVER RESTRAINTS ONLY. BEFORE NEXT PRE POUR ALL PAVER BASE NEEDS TO SPREAD AND COMPACTED TO CITY'S STANDARDS WITH NO PAVERS LAID AT THE TIME OF THE INSPECTION. ALL CONCRETE NEEDS TO BE A MINIMUM OF 3000PSI WITH FIBER OR WITH METAL MESH IN THE CONCRETE TO MEET ALL CITY'S STANDARDS. At the time of the inspection all minimum city requirements were met. It is the builders and the homowners responsibility to ensure that nothing changes after this Inspection is approved. It will not be on the city if any changes after this inspection.
ELECTRIC - EARLY POWER 08/08/2024 APPROVED JSTEWART
Note: 8/7/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JSTEWART 8/7/2024 1:36:54 PM *** 1. exterior outlet next to hose bibb (left side) needs to be safed off. 110.27 Live parts guarded 2. Floor outlet romex needs caps installed. 110.27 Live parts guarded 3. Please post address for Emergency services. FBCR 319.1
ELECTRIC - EARLY POWER 08/07/2024 Disapproved -FEE REQUIRED JSTEWART
Note: *** NOTES ADDED BY JSTEWART 8/7/2024 1:36:54 PM *** 1. exterior outlet next to hose bibb (left side) needs to be safed off. 110.27 Live parts guarded 2. Floor outlet romex needs caps installed. 110.27 Live parts guarded 3. Please post address for Emergency services. FBCR 319.1
INSULATION 06/12/2024 APPROVED JSTEWART
Note: 6/11/2024 - PREVIOUS INSPECTION NOTES 1. Length of the fire place wall. Seal the chase completely for fire blocking requirements. FBCR 302.1 2. Dryer flex duct cannot be used at the bathroom exhaust fan. FBCR- 1502.4.1 Inspector Notes from Inspection 2420 1. Service wire not installed to interior electirical sub panel. 2. Rear right side bath fan. Exhaust duct not connected to fan. 3. 5' head test is not holding water. Check for corrections at the insulation inspection.
LATH/BRICK/ WATER BARRIER 06/12/2024 APPROVED JSTEWART
Note: Inspector Notes from Inspection 2420 1. Service wire not installed to interior electirical sub panel. 2. Rear right side bath fan. Exhaust duct not connected to fan. 3. 5' head test is not holding water. Check for corrections at the insulation inspection.
INSULATION 06/11/2024 Disapproved -FEE REQUIRED JWALKER
Note: 1. Length of the fire place wall. Seal the chase completely for fire blocking requirements. FBCR 302.1 2. Dryer flex duct cannot be used at the bathroom exhaust fan. FBCR- 1502.4.1 Inspector Notes from Inspection 2420 1. Service wire not installed to interior electirical sub panel. 2. Rear right side bath fan. Exhaust duct not connected to fan. 3. 5' head test is not holding water. Check for corrections at the insulation inspection.
ALL ROUGH 05/31/2024 APPROVED - AS NOTED JWALKER
Note: 1. Service wire not installed to interior electirical sub panel. 2. Rear right side bath fan. Exhaust duct not connected to fan. 3. 5' head test is not holding water. Check for corrections at the insulation inspection.
WALL SHEATHING 05/23/2024 APPROVED JWALKER
GRAVITY SEWER TEST 05/23/2024 APPROVED - AS NOTED MGIBSON
Note: THIS WAS A VIRTUAL INSPECTION
SEWER TIE IN 05/23/2024 APPROVED - AS NOTED MGIBSON
Note: THIS WAS A VIRTUAL INSPECTION
U-CROSS CONNECTION 05/23/2024 APPROVED DHANEY
ROOF VALLEY & METAL 04/30/2024 APPROVED FWILLIS
Note: Inspector Notes from Inspection 2460 3/27/24- Missing (3) points of connection with a VGT simpson girder tie downs at B01 per plans F5. Will check at all Rough.
ELECTRIC-TUG 04/19/2024 APPROVED RMARTIN
ROOF SHEATHING / BRACES/TIES/DOWN CELL 03/27/2024 APPROVED - AS NOTED JSTEWART
Note: 3/27/24- Missing (3) points of connection with a VGT simpson girder tie downs at B01 per plans F5. Will check at all Rough.
FOUND SURVEY APPROVED (OFFICE) 03/26/2024 APPROVED AMOBLEY
TIE BEAM / LINTEL 02/13/2024 APPROVED JSTEWART
MONOLITHIC SLAB 01/24/2024 Disapproved - NO FEE AGAETANO
Note: 01-24-2024 Please provide a clean, complete, organized set of approved drawings for all inspections. Missing pages. Approved drawings are dirty and disorganized.
MONOLITHIC SLAB 01/24/2024 APPROVED AGAETANO
Note: 1/24/2024 - PREVIOUS INSPECTION NOTES 01-24-2024 Please provide a clean, complete, organized set of approved drawings for all inspections. Missing pages. Approved drawings are dirty and disorganized. 01-24-2024 Inspector returned to job site.
PLUMBING 1ST ROUGH UNDERGROUND 01/18/2024 APPROVED MGIBSON
WATER METER INSTALLATION REQUEST 12/08/2023 APPROVED BVITALE

