Permit #2023101311
Permit Details
Status: COED
| Parcel Id: 07-11-31-7011-00090-0300 |
| Block: 00090 |
| Subdivision: 2193 - SECTION 11-BELLE TERRE |
| Job Phone: 904-750-3404 |
| Location Address: 112 BEACHWAY DR |
| Type: BIA - BUILDING INTERIOR EXTERIOR ALTERATION |
| Issue Date: 11/08/2023 |
| NOC: RECORDED |
| Applicant name: PATRICK ANTHONY PIZZULO |
| Owner: WHITNEY ELIZABETH M TRUSTEE |
|
Address 112 BEACHWAY DRIVE PALM COAST, FL 32137 |
| Lot: 0300 |
| Contracted Stated Job Value: ¤36,506.61 |
| Job Description: replace insulation and drywall due to fire damage |
| Type: CN |
Contractor
ONERESTORE, LLC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
1540 SW 5TH AVE, SUITE 101 SAINT AUGUSTINE, FL 32084 |
CRC1326353 (Exp: 08/31/2026) | 904-750-3404 |
Sub Contractors
STEPHEN MICHAEL BETROS JR
| Status | Location Address | Mailing Address | State License Number | Phone |
| ACTIVE |
5215 HIGHWAY AVE JACKSONVILLE, FL 32254 |
STE 102 JACKSONVILLE, FL 32254 |
CFC1428972 (Exp: 08/31/2026) | 904-683-1968 |
JAMES ISAAC LEWIS
| Status | Location Address | State License Number | Phone |
| INACTIVE |
6627 MORSE GLEN LANE , 0 |
EC13010228 (Exp: 08/31/2024) | 850-221-4853 |
Inspection History
| Type | Request Date | Result | Inspector |
| BLD - BUILDING FINAL | 05/20/2024 | CANCELLED BY APPLICANT | WEB |
| BLD - BUILDING FINAL | 05/20/2024 | FINAL APPROVED | JSTEWART |
| ELECTRIC FINAL | 05/16/2024 | APPROVED | MKRASKI |
| Note: 5/14/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JSTEWART 5/14/2024 3:12:03 PM *** Breaker panel enclosure is not installed with live terminals exposed to possible injury. NEC 230.62 / 110.27 Live parts guarded against accidental contact 5/10/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JSTEWART 5/10/2024 2:08:22 PM *** previous note not rectified......1 kitchen counter top outlet is not GFCI protected (tested). Note: for building final please check power at master bath counter outlets. 5/3/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JSTEWART 5/3/2024 2:16:41 PM *** 5/3/24- 1. all Kitchen outlets need to be GFCI protected. 2. Please verify 2 circuits in Kitchen. 3. Outlet for disposal and dishwasher need to be accessible. 4. please safe off Microwave outlet in cabinet. | |||
| ELECTRIC FINAL | 05/14/2024 | Disapproved -FEE REQUIRED | JSTEWART |
| Note: *** NOTES ADDED BY JSTEWART 5/14/2024 3:12:03 PM *** Breaker panel enclosure is not installed with live terminals exposed to possible injury. NEC 230.62 / 110.27 Live parts guarded against accidental contact 5/10/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JSTEWART 5/10/2024 2:08:22 PM *** previous note not rectified......1 kitchen counter top outlet is not GFCI protected (tested). Note: for building final please check power at master bath counter outlets. 5/3/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JSTEWART 5/3/2024 2:16:41 PM *** 5/3/24- 1. all Kitchen outlets need to be GFCI protected. 2. Please verify 2 circuits in Kitchen. 3. Outlet for disposal and dishwasher need to be accessible. 4. please safe off Microwave outlet in cabinet. | |||
| ELECTRIC FINAL | 05/10/2024 | Disapproved - NO FEE | JSTEWART |
| Note: *** NOTES ADDED BY JSTEWART 5/10/2024 2:08:22 PM *** previous note not rectified......1 kitchen counter top outlet is not GFCI protected (tested). Note: for building final please check power at master bath counter outlets. 5/3/2024 - PREVIOUS INSPECTION NOTES *** NOTES ADDED BY JSTEWART 5/3/2024 2:16:41 PM *** 5/3/24- 1. all Kitchen outlets need to be GFCI protected. 2. Please verify 2 circuits in Kitchen. 3. Outlet for disposal and dishwasher need to be accessible. 4. please safe off Microwave outlet in cabinet. | |||
