Permit #2023120931
Permit Details
Status: CANCEL
| Parcel Id: 10-11-30-4937-00000-0230 |
| COMMERCIAL SQUARE FOOTAGE: 2580 sqft |
| Total Square Footage: 2580 sqft |
| Block: 00000 |
| Subdivision: 1150 - PALM COAST COMMERCIAL & INDUSTRIAL CENTER |
| Job Phone: 386-627-0430 |
| Location Address: 13 HARGROVE GRADE |
| Type: CA - COMM ADDITION |
| NOC: NO DOCUMENTATION |
| Applicant name: ANNA WIKTORIA LISOWSKI |
| Owner: FIRST OWL LLC |
|
Address 13 HARGROVE GRADE PALM COAST, FL 32137 |
| Lot: 0230 |
| Contracted Stated Job Value: ¤100,000.00 |
| Job Description: ADDITION |
| Type: CN |
Contractor
GOLDEN FOX HOME REMODELING, INC
| Status | Location Address | State License Number | Phone |
| ACTIVE |
72 HERNANDEZ AVE PALM COAST, FL 32137 |
CBC1259266 (Exp: 08/31/2026) | 386-627-0430 |
Sub Contractors
WILLIAM TODD SIKES
| Status | Location Address | State License Number | Phone |
| ACTIVE |
83 PORT ROYAL DR ST AUGUSTINE, FL 32084 |
EC0002726 (Exp: 08/31/2026) | 904-762-8762 |
Inspection History
| Type | Request Date | Result | Inspector |
| FOUND SURVEY APPROVED (OFFICE) | |||
| PLUMBING 1ST ROUGH | |||
| PLUMBING FINAL | |||
| HVAC ROUGH | |||
| HVAC FINAL | |||
| ELECTRIC 1ST ROUGH | |||
| ELECTRIC FINAL | |||
| MONOLITHIC SLAB | |||
| FOOTER | |||
| LINTEL | |||
| ALL ROUGH | |||
| ROOF SHEATHING / BRACE / TIE DOWN | |||
| ABOVE CEILING | |||
| INSULATION | |||
| BUILDING FINAL | |||
| FIRE FINAL | |||
| LDSC- LANDSCAPE FINAL | |||
| U - UTILITY COMMERCIAL FINAL |
Review History
| Department | Status | Date In | Date Out |
| PLFM | HOLD | 01/08/2024 | 01/10/2024 |
| Note: Held By: JORDAN MYERS, C.F.M - (386)986-4789 - JMYERS@PALMCOASTGOV.COM Flood Zone line needs to be shown on survey. There is Flood Zone A on this property, per 10.02.07.B in the Land Development Code, the Base Flood Elevation must be established by an engineer and submitted to the City for review. Additional comments may apply when the analysis is submitted. | |||
| ARCHR | HOLD | 12/22/2023 | 01/05/2024 |
| Note: Held By: RICHARD PICATAGI - (386)986-3760 - RPICATAGI@PALMCOASTGOV.COM Provide exterior colors for all materals with LRV and finish specs Provide foundation plantings along north wall and east wall of addition to include 30" ht. plants at 36" on center within and 3 feet wide mulched planting bed. | |||
| BLD | HOLD | 12/22/2023 | 01/08/2024 |
| Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM Incomplete plan submittal. Insufficient information provided to perform plan review. At a minimum provide the following for a complete plan review. 1. Provide cover sheet and index of plan sheets. 2. Provide architectural site plan. Site plan to be drawn in accordance with boundary survey plat. Show design flood infomration. Show location of SFHA Zone A on property. See FBC Section 107.2.6 for additional site plan requirements. 3. Provide occupancy classification(s) for existing building. Provide occupancy classification(s) for proposed addition. 4. Provide construction type of existing building. Provide construction type of proposed addition. 5. Provide building area and height analysis based on existing and proposed occupancy classification(s) and construction type. 6. Provide occupancy calculations and total occupant load for each occupancy classifications. 7. Provide means of egress / life safety plans. 8. Provide complete design criteria. 9. Provide wind exposure category. 10. Provide floor live loads. 11. Provide full exterior wall sections and framing details for exterior walls. From inside / interior finish through exterior cladding. NOT A COMPLETE LIST OF PLAN REVIEW COMMENTS. ADDITIONAL COMMENTS ARE LIKELY FORTHCOMING ONCE A COMPLETE PLAN SUBMITTAL IS MADE. | |||
