Permit #2024010559
Permit Details
Status: FINAL
| Parcel Id: 07-11-31-7023-00090-0010 |
| Total Square Footage: 4222 sqft |
| Block: 00090 |
| Subdivision: 2191 - SECTION 23-WYNNFIELD |
| Job Phone: 904-379-4189 |
| Location Address: 8 WHITCOCK LN |
| Type: GEN - GENERATOR |
| Issue Date: 01/19/2024 |
| NOC: RECORDED |
| Applicant name: JACOB HURLEY |
| Owner: PLACZKIEWICZ-RAJSKI SZYMON PIOTR & |
|
Address STEVEN ROBERT RAJSKI AMC PALM COAST, FL 32164 |
|
Address 8 WHITCOCK LANE PALM COAST, FL 32164 |
| Lot: 0010 |
| Contracted Stated Job Value: ¤17,738.34 |
| Job Description: 26KW GENERAC GENERATOR WITH AN AUTO T/S AND 2-120(G) AG LP TANKS |
| Type: CN |
Contractor
GENERATOR SUPERCENTER OF JACKSONVILLE
| Status | Location Address | State License Number | Phone |
| ACTIVE |
8081 PHILLIPS HWY STE 1 JACKSONVILLE, FL 32256 |
EC13009708 (Exp: 08/31/2026) | 904-379-4189 |
Inspection History
| Type | Request Date | Result | Inspector |
| ELECTRIC FINAL | 06/07/2024 | FINAL APPROVED | AGAETANO |
| Note: 5/22/2024 - PREVIOUS INSPECTION NOTES 4/29/2024 - PREVIOUS INSPECTION NOTES 1. Contractor not onsite, must meet inspector onsite for generator start up 2. Gas final must be approved befoe electric can be approved 05-22-2024 Electrician not on site for start up. | |||
| ELECTRIC FINAL | 05/22/2024 | Disapproved - NO FEE | AGAETANO |
| Note: 4/29/2024 - PREVIOUS INSPECTION NOTES 1. Contractor not onsite, must meet inspector onsite for generator start up 2. Gas final must be approved befoe electric can be approved 05-22-2024 Electrician not on site for start up. | |||
| GAS FINAL | 05/22/2024 | FINAL APPROVED | AGAETANO |
| Note: 4/29/2024 - PREVIOUS INSPECTION NOTES REGULATOR VENT SHALL BE AWAY FROM IGNITION SOURCE, A/C UNIT AND GENERATOR ARE BOTH IGNITION SOURCES | |||
| GAS FINAL | 04/29/2024 | Disapproved -FEE REQUIRED | MGIBSON |
| Note: REGULATOR VENT SHALL BE AWAY FROM IGNITION SOURCE, A/C UNIT AND GENERATOR ARE BOTH IGNITION SOURCES | |||
| ELECTRIC FINAL | 04/29/2024 | Disapproved - NO FEE | MKRASKI |
| Note: 1. Contractor not onsite, must meet inspector onsite for generator start up 2. Gas final must be approved befoe electric can be approved | |||
| GAS ROUGH | 03/14/2024 | APPROVED | MKRASKI |
| GAS ROUGH | 03/11/2024 | CANCELLED BY APPLICANT | WEB |
| Note: 3/6/2024 - PREVIOUS INSPECTION NOTES GATE WAS CLOSED RANG DOORBELL AND KNOCKED ON DOR WOKE UP DOGS, LEAVE GATE PROPT OPEN OR HAVE SOMEONE HOME FOR INSPECTIO, DON'T KNOW IF DOGS HAVE ACCESS TO FENCED AREA OUTSIDE | |||
| GAS ROUGH | 03/11/2024 | Disapproved - NO FEE | MGIBSON |
| Note: New inspection due to canceled inspection 3/6/2024 - PREVIOUS INSPECTION NOTES GATE WAS CLOSED RANG DOORBELL AND KNOCKED ON DOR WOKE UP DOGS, LEAVE GATE PROPT OPEN OR HAVE SOMEONE HOME FOR INSPECTIO, DON'T KNOW IF DOGS HAVE ACCESS TO FENCED AREA OUTSIDE NOT HOLDING 15LBS OF PRESSURE FOR 15 MIN, ALSO NEEDS TO HAVE SITE TUBES OR LEAVE DITCH OPEN FOR INSPECTION | |||
| GAS ROUGH | 03/06/2024 | Disapproved - NO FEE | MGIBSON |