Review History

Department Status Date In Date Out
BLD COMPLETE 01/23/2025 01/28/2025
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
ELEC CANCEL 11/07/2024 11/14/2024
SW1 COMPLETE 11/07/2024 11/08/2024
Note: Released By: JOHN HOWARD - - JHOWARD@PALMCOASTGOV.COM
ZON COMPLETE 11/07/2024 11/07/2024
Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM
GAS COMPLETE 05/22/2024 05/24/2024
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
ENGIN1 COMPLETE 03/26/2024 03/26/2024
Note: Released By: SCOTT THOMAS - (386)986-3780 - STHOMAS@PALMCOASTGOV.COM
ZON COMPLETE 03/26/2024 03/26/2024
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
BLD COMPLETE 01/29/2024 01/30/2024
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
BLD HOLD 01/26/2024 01/29/2024
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Need shop drawing approval stamp from the engineer of record who designed the house.
SW1 COMPLETE 11/21/2023 12/01/2023
Note: Released By: JEFF CREWS - - JCREWS@PALMCOASTGOV.COM
ENGIN1 COMPLETE 11/21/2023 11/21/2023
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
ZON COMPLETE 11/21/2023 11/21/2023
Note: Released By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM
ZON COMPLETE 10/17/2023 10/18/2023
Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM
SW1 HOLD 10/17/2023 10/25/2023
Note: Held By: GABRIEL BERTOLA - (386)986-7660 - GBERTOLA@PALMCOASTGOV.COM LOT GRADING PLAN FFE IS 25 IN YOU SITE PLAN 26.50. REVISE THE SITE PLAN
ELEC COMPLETE 10/17/2023 10/19/2023
Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM
BLD COMPLETE 10/17/2023 10/18/2023
Note: Released By: JPI
MECH COMPLETE 10/17/2023 10/18/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
URB COMPLETE 10/04/2023 10/05/2023
Note: Released By: JOHN BEAUDET - (386)986-2456 - JBEAUDET@PALMCOASTGOV.COM
BLD HOLD 10/03/2023 10/06/2023
Note: Held By: JPI 1. Per City Truss Submittal Requirements dated April 15, 2023, provide the truss plan packet signed and sealed by a licensed design professional including a completed shop drawing approval stamp on the truss cover sheet.
CUSVC COMPLETE 10/03/2023 10/09/2023
Note: Released By: CYNTHIA SCHWEERS - - CSCHWEERS@PALMCOASSTGOV.COM
ELEC HOLD 10/03/2023 10/05/2023
Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Need correct outlet spacing in bed 3. NEC 2017 210.52 2. Need outlet in hallway by bed 2. NEC 2017 210.52 (H) 3. Submit electircal load cals.
ENGIN1 COMPLETE 10/03/2023 10/04/2023
Note: Released By: TIM BAKER - (386)986-4726 - TBAKER@PALMCOASTGOV.COM
GAS COMPLETE 10/03/2023 10/09/2023
Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM
LOCATE COMPLETE 10/03/2023 10/05/2023
Note: Released By: CANDACE BOWERMASTER - - CBOWERMASTER@PALMCOASTGOV.COM
MECH HOLD 10/03/2023 10/09/2023
Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Energy Calcs need to be signed by the owner/ owner agent below the preparer per R103.1.1.2 FBC Energy Conservation 2020 7Th edition
SW1 HOLD 10/03/2023 10/04/2023
Note: Held By: PARREN FLANAGAN - (386)986-2392 - PFLANAGAN@PALMCOASTGOV.COM DRAINAGE ON THE RIGHT DOESN'T WORK NEED TO REDO THE PROPOSED SO WATER WILL FLOW CORRECTLY AWAY FROM HOUSE AND TO OUTFALL
ZON HOLD 10/03/2023 10/04/2023
Note: Held By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM Plans are for a one story home. Site plan/survey states a two story.
BLD HOLD 10/03/2023 10/06/2023
Note: Held By: JPI duplicate

Fees & Payments

(Permit is not ready for pickup until the permit has been processed and fees appear)
Description Amount Due Date Paid
CONTRACTOR CHANGE ¤20.00 01/31/2025
CONTRACTOR CHANGE ¤20.00 01/31/2025
REINSPECTION RESIDENTIAL ¤40.00 01/31/2025
REINSPECTION RESIDENTIAL ¤40.00 01/31/2025
CONNECTION FEES ¤25.00 12/01/2023
WATER-METER ¤505.39 12/01/2023
WATER-METER ¤505.39 12/01/2023
WATER- TURN ON ¤25.00 12/01/2023
ADJUSTMENT 50% (¤1,427.00) 12/01/2023
ADMINISTRATIVE RESIDENTIAL ¤30.00 12/01/2023
INSPECTION - RESIDENTIAL ¤2,200.00 12/01/2023
PLAN REVIEW - RESIDENTIAL ¤624.00 12/01/2023
FC IMPACT FEE EMS ¤62.00 12/01/2023
IMPACT FEE FIRE ¤428.09 12/01/2023
FC IMPACT FEE LAW ENFORCEMENT ¤218.00 12/01/2023
FC IMPACT FEE LIBRARY ¤268.00 12/01/2023
IMPACT FEE PARKS ¤1,800.99 12/01/2023
IMPACT FEE SCHOOL ¤5,450.00 12/01/2023
IMPACT FEE TRANSPORTATION ¤3,311.00 12/01/2023
WATER -IRRIGATION INSPECTION ¤25.00 12/01/2023
SURCHARGE FS 533.721 ¤14.27 12/01/2023
SURCHARGE - FS 468.631 ¤21.41 12/01/2023
SW ENG - FOUNDATION SURVEY ¤20.00 12/01/2023
SW ENG INSPECTION 80 ¤80.00 12/01/2023
SW ENG PRE APRON ¤30.00 12/01/2023
SW ENG - REVIEW 20 ¤20.00 12/01/2023
SW ENG RES REVIEW 200 ¤200.00 12/01/2023
SEWER INSPECTION ¤25.00 12/01/2023
SITE PLAN 30 ¤30.00 12/01/2023
Fees Total Due: ¤0.00 Total Paid: ¤14,611.54