| PLUMBING FINAL | 05/03/2024 | APPROVED | MGIBSON |
| Note: 4/29/2024 - PREVIOUS INSPECTION NOTES New inspection due to canceled inspection 4/1/2024 - PREVIOUS INSPECTION NOTES WAS CONTACTED BY CONTRACTOR IN REFRENCE TO ARRIVAL TIME. TOLD HIM BETWEEN 12/1PM. CALLED HIM BACK NO ANSWER. TEXT HIM NO RESPONSE, NEED TO SCHEDULE CORRECT INSPECTION. | |||
| ELECTRIC FINAL | 05/03/2024 | Disapproved - NO FEE | JSTEWART |
| Note: *** NOTES ADDED BY JSTEWART 5/3/2024 2:16:41 PM *** 5/3/24- 1. all Kitchen outlets need to be GFCI protected. 2. Please verify 2 circuits in Kitchen. 3. Outlet for disposal and dishwasher need to be accessible. 4. please safe off Microwave outlet in cabinet. | |||
| PLUMBING FINAL | 04/29/2024 | CANCELLED BY APPLICANT | MGIBSON |
| Note: New inspection due to canceled inspection 4/1/2024 - PREVIOUS INSPECTION NOTES WAS CONTACTED BY CONTRACTOR IN REFRENCE TO ARRIVAL TIME. TOLD HIM BETWEEN 12/1PM. CALLED HIM BACK NO ANSWER. TEXT HIM NO RESPONSE, NEED TO SCHEDULE CORRECT INSPECTION. | |||
| PLUMBING FINAL | 04/25/2024 | CANCELLED BY APPLICANT | WEB |
| Note: 4/1/2024 - PREVIOUS INSPECTION NOTES WAS CONTACTED BY CONTRACTOR IN REFRENCE TO ARRIVAL TIME. TOLD HIM BETWEEN 12/1PM. CALLED HIM BACK NO ANSWER. TEXT HIM NO RESPONSE, NEED TO SCHEDULE CORRECT INSPECTION. | |||
| PLUMBING FINAL | 04/01/2024 | Disapproved - NO FEE | MGIBSON |
| Note: WAS CONTACTED BY CONTRACTOR IN REFRENCE TO ARRIVAL TIME. TOLD HIM BETWEEN 12/1PM. CALLED HIM BACK NO ANSWER. TEXT HIM NO RESPONSE, NEED TO SCHEDULE CORRECT INSPECTION. | |||
| WINDOW FASTENING | 03/27/2024 | APPROVED | FWILLIS |
| Note: 3/26/2024 - PREVIOUS INSPECTION NOTES 3/26/24- Please add anchors to doors Per FL Product approval code. Please remove stucco from Fin windows for Nailing Inspection, Or Install Jamb anchoring to the Product aproval code. Not ready, Please check all windows and doors at reinspect. | |||
| WINDOW FASTENING | 03/26/2024 | Disapproved -FEE REQUIRED | JSTEWART |
| Note: 3/26/24- Please add anchors to doors Per FL Product approval code. Please remove stucco from Fin windows for Nailing Inspection, Or Install Jamb anchoring to the Product aproval code. Not ready, Please check all windows and doors at reinspect. | |||
| PLUMBING 1ST ROUGH UNDERGROUND | 03/25/2024 | APPROVED | MGIBSON |
| MONOLITHIC SLAB | 03/20/2024 | APPROVED | FWILLIS |
| MONOLITHIC SLAB | 03/19/2024 | CANCELLED BY APPLICANT | WEB |
| INSULATION | 02/01/2024 | APPROVED | FWILLIS |
| ALL ROUGH | 01/04/2024 | Disapproved -FEE REQUIRED | JSTEWART |
| Note: 1/4/24- Please have Power locked out to the main building (exposed wireing). Please seal duct work in attic entering Plenums. Please strap all duct work in attic to trusses. M1601.4.4 Support.....every 4ft. | |||
| PROJECT STATUS (OFFICE USE) | 12/12/2023 | APPROVED - AS NOTED | RMARTIN |
| Note: 12/12/23 Met the contractor on site with John Stewart, must open up drywall areas discussed, need to verify that the insulation that was changed out is sufficient to use. There was foil paper originally now they went to foam board but BETWEEN the furing strips. Ducts need to be supported and sealed, electrical needs to be per code 11/9/2023 - PREVIOUS INSPECTION NOTES 11/9/23- all drywall exept 2 rooms was removed and replaced, added and relocated electrical, replaced HVAC Ducts (supplys and returns). Framing added, and removed. Full Kitchen and Bathrooms demoed. Building dept will contact contractor on Inspections that will be required. Please contact Josh Munson with any questions or concerns 1-386-986-4736/ 1-386-529-4514. | |||