| DSD | HOLD | 12/22/2023 | 01/02/2024 |
| Note: Held By: DAMARIS RAMIREZ - (386)986-3750 - DRAMIREZ@PALMCOASTGOV.COM Rear setback is 10'. Please increase rear setback to be 10' and not 9.5' Informational additional impact fee will be assessed. | |||
| ELEC | HOLD | 12/22/2023 | 12/28/2023 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. A complete review can not be done since the building addition has not been identified for its use or its occupancy. | |||
| FI1 | HOLD | 12/22/2023 | 01/05/2024 |
| Note: Held By: LEE MILLER - (386)986-3783 - WMILLER@PALMCOASTGOV.COM All comments below per the 2020 Florida Fire Prevention Code, 2020 FBC, and or 2020 Existing Building Code Please provide a written response to each comment below in a response letter and provide clouded response changes on plan sheets and add page locations for each response. Additional comments are likely after resubmittal. (Submittal is incomplete). 1. Please provide code analysis using the 2020 Florida Building code and the 2020 FFPC. 2. Please include in the code analysis, the existing and proposed occupancy classification per Section 302 2020 Florida Building Code-Building. 3. Please provide building construction type per Section 601 2020 Florida Building Code Building. 4. Need Life Safety Plan to include travel distance from most remote location to exit, travel distance to extinguishers, extinguisher location, Emergency lights and exit signs at egress/ingress and visible from any exit access path from any office/room and bathroom. Per FFPC 7th edition and AHJ | |||
| MECH | HOLD | 12/22/2023 | 01/09/2024 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Provide a full set of plans and code analysis showing use and occupoancy. 2, Provide ventilation calculation and means of ventilation This is not a ccomplete review. Further comment may arise after resubmittal. | |||
| PLENG | COMPLETE | 12/22/2023 | 12/22/2023 |
| Note: Released By: DENNIS R. LEAP, P.E. - (386)986-2482 - DLEAP@PALMCOASTGOV.COM | |||
| PLUM | HOLD | 12/22/2023 | 01/08/2024 |
| Note: Held By: PATRICK BUCKLEY - (386)986-3786 - PBUCKLEY@PALMCOASTGOV.COM Plumbing plan review not completed. Insufficient information provided to determine whether plumbing plan review is required. See Building Plan Review comments for more information. | |||
| UD1 | COMPLETE | 12/22/2023 | 12/28/2023 |
| Note: Released By: GREG DEGLER - - GDEGLER@PALMCOASTGOV.COM | |||
| ELEC | CANCEL | ||
| DSD | CANCEL | ||
| FI1 | CANCEL | ||
| ARCHR | CANCEL | ||
| PLUM | CANCEL | ||
| BLD | CANCEL | ||
| MECH | CANCEL | ||
| PLFM | CANCEL |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| ADJUSTMENT 50% | (¤445.00) | |
| ADMINISTRATIVE - COMMERCIAL | ¤75.00 | |
| INSPECTION COMMERCIAL | ¤700.00 | |
| PLAN REVIEW - COMMERCIAL | ¤115.00 | |
| FC IMPACT FEE EMS | ¤10.32 | |
| IMPACT FEE FIRE | ¤1,780.20 | |
| FC IMPACT FEE LAW ENFORCEMENT | ¤41.28 | |
| IMPACT FEE TRANSPORTATION | ¤4,824.60 | |
| SURCHARGE FS 533.721 | ¤4.45 | |
| SURCHARGE - FS 468.631 | ¤6.68 | |
| SW ENG REVIEW- 40 | ¤40.00 | |
| SITE PLAN 30 | ¤30.00 | |
| Fees | Total Due: ¤7,182.53 | Total Paid: ¤0.00 |