| Note: GATE WAS CLOSED RANG DOORBELL AND KNOCKED ON DOR WOKE UP DOGS, LEAVE GATE PROPT OPEN OR HAVE SOMEONE HOME FOR INSPECTIO, DON'T KNOW IF DOGS HAVE ACCESS TO FENCED AREA OUTSIDE | |||
| GAS ROUGH | 02/29/2024 | CANCELLED BY APPLICANT | WEB |
Review History
| Department | Status | Date In | Date Out |
| ELEC | COMPLETE | 01/19/2024 | 01/19/2024 |
| Note: Released By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM | |||
| GAS | COMPLETE | 01/19/2024 | 01/19/2024 |
| Note: Released By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM | |||
| ZON | COMPLETE | 01/19/2024 | 01/19/2024 |
| Note: Released By: TRACEY DOAK - (386)986-3751 - TDOAK@PALMCOASTGOV.COM | |||
| ELEC | HOLD | 01/18/2024 | 01/18/2024 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Need to show location of Emergency shutdown for generator. NEC 2020 445.18 (D) 2nd REQUEST | |||
| GAS | HOLD | 01/18/2024 | 01/18/2024 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Clarify site plan. Has the location of tanks changes? 2. Provide gas line material and size on gas riser diagram | |||
| ZON | HOLD | 01/18/2024 | 01/18/2024 |
| Note: Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM Please clarify what has changed since the zoining approval as the placement of the tanks looks to be in the same place. | |||
| ELEC | HOLD | 01/18/2024 | 01/18/2024 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Switch on the back of the Generator is not in compliance with the new 2020 NEC 445.18. If you look in the 2020 NEC handbook it will give you a example of the what the switch needs to look like and do. | |||
| ZON | HOLD | 01/18/2024 | 01/18/2024 |
| Note: Held By: CINDY CHIRI-GONCALVES - (386)986-4737 - CGONCALVES@PALMCOASTGOV.COM repeat comment Please clarify what has changed since the zoining approval as the placement of the tanks looks to be in the same place. | |||
| GAS | HOLD | 01/18/2024 | 01/18/2024 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM 1. Clarify site plan. Has the location of tanks changes? 2. Provide gas line material and size on gas riser diagram | |||
| ELEC | HOLD | 01/16/2024 | 01/17/2024 |
| Note: Held By: JOSH MUNSON - (386)986-4736 - JMUNSON@PALMCOASTGOV.COM 1. Need to show location of Emergency shutdown for generator. NEC 2020 445.18 (D) | |||
| ZON | COMPLETE | 01/16/2024 | 01/16/2024 |
| Note: Released By: ALISHA MOBLEY - (386)986-3751 - AMOBLEY@PALMCOASTGOV.COM | |||
| GAS | HOLD | 01/16/2024 | 01/18/2024 |
| Note: Held By: CHRIS PISCITELLI - (386)986-2574 - CPISCITELLI@PALMCOASTGOV.COM Provide gas riser diagram |
Fees & Payments
(Permit is not ready for pickup until the permit has been processed and fees appear)
| Description | Amount Due | Date Paid |
| REINSPECTION RESIDENTIAL | ¤40.00 | 05/20/2024 |
| SURCHARGE FS 533.721 | ¤2.00 | 01/19/2024 |
| SURCHARGE - FS 468.631 | ¤2.00 | 01/19/2024 |
| SITE PLAN 15 | ¤15.00 | 01/19/2024 |
| ADJUSTMENT 50% | (¤61.25) | 01/19/2024 |
| ADMINISTRATIVE RESIDENTIAL | ¤30.00 | 01/19/2024 |
| INSPECTION - RESIDENTIAL | ¤60.00 | 01/19/2024 |
| PLAN REVIEW - MISC 32.50 | ¤32.50 | 01/19/2024 |
| Fees | Total Due: ¤0.00 | Total Paid: ¤120.25 |