| PROJECT STATUS (OFFICE USE) | 11/09/2023 | Disapproved - NO FEE | JSTEWART |
| Note: 11/9/23- all drywall exept 2 rooms was removed and replaced, added and relocated electrical, replaced HVAC Ducts (supplys and returns). Framing added, and removed. Full Kitchen and Bathrooms demoed. Building dept will contact contractor on Inspections that will be required. Please contact Josh Munson with any questions or concerns 1-386-986-4736/ 1-386-529-4514. |
Review History
| Department | Status | Date In | Date Out |
| PLUM | COMPLETE | 05/16/2024 | 05/17/2024 |
| Note: Released By: JIM WALKER - (386)529-4112 - JWALKER@PALMCOASTGOV.COM | |||
| BLD | COMPLETE | 03/13/2024 | 03/18/2024 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| PLUM | HOLD | 03/13/2024 | 03/14/2024 |
| Note: Held By: JIM WALKER - - JWALKER@PALMCOASTGOV.COM Note on the plumbing work description states two shower pans will need to be purchased, cut and glued together. Provide manufacture specifications and instructions showing the process of cutting and gluing of the shower pan together. Or provide different details for shower pan. | |||
| PLUM | HOLD | 01/25/2024 | 01/26/2024 |
| Note: Held By: JIM WALKER - - JWALKER@PALMCOASTGOV.COM Please specify what plumbing will be done in the master bath. | |||
| BLD | HOLD | 01/18/2024 | 01/19/2024 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. We do not accept letters from home inspectors. | |||
| BADMIN | INFORMATION | 11/13/2023 | 11/13/2023 |
| Note: Marked INFORMATION By: SCOTT THOMAS - (386)986-3780 - STHOMAS@PALMCOASTGOV.COM NOC NOT RECORDED | |||
| BADMIN | INFORMATION | 11/12/2023 | 11/12/2023 |
| Note: Marked INFORMATION By: BARBIE BEMBRY - (386)986-3780 - BUILDINGDIVISION@PALMCOASTGOV.COM The NOC needs to be a recorded copy from the Flagler County Clerks office. When you re-upload, please name your file Notice of Commencement (do not add to the front of the file name) | |||
| BLD | COMPLETE | 11/01/2023 | 11/03/2023 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| ELEC | COMPLETE | 11/01/2023 | 11/03/2023 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. You will not get a inspection until there is a electrical permit on file. | |||
| BLD | HOLD | 10/29/2023 | 10/31/2023 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide location of repairs on plans | |||
| ELEC | HOLD | 10/29/2023 | 10/31/2023 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Was any electric damaged by the fire? If therre was you need to add plans and sub contractor to your permit. | |||
| MECH | CANCEL | 10/29/2023 | 10/31/2023 |
| PLUM | CANCEL | 10/29/2023 | 10/31/2023 |
| ZON | COMPLETE | 10/29/2023 | 10/30/2023 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM No zoning review required to do interior insulation and drywall only. |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 05/16/2024 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 05/13/2024 |
| CONTRACTOR CHANGE | ¤20.00 | 03/18/2024 |
| CONTRACTOR CHANGE | ¤20.00 | 01/25/2024 |
| REINSPECTION RESIDENTIAL | ¤40.00 | 01/17/2024 |
| ADJUSTMENT 50% | (¤98.38) | 11/08/2023 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 11/08/2023 |
| INSPECTION - RESIDENTIAL | ¤101.75 | 11/08/2023 |
| PLAN REVIEW - RESIDENTIAL | ¤65.00 | 11/08/2023 |
| SURCHARGE FS 533.721 | ¤2.00 | 11/08/2023 |
| SURCHARGE - FS 468.631 | ¤2.00 | 11/08/2023 |
| SITE PLAN 30 | ¤30.00 | 11/08/2023 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤292.